Tender For Provision Of Deficient Smqs At 1Wg, Af Stn Srinagar; 1 Total amount ofSch A Part-I (Section-I) ( Bldg Work) Note : This schedule is not pre priced by MES and the pre priced rate indicated as Rs. 0.00 under Col.5 signifies this fact only 2 Design, Fabrication, Erection and construction of building (Stilt + 6 ) configuration for Married Accommodationin steel structure with LGSF member, as per architectural Drawings andstructural drawings designed by the bidder based on input data as provided in the tender documents and asper specification including as per note given below:-Note:- (A) Super structure insteel strcture as per IS 800 and IS 1893-2016 with limit state method using LGSF member confirming to IS standard with RCC foundation Shallow or deep foundation based on the safe bearing capacity (SBC) of the soil asand the structure load as per design criteria specified.(B) Reinforced Cement Concrete- M-30 Design mix and Reinforcementsteel of grade Fe-550D TMT bars. (C) Floor/ Deck slab shall be of GI profiled sheet of thickness as per design with RCC laid over it as per IS 11384. (D) Internal and external wall shall be ofminimum140 mm thick composed of LGSF member with surface as specified. Space between surface shall be filled with Rockwool insulation of minimum 50 mm thickness ofdensity 48 kg/cum.(E) Firefighting cum over head tank of capacity as shown shall be design, construct and finished in GRP as per IS 14399- 1&2 (F) The detailed design and construction shall also include design of internal water supply scheme and sanitary plumbing scheme and supply and fixing of fitting and fixture as specified. (G) The design and construction shall cater for provision of services such as internal electric supply,water supply, sanitary plumbing works, internal heatingetc.(H) Confirmatory SBC test as per IS Provisions.(J) Finish of Building as per SChedule. any missing details of finish shall be as per manufacturuer guidelines and as approved by GE 3 Construction of building for Pump House Bldg in single storey in RCC frame as per drawings,complete all as specifiedand asdirected by Engr-in-charge 4 Construction of UG Sump of 50000 ltr capacity sump in RCC as per Drawing No CEAF/STD-34/2002, complete all as specifiedand asdirected by Engr-in-charge 5 Total amount ofSchedule A PART-I (BUILDING WORK) 6 Total amount ofSch A PART-II (SEC-I)(INTERNAL ELECTRIC SUPPLY WORKS) 7 Total amount ofSch A Part-II (Section-II) (INTERNAL ELECTRIC SUPPLY WORKS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as Rs. 0.00 under Col.5 signifies this fact only 8 S&F LED Building securityLight fitting 25 watt, for opearting voltage between 110V to 320V system efficiency not less than 120 lumen / watt, PF-0.95 minimum, IP66 protection, 5700CCT(K), CRI between 80-85, confirming to LM79 and LM 80 standards or as per IS-16104:2012 and IS-16106:2012, for estimated life span ofminimum 50,000 hrs consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with LED street optics LENS for uniform light distribution,weather proof gasket for lamp & driver compartment, Heat resistance toughened UV stabilized glass fitted in cast aluminium housing with SS screws, complete all as specified and directed by Engineer-in-Charge 9 Supply and fixing MCB Single Pole 2 Amps rating 240V, 10KA C curve miniature circuit breaker complete with connection testing and commissioning complete all as specified and directed by Engineer-in-Charge. 10 Supply and fixing MCB Single Pole 6 Amps rating 240V, 10KA C curve miniature circuit breaker complete with connection testing and commissioning complete all as specified and directed by Engineer-in-Charge 11 Supply and fixing MCB Single Pole 16Amps rating 240V, 10KA C curve miniature circuit breaker complete with connection testing and commissioning complete all as specified and directed by Engineer-in-Charge 12 Supply and fixing RCBO for earth leakage, overload & short-circuit protection double pole 20 A , 100 mA, AC 240 volt, 10 kA, C - curve comforming to IS-12640-2 & IEC 61009-1 complete with connection testing and commissioning complete all as specified and directed by Engineer-in-Charge 13 Supply and fixing of indoor type weather & dust vermin proof metal body energy meter panel board factory fabricated indoor cubicle typetotally enclosed suitable for fixing 8 energy meter inside made of GI sheet 2mm thickness powder coated, including transparent cover for each energy meter , arrangement for two nos of body earthing,The panel shall have integral base frame of100 MM ISMC base channel, removeable undrilled gland plates shall be fitted for bottom for incoming cable and making connections, comprising of the followings and specified herewith:- (i) Rectangular Aluminium bus bar fixed on insulated mounting arrangement 100 Amps current rating -04 Nos provided with heat shrinkable sleeve not less than one mm thick.