Tender For Electrical Power Wiring In Cif Lab In Sbt Building At Jnu.; 1 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel / PVC conduit as required.. 2 3 x 1.5sq. mm 3 3 x 4 sq. mm 4 6 x 4 sq. mm 5 Supplying and fixing following size / modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 6 8 Module (125mmX125mm) 7 12 Module (200mmX150mm) 8 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box includingconnections but excluding modular plate etc. as required. 9 5/6 amps switch 10 Providing and Fixing following rating and braking capacity MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connection etc. as required. 11 125 amp, 16 KA TP (Thermal Magnetic Type) 12 Supplying and Fixing 5 amps to 32 amps rating, 240/415 volts, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 13 Single pole 14 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. 15 Supplying and making indoor end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required. 16 3.5 core X 50 sq. mm (35mm) 17 Supplying and fixing following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs, with provision of 100 amps TP 16 KA MCCB as incomer, interconnection between incomer MCCB and bus bars etc. as required. 18 8way (4 + 24), Double door 19 S/I/T/C of U-PVC DLP adaptable trunking system of size 105mm x 50mm complete with suitable width flexible cover, base & cover joints, internal & external angles end caps, clips, separation partition complete as required. 20 S/F3 module cover plate on existing U-PVC DLP adaptable trunking system of size 105mm x 50mm for fixing of 15amp switch and 15amp socket etc. as required. 21 Supplying and Fixing following modular switch / socket on the existingU-PVC DLP adaptable trunking of approved makeincluding connections but excluding modular plate etc. as required 22 20 amps switch 23 6 pin 6/16 Amps Socket outlet 24 SITC of recess downlight18 W LED 5700 to 6500Kinthedia cast aluminium housingwith efficacy of 100 Lumen/Watt suitable for armstrong/grid/POP ceiling complete with separate electronic driver & high brightness SMD LEDs, wiring with 3 x 1.5 sq. mm copper conductor wirei/c making cutout of suitable size for fittingin armstrong/grid/POP ceiling& dismantaling of existing Light fixture etc. complete as required with 2 year replacement warranty. 25 Supply& Layingof1100 volts rated aluminium conductor steel wire / strip armored XLPEpower cable of following sizes as per IS-7098 part-Iwith ISI marked on wall surfaceincludingtesting at manufacturer site etc complete as required. 26 3.5 core50 sq.mm Armoured Aluminium cable 27 SITC ofFloor/wallmounted cubical type panel board indoor typemade of 14 SWG CRCA sheet fully compartmentalized duly dust & vermin proof powder coated &Phosphatized with 7 tank process, complete with following switch gear mounted there on, earthing strip of suitable size, connection, interconnection, sign writing etcsuitable mounting base plate/angle iron i/c Brick/cement concrete foundations as per site requirementetc as required. (depth up to 400mm)Incoming a. 200 A, 25KA, 3 Polethermal magnetic release MCCB with neutral link – 01 No. b. RYB indicating lights with toggle switch - 01 set BUSBAR a. 400 A capacity, 4 strip aluminum bus bar – 01 No.Outgoing b. 125 A, 18 KA, 3 Pole Thermal Megnetic release MCCB – 3 Nos including distamtaling of old LT panel. 28 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position andapplying a priming coat of approved steel primer all complete.