| 1 | Excavation in trenches not exceeding 1.5 m width andnot exc 1.5 in depthgetting out soft disintegrated rock for laying and taking down UG cable complete all as specified and as directed. |
| 2 | Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm in thick using excavated hard / dense soil complete all as specified and as directed. |
| 3 | Removal of surplus soil to a distance not exceeding 50 m and depositing where complete all as specified and as directed.by Engr-in-charge. |
| 4 | Taking out unserviceable street light, security light fitting complete from different locations / poles of any sizes, makes, model and refixing after replacement of defective items including replacement of defective wiring, cleaning of acrylic cover/ diffusers, replacement of unserviceable screws and nuts complete all as specified and as directed.Note:- Replacement of defective items shall be measured and paid separately. |
| 5 | Supply & Fixing sheet moulding compound junction box (SMC) suitable for terminating 2 Nos 4 x 6/10/16 Sqmm UG cable including one in Nos MCB SP 0.5 Ampsincluding cable glandes of 2 Nos, and two way connector 1 No, including MS Clamp, nut, bolt and washer, including dismantling old one complete all as specified and as directed. |
| 6 | M&L for High density polyethylene pipes (HDPE) of 20mm dia pressure rating PN 6 (SDR 21) laid in trenches or on wall for cable protection complete all as specified and as directed. |
| 7 | Supply & Fixing on wall or in ceiling, PVC unarmoured 1100V grade three core multistranded copper conductor cable of size 2.5 Sqmm including cable clamps and connection complete all as specified and as directed. |
| 8 | Supply & Fixing GI pipe with suitable clamps on existing pole made of MS flat 40x5mm and 40mm dia GI pipe (light grade) bend to 1.2 mtr in length & in any shape with all fixing arrangement, nuts, bolts and washers etc and including 2.5M copper conductor cable multistranded of 2.5 Sqmm PVC cable from overhead line to fitting connecting box etc complete all as specified and as directed. by Engr-in-Charge and including dismantling the rusted/ broken U/S old one. |
| 9 | Supply & Fixing PVC unarmored 1100V grade three core cable, stranded aluminium conductor of size 4 Sqmm complete all as specified and as directed. |
| 10 | Supply only Surge protector of LED street light with specifications to match the existing street light fitting including dismantling defective driver from existing light fitting complete all as specified and as directed. |
| 11 | Supply & fixingPressure die cast powder coated housing with PC diffuser. Efficient high output LED with IP 66 protection. aluminium landscape luminaries (bollard lights) with high power LED as light source of 10 watts capacity including PCC block made up of concrete of 1:3:6 type C1 20mm grade aggregate set in cement mortar 1:4 for mounting bollard lights and nut bolts complete all as specified and as directed by Engr-in-Charge. |
| 12 | Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete including making necessary electric connection to the fitting with suitable size flexible copper cable complete all as specified and as directed by Engr-in-Charge. |
| 13 | Supply and fixing LED street light fitting 120 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermalmanagement in multiple optics complete with IP 65/66 protection complete all as specified and as directed by Engr-in-Charge. |
| 14 | Supply and fixing LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed by Engr-in-Charge. |
| 15 | Supply & fixing aluminium strip 25 x 3 mm fix on porcelain insulator for roof conductors and down conductors above ground level as lighting conductor (including insulator) complete including removal of old unserviceable earth strip complete all as specified and as directed. |
| 16 | Supply and fixing Air termination, single pointed Copper Rod 12mm dia and 300 mm long complete all as specified and as directed by Engr-in-Charge. |
| 17 | M&Lfor earthing complete with copper plate earth plate electrode 60 cmx 60 cm x 3.15 mm thick buried directly in ground vertically to a depth not less than 2.25 m below ground level with top connected to Copper earth strip 25 x 3 mmbymeans of bolts, nuts, check nuts and washers ofbrassand earth lead connected to terminal box with including necessary and earth work and excavation includingPCC chamber made up of 1:3:6 and GI cover all as specified and or shown in electric plate No 5 of SSR-1 complete all as specified and directed by Engr-in-Charge. |
| 18 | M&L for Providing precast cement concrete Type C1 1:3:6 (20mm graded aggregate) Set in cement mortar 1:4 in copings and setting in mortar complete with joints to match complete all as specified and directed. |
| 19 | M&L for painting of steel tubularpoles for street lights any type complete including flat iron clamps,D clamps, Stay clamps,bracing, cross arm with two coat aluminium paint including preparation old painted surface initially & applying one coat of red oxide, applying two coat of aluminum paint over the red oxide, marking with alternate white and red strips 30 cm height 5 Nos strips with two coat of synthetic enamel paint and also including numbering of poles with white paint are located on different locationscomplete all as specified and directed by Engr-in-Charge. |
| 20 | S&F in replacement of battery 3.2 volt lead acid suitable for solar street light having capacity 12 AH including all fitting arrangements complete all as specified and as directed. |
| 21 | Supply and fixing LED flood light 250 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed by Engr-in-Charge. |