(ii) Cable alley for 01 I/C and 08 outging feeders.(a) INCOMING (i) MCCB 4P 63 AmpsIcu =16 KAat415 volts, adjustable type - 01 No (I/C) .(ii) Phase indicating RYB light LED type- 1 set. (b) OUTGOING(i) MCB DP 25 Amps, 10 KA 230 volts - 08 No (Each for separate energy meter outgoing).All accessories prewired with suitable size copper wire with stand high temperature, housed in cubical panel made out of standardMS sheetfactory made duly powder coated front and rear door open ablewith locking arrangement complete with fixing arrangements as required or recommended by manufacturer. (ii) single phase 2 wire energy meter of rating 10-40 Amps conforming to IS: 16444 compatible with prepaid-postpaid mode version, having interoperability and other applications described in IS: 16444 - 8 Nos. (iii) Earthing busbar with green DIN rail clips for connecting two incoming GI wire (4mm dia) and 8 nos outgoing copper earthing wires. Note: Main Aluminum busbars with 0.8Amps/sqmm current density & all internal wiring with copper FRLS wires and connections. All MCCBs are Microprocessor/Thermal Magnetic based(Icu = Ics = 100%) as given in sld, housed in separate compartments, enclosed on sides, with rotating handle. All MCB Icu=10kA where not given/mentioned in sld.Earthing all components, frame etc. to a common internal earth bar.Painting all sheet metal works support structure etc.All accessories & supportingstructure (Hot Dip Galvanised).The panel shall be wall mounted and item required for fixing are included in quoted rates.The panel shall be prewired, ready for External Cable termination.All Gland Plates shall be 3 mm thick removable type. 14 The panel shall be in convenient sections suitable for transportation, erection & have sufficient space for Incoming & Outgoing cable terminations.The panel Incomers/Outgoings shall have Potential free Contact.All the panel Incomers & Outgoings shall be tagged with aluminum anodized engraved name plates (Detailed tag of the feeders will be given during the final approval of panel drawings). contractor shall arrange to configure / check / set all the meters once the panel is completely installed & in operation at site. 15 S&F TV concealed socketoutlet with gripModular type 01 Module for Coaxial cable complete set icluding Modular Sunken Box along with Module base cover complete in all respect all as specified and directed. 16 Total amount ofSch A Part-II (Section-II) (INTERNAL ELECTRIFICATION) 17 Total amount ofSch A PART-III (SEC-I) ( ROAD, PATH, CULVERT) 18 Total amount ofSch A PART-IV (SEC-I)(EXTERNAL WATER SUPPLY) 19 Total amount ofSch A Part-IV (Section-II) (EXTERNAL WATER SUPPLY) Note : This schedule is not pre priced by MES and the pre priced rate indicated as Rs. 0.00 under Col.5 signifies this fact only 20 Supply and fixing cast iron heavy duty Foot Valve screwed/flanged conforming to IS 4038, 50 mm (2”) dia. comlete all as specified and directed by Engineer-in-Charge 21 Material and labour for valve chamber (1.5mtr x 1.5 mtrx 0.9 mtr ) (internal ) with brick masonary valve chamber, PCC foundation, plastering and necessary excavation and earth work in any type of soil, MS sheet cover 3 mm thickness along with angle iron frame of size (40 x 40 x 6) mm with locking arrangement & necessary fixing materials like hinges, nut/bolts etc and painting to MS cover with one coat of red oxide and two coats of synthetic enamel paint etc comlete all as specified and directed by Engineer-in-Charge 22 Material and labour for valve chamber (900mm x 900mm x 900 mm) (internal ) with brick masonary valve chamber, PCC foundation, plastering and necessary excavation and earth work in any type of soil, MS sheet cover 3 mm thickness along with angle iron frame of size (40 x 40 x 6) mm with locking arrangement & necessary fixing materials like hinges, nut/bolts etc and painting to MS cover with one coat of red oxide and two coats of synthetic enamel paint etc comlete all as specified and directed by Engineer-in-Charge 23 Supply, fixing, testing and commissioning of centrifugal monoblock pump set for water supply set of 5.0 HP having discharge capacity 14000 Ltr/Hr attotal head 40 m, self priming type, suction dia 50 mm and delivery data 50 mm,CI impeller, CI valute, SS shaft, carbon/ceramic mechanical seal,electric driven , electric motor 415 V+6%, -15%, 50 HZ, 3 phase, AC supply with class F insulation and temperature riserestricted to class B with IP 55 protection inclusive of PCC foundation comlete all as specified and directed by Engineer-in-Charge 24 Supply and laying, connecting and testing copper flexible cable, pvc insulated,heavy duty 1100 volts grade 4.0 sqmm 3.0 core laid in trenches passing through existing/new pipe under road crossing, clamping on walletc. comlete all as specified and directed by Engineer-in-Charge 25 Supply, testing and commissioningof free standing infront operated fully compartmentalized extendable on both sidesIndoor weather& dust vermin proof L.T. Panel board suitable for 3 Phase4 wire, 415 Volts, 50 Hz, AC supply system housed with incoming and outgoing feeders, bus bars,interconnections etc , factory fabricated with indoor cubicle typetotally enclosed .The Panels must be design and verified as per the IS/IEC 61439-01 & 2 with complete type test certificates for conformance to IS / IEC 61439 -1 and 2, with 65 KA 1 sec along with MCCB mounted in switch boards with aluminiumbus bars as mandatory as conformed to IEC 61641 with internal arc containment fault level of 65 KA/03 Sec and shall be suiatbale for Seismeic Zone III/IV Zone including the type test conducted at ERDA/CPRI for seismic test.. All MCCBs panel should be single Tierfor easy cable termination.Cable termination space should be adequate to safely gland and terminate AL/CU cables for the given current ratings with FormB seperation for Incoming MCCB feeders and For OutgoingMCCB feeders. The Switch board cubicles shall have steel frame work enclosed on all sides and top by CRCA sheet steel of Minimum 2.00 mm thickness.The panel shall have integral base frame of100 MM ISMC base channel.removeable undrilled gland plates shall be fitted for bottom cable entry.Pump House LT Panel 26 1.Incoming:- (a) MCCB 40 Amp 16 KA Four pole 415 volts fixed type withthermal magnetic release. It should bewith adjustableload setting Ir = (0.8 to 1.0) x In,Tcs = 100 % Icu and with adjustable thermal setting. It should be thermal based release with adjustable O/L, Adjustable S/C setting Class II front face, 16 KA rupturing cap, Ics=100% Icu, Isolation with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc - 01 Nos .(b) Bus Bar TPNelectrolytic Aluminium extensible type as main bus bars of minimum 100 A capacity (As per capacity of corresponding incoming / Bus couplers), and auxilliary bus bars ofsuitable capacity with heat shrunk coloured sleeves and i/c SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of36kA .(c). Metering Section - Suitable rated Digital Ammeter in amps-01 No along withresin type CTs as per design ratiowith necessary CT shorting link- 03 Nos , digital volt meter inVolts- 01 No , RYB indicating Lamps-03 Nos , Suitable Load mangaer to have a parameters like KW,KWH,KVA,A,V,PF,KVAR,Active and Reactive componentof the power - 1 No .(d)Single Phase preventer and Voltage monitoring Relay -01 No 27 2. OUTGOINGS(a) MPCB 9- 13 ATP with thermal and magnetic release 415 volts 50 Hz with breaking cap of 100 KAwith indicating lamp : On-Trip-Stop with suitable Ammeter along with necesary CTs etc- 02 Nos .(b)Heavuy duty ASD (Automatic Star Delta)Starter suitable upto 5 HP pumps with 4 Pole contactors ,OLR and electronic star delta timer in S.S enclosurewith relay range of 5.5 to 8.0Amps for centrifugalpumps-02 Nos . (All starter should be complete in all respect withTDR ,O/L, S/C and Phase sequence corrector relay etc completein all respect and specified ).(c)MCB SPN 10 Amp 10 KA .-01 NosNote:Main Aluminum busbars with 0.8Amps/sqmm current density & all internal wiring with copper FRLS wires and connections.Earthing all components, frame etc. to a common internal earth bar.Painting all sheet metal works support structure etc.All accessories & supportingstructure (Hot Dip Galvanised).The panel shall be with Galvanized MS mounting base frame & the height shall not exceed more than 2100mm.The panel shall be prewired, ready for External Cable termination.All Gland Plates shall be 3 mm thick removable type.All the CTs shall be cast resin type, with necessary CT shorting link.The panel shall be in convenient sections suitable for transportation, erection & have sufficient space for Incoming & Outgoing cable terminations.The panel Incomers/Outgoings shall have Potential free Contact.3 mm thick acrylic sheet shall be provided on the top of all outgoing termination sections, for protection against live terminals.All the panel Incomers & Outgoings shall be tagged with aluminum anodized engraved name plates (Detailed tag of the feeders will be given during the final approval of panel drawings) Vendor shall arrange to configure / check / set all the meters once the panel is completely installed & in operation at site.Complete Digital / Electronic interlocking should be provided in the panel for sequence operation of the system to ensure proper safety Suitable sufficient arrangement of LEDs light and provision of blower fans should be provided in the panel. 28 Total amount ofSchedule ASch A Part-IV (Section-II) (EXTERNAL WATER SUPPLY) 29 Total amount ofSch A PART-V(SEC-I)(EXTERNAL ELECTRIC SUPPLY) 30 Total amount ofSch A Part-V(Section-II) (EXTERNAL ELECTRIC SUPPLY) Note : This schedule is not pre priced by MES and the pre priced rate indicated as Rs. 0.00 under Col.5 signifies this fact only 31 Supply, testing and commissioningof outdoor weather & dust vermin proof L.T. Panel board factory fabricated indoor cubicle typetotally enclosed with outer sheel shall be made out of 3.15 mm thick sheet & MS angle section of suitable size for frame, factory fabricated, compartmentalized inner shell shall be made of out of 2.0 mm thick sheet .The Panels must be design and verified as per the IS/IEC 61439-01 & 2 with complete type test certificates for conformance to IS / IEC 61439 -1 and 2, with 65 KA 1 sec along with MCCB mounted in switch boards with aluminiumbus bars as mandatory as conformed to IEC 61641 with internal arc containment fault level of 65 KA/03 Sec and shall be suiatbale for Seismeic Zone III/IV Zone including the type test conducted at ERDA/CPRI for seismic test.All MCCB/ ACB panel should be single Tierfor easy cable termination.Cable termination space should be adequate to safely gland and terminate al/cu cables for the given current ratings with FormB seperation for Incoming MCCB / ACB feeders and For OutgoingMCCB feeders. The Switch board cubicles shall have steel frame work enclosed on all sides and top by CRCA sheet steel of Minimum 2.00 mm thickness.The panel shall have integral base frame of100 MM ISMC base channel.removeable undrilled gland plates shall be fitted for bottom cable entry and making connections, earth work and PCC foundation complete comprising of the followings and specified herewith:- (i) Rectangular Aluminium bus bar fixed on insulated mounting arrangement 400 Amps current rating -04 Nos provided with heat shrinkable sleeve not less than one mm thick.(ii) Cable alley for 01 I/C and 03 outging feeders.(a) INCOMING(i) MCCB 4P 250 AmpsIcu =36 KAat415 volts with microprocessorrelease type - 01 No (I/C) . Ics = 100 % Icu and class II front face,Isolation with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrieretc .(ii) Ammeter digital type 0 to 800 A -1 Nos(iii) Voltmeter digital type 0-500 V- 1 Nos(iv) Three way selector switch for current- 1 Nos(v) Three way selector switch for voltage- 1 Nos(vi) Phase indicating RYB light LED type- 1 set.(vii) Suitable CTs of cast resin type with necesaary CT shortlinking should be provieded . - 1 set. 32 (vii) Suitable CTs of cast resin type with necesaary CT shortlinking should be provieded . - 1 set. OUTGOING(i) MCCBFour pole 100 Amps Icu =16 KA at 415 volts, adjustable type withthermal magnetic release-04 No (O/G). They should bewith adjustableover load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and with adjustable thermal setting. Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etcNote:Main Aluminum busbars with 0.8Amps/sqmm current density & all internal wiring with copper FRLS wires and connections. All MCCBs are Microprocessor/Thermal Magnetic based(Icu = Ics = 100%) as given in sld, housed in separate compartments, enclosed on sides, with rotating handle. All MCB Icu=10kA where not given/mentioned.Earthing all components, frame etc. to a common internal earth bar.Painting all sheet metal works support structure etc.All accessories & supportingstructure (Hot Dip Galvanised).The panel shall be with Galvanized MS mounting base frame & the height shall not exceed more than 2100mm.The panel shall be prewired, ready for External Cable termination.All Gland Plates shall be 3 mm thick removable type.All the CTs shall be cast resin type, with necessary CT shorting link.The panel shall be in convenient sections suitable for transportation, erection & have sufficient space for Incoming & Outgoing cable terminations.The panel Incomers/Outgoings shall have Potential free Contact.3 mm thick acrylic sheet shall be provided on the top of all outgoing termination sections, for protection against live terminals.All the panel Incomers & Outgoings shall be tagged with aluminum anodized engraved name plates (Detailed tag of the feeders will be given during the final approval of panel drawings)Vendor shall arrange to configure / check / set all the meters once the panel is completely installed & in operation at site. 33 Supply, testing and commissioningof Indoor weather & dust vermin proof L.T. Panel board factory fabricated indoor cubicle typetotally enclosed .The Panels must be design and verified as per the IS/IEC 61439-01 & 2 with complete type test certificates for conformance to IS / IEC 61439 -1 and 2, with 65 KA 1 sec along with MCCB mounted in switch boards with aluminiumbus bars as mandatory as conformed to IEC 61641 with internal arc containment fault level of 65 KA/03 Sec and shall be suiatbale for Seismeic Zone III/IV Zone including the type test conducted at ERDA/CPRI for seismic test.All MCCB/ ACB panel should be single Tierfor easy cable termination.Cable termination space should be adequate to safely gland and terminate al/cu cables for the given current ratings with FormB seperation for Incoming MCCB / ACB feeders and For OutgoingMCCB feeders. The Switch board cubicles shall have steel frame work enclosed on all sides and top by CRCA sheet steel of Minimum 2.00 mm thickness.The panel shall have integral base frame of100 MM ISMC base channel.removeable undrilled gland plates shall be fitted for bottom cable entry and making connections, earth work and PCC foundation complete comprising of the followings and specified herewith:- (i) Rectangular Aluminium bus bar fixed on insulated mounting arrangement 200 Amps current rating -04 Nos provided with heat shrinkable sleeve not less than one mm thick.(ii) Cable alley for 01 I/C and 06 outging feeders.(a) INCOMING(i) MCCB 4P 250 AmpsIcu =36 KAat415 volts with microprocessorrelease type - 01 No (I/C) . Ics = 100 % Icu and class II front face,Isolation with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrieretc .(ii) Ammeter digital type 0 to 800 A -1 Nos(iii) Voltmeter digital type 0-500 V- 1 Nos(iv) Three way selector switch for current- 1 Nos(v) Three way selector switch for voltage- 1 Nos(vi) Phase indicating RYB light LED type- 1 set.(vii) Suitable CTs of cast resin type with necesaary CT shortlinking should be provieded . - 1 set.(b) OUTGOING (i) MCCBFour pole 32 Amps Icu =16 KA at 415 volts, adjustable type withthermal magnetic release-04 No 34 (O/G) ( 3 W + 1S) . They should bewith adjustableover load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and with adjustable thermal setting. Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc(ii) Timer switche along with415 V three Phasecontactors25 Amp rating and MCB 4 Pole 415 V, 25 Amps as incoming and one MCB 4 Pole 415 V, 20 Amps as outgoing incl copper cable for connection and fixing complete all as specified and directed.All accessories prewired with suitable size copper wire with stand high temperature, housed in cubical panel made out of standardMS sheetfactory made duly powder coated front and rear door open ablewith locking arrangement complete with foundation as required or recommended by manufacturerNOTE Main Aluminum busbars with 0.8Amps/sqmm current density & all internal wiring with copper FRLS wires and connections. All MCCBs are Microprocessor/Thermal Magnetic based(Icu = Ics = 100%) as given in sld, housed in separate compartments, enclosed on sides, with rotating handle. All MCB Icu=10kA where not given/mentioned.Earthing all components, frame etc. to a common internal earth bar.Painting all sheet metal works support structure etc.All accessories & supportingstructure (Hot Dip Galvanised).The panel shall be with Galvanized MS mounting base frame & the height shall not exceed more than 2100mm.The panel shall be prewired, ready for External Cable termination.All Gland Plates shall be 3 mm thick removable type.All the CTs shall be cast resin type, with necessary CT shorting link.The panel shall be in convenient sections suitable for transportation, erection & have sufficient space for Incoming & Outgoing cable terminations.The panel Incomers/Outgoings shall have Potential free Contact.3 mm thick acrylic sheet shall be provided on the top of all outgoing termination sections, for protection against live terminals.All the panel Incomers & Outgoings shall be tagged with aluminum anodized engraved name plates (Detailed tag of the feeders will be given during the final approval of panel drawings)Vendor shall arrange to configure / check / set all the meters once the panel is completely installed & in operation at site. 35 M&L Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 200 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. 36 Supply & Fixing Bracket made out of GI light grade pipe of size upto 40 mm dia, suitable for fixing street light, 1.5 mtr long bend to an angle of 120 degree with 02 Nos MS clamp made out of flat iron ofsize 40mm x 6mm and 04 sets of nuts,bolts and washers painting with two coats of synthetic enamel paint over a red oxide primer complete all as specifiedand asdirected by Engr-in-charge. 37 Supply and fix MS box (Kiosk) weather proof made out of FRP sheet of size 325 x 220 x 150 mm including two strip single phase bus bar of aluminium strip with neutral link 32 A rating mounted on insulators of inflammable material and fixed with one Nos MCB SP 240 volts and current rating 2 Amps for controlling street lightfittings to be mounted onpoles at easily accessible height complete all as specified and directed by Engineer-in-Charge. 38 Total amount ofSchedule ASch ASch A Part-V (Section-II) (EXTERNAL ELECTRIC SUPPLY) 39 Total amount ofSch A PART-VI (LIGHTENING PROTECTION) 40 Total amount ofSch A PART-VII (SEC-I)(FIRE FIGHTING SYSTEM) 41 Total amount ofSch A PART-VII (SEC-II) (FIRE FIGHTING SYSTEM) Note : This schedule is not pre priced by MES and the pre priced rate indicated as Rs. 0.00 under Col.5 signifies this fact only 42 Supply, fixing, testing and commissioning of centrifugal monoblock/ Terrace pump set for fire fighting of 7.5 HP, 2900 RPM,suitable size (suction and delivery) having discharge capacity 900 LPM, total head 30 m,self priming type , CI impeller, CI valute, SS shaft, carbon/ceramic mechanical seal,electric driven , electric motor 415 V+6%, -15%, 50 HZ, 3 phase, AC supply with class F insulation and temperature riserestricted to class B with IP 55 protection with fixing arrangement with suction and delivery pipe including suitable PVC sheet and angle frame for pump shed for protection from raincomplete all as specified and directed by Engineer-in-Charge. 43 Supply, testing and commissioningof outdoor weather & dust vermin proof L.T. Panel board factory fabricated indoor cubicle typetotally enclosed with outer sheel shall be made out of 3.15 mm thick sheet & MS angle section of suitable size for frame, factory fabricated, compartmentalized inner shell shall be made of out of 2.0 mm thick sheet .The Panels must be design and verified as per the IS/IEC 61439-01 & 2 with complete type test certificates for conformance to IS / IEC 61439 -1 and 2, with 65 KA 1 sec along with MCCB mounted in switch boards with aluminiumbus bars as mandatory as conformed to IEC 61641 with internal arc containment fault level of 65 KA/03 Sec and shall be suiatbale for Seismeic Zone III/IV Zone including the type test conducted at ERDA/CPRI for seismic test.All MCCB/ ACB panel should be single Tierfor easy cable termination.Cable termination space should be adequate to safely gland and terminate al/cu cables for the given current ratings with FormB seperation for Incoming MCCB / ACB feeders and For OutgoingMCCB feeders. The Switch board cubicles shall have steel frame work enclosed on all sides and top by CRCA sheet steel of Minimum 2.00 mm thickness.The panel shall have integral base frame of100 MM ISMC base channel.removeable undrilled gland plates shall be fitted for bottom cable entry and making connections, earth work and PCC foundation complete comprising of the followings and specified herewith:-(forTarrace pumps) :1.Incoming:- (a) MCCB 25 Amp 16 KA Four pole 415 volts. It should bewith adjustableload setting Ir = (0.8 to 1.0) x In,Tcs = 100 % Icu and with adjustable thermal setting. It should be thermal based release with adjustable O/L, Ics=100% Icu, Isolation with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc - 01 Nos .(b) Bus Bar TPNelectrolytic Aluminium extensible type as main bus bars of minimum 200 A capacity (As per capacity of corresponding incoming / Bus couplers), and auxilliary bus bars ofsuitable capacity with heat shrunk coloured sleeves and i/c SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of36kA .(c). Metering Section - Suitable rated Digital Ammeter in amps-01 No along withresin type CTs as per design ratiowith necessary CT shorting link- 03 Nos , digital volt meter inVolts- 01 No , RYB indicating Lamps-03 Nos , Suitable Load mangaer to have a parameters like KW,KWH,KVA,A,V,PF,KVAR,Active and Reactive componentof the power - 1 No .(d)Single Phase preventer and Voltage monitoring Relay -01 No 44 2. OUTGOINGS(a) MPCB 9- 13 ATP with thermal and magnetic release 415 volts 50 Hz with breaking cap of 100 KAwith indicating lamp : On-Trip-Stop with suitable Ammeter along with necesary CTs etc- 03 Nos for ( 2 Working +01 Stand By) (b)Heavuy duty ASD (Automatic Star Delta)Starter suitable upto 7.5 HP pumps with 4 Pole contactors ,OLR and electronic star delta timer in S.S enclosurewith relay range of9.0 to 14.0Amps for centrifugalpumps-02 Nos(All starter should be complete in all respect withTDR ,O/L, S/C and Phase sequence corrector relay etc completein all respect and specified ). (c) System Controller: Designing, Supply, Installation, Testing and commissioning of system controller i.eAutomatic operation and control of main and standbyPressurization pump in sequence as per specification consisting of relays, timers. Sensors, Pressure switches, Guages , annunciation window for fault indication, complete as per specification along with control cable of suitable sizes shall be deemed to be included in quoted rates complete all as directed.- 01 Job 45 Note:Main Aluminum busbars with 0.8Amps/sqmm current density & all internal wiring with copper FRLS wires and connections.Earthing all components, frame etc. to a common internal earth bar.Painting all sheet metal works support structure etc.All accessories & supportingstructure (Hot Dip Galvanised).The panel shall be with Galvanized MS mounting base frame & the height shall not exceed more than 2100mm.The panel shall be prewired, ready for External Cable termination.All Gland Plates shall be 3 mm thick removable type.All the CTs shall be cast resin type, with necessary CT shorting link.The panel shall be in convenient sections suitable for transportation, erection & have sufficient space for Incoming & Outgoing cable terminations.The panel Incomers/Outgoings shall have Potential free Contact.3 mm thick acrylic sheet shall be provided on the top of all outgoing termination sections, for protection against live terminals.All the panel Incomers & Outgoings shall be tagged with aluminum anodized engraved name plates (Detailed tag of the feeders will be given during the final approval of panel drawings)Vendor shall arrange to configure / check / set all the meters once the panel is completely installed & in operation at site.Complete Digital / Electronic interlocking should be provided in the panel for sequence operation of the system to ensure proper safety Suitable sufficient arrangement of LEDs light and provision of blower fans should be provided in the panel. 46 Supply and fixing reducer 100/63mm flanged type including fabrication as per site requirement complete all as specified and directed. (Between landing valve / fire brigade inlet and downcomer). 47 Supply and fixing automatic air release valve 50mm dia suitable for domestic water with 50mm gun metal stop valve with suitable reducer for connecting downcomer pipe complete all as specified and directed by Engineer-in-Charge. 48 Supply and fixing of Retro reflective sign board of size 3.0 feet x 1.5 feet made of ACP sheet will be fixed on wall showing alarm point, fire extinguishers, escape routes and emergency power off switches and other points as required on site complete all as specified and directed by Engineer-in-Charge. 49 Supply and fixing of Escape Retro reflective sign board made of ACP sheet will be fixed on wall showing fire escape route complete all as specified and directed.Note: The sizes and colours of the exit signs shall be in accordance with IS-9457 & IS-12349. 50 Supply and fixing LED escape lighting 20 watt fittings with invertor of four hours battery backup normal/trickle charging including point wiring with conductor 1.5 sqmm multi stranded complete all as specified and directed. 51 Supply, installation, testing & commissioning of Public addressable (PA) system with talk back station in (S+6) MD Accn to accommodate and including following:- 52 (a) Supply and fixing 10 Watt wall mounted CD Speaker for PA system complete all as specified and directed by Engineer-in-Charge 53 (b) Supply and fixing 250 watt amplifier complete all as specified and directed by Engineer-in-Charge 54 (c) Supply and fixing Microphone set complete all as specified and directed by Engineer-in-Charge 55 (d) Supply and fixing control console for PA system inclding neccesarry wiring , connections and other accessories complete all as specified and directed by Engineer-in-Charge 56 Supply, Installation, testing and commissioning of dry chemical powder (ABC) type fire extinguishers with operating temperature -20°C to 35°C of 6 Kg capacity, approved make ISI marked, IS: 15683, complete with accessories all as specified and as directed. 57 Supply, Installation, testing and commissioning of approved make light weight squeeze grip CO2 type fire extinguishers with operating temperature -20°C to 35°C of 4.5 Kg capacity with ISI mark,IS: 15683, complete with accessories all as specified and as directed. 58 Supply, Installation, testing and commissioning of approved make light weight water stored pressure type fire extinguishers with operating temperature -20°C to 35°C of 9 Kg capacity with ISI mark,IS: 15683, complete with accessories complete all as specified and directed by Engineer-in-Charge. 59 Supply, Installation, testing and commissioning of approved make Mechanical Foam type fire extinguishers with operating temperature -20°C to 35°C of 9.0 ltr capacity with ISI mark, IS: 15683, complete all as specified and directed by Engineer-in-Charge. 60 Supply and fixing fire beater with bamboo complete all as specified and directed. 61 Supply and fixing fire bucket stand with two fire buckets. The stand and buckets are made of GI material, rustproof and anti-corrosive.The outer surface of the bucket and stand are painted red in colour. The stands are equipped with a canopy and legs with all accessories complete all as specified and directed by Engineer-in-Charge. 62 Total amount ofSch A PART-VII (SEC-II)(FIRE FIGHTING) 63 Total amount ofSch A PART-VIII (SEC-I)(LIFT) 64 Total amount ofSch A PART-VIII (SEC-II)(LIFT ) Note : This schedule is not pre priced by MES and the pre priced rate indicated as Rs. 0.00 under Col.5 signifies this fact only 65 Supply, testing and commissioningof Indoor weather & dust vermin proof L.T. Panel board factory fabricated indoor cubicle typetotally enclosed .The Panels must be design and verified as per the IS/IEC 61439-01 & 2 with complete type test certificates for conformance to IS / IEC 61439 -1 and 2, with 65 KA 1 sec along with MCCB mounted in switch boards with aluminiumbus bars as mandatory as conformed to IEC 61641 with internal arc containment fault level of 65 KA/03 Sec and shall be suiatbale for Seismeic Zone III/IV Zone including the type test conducted at ERDA/CPRI for seismic test.All MCCB/ ACB panel should be single Tierfor easy cable termination.Cable termination space should be adequate to safely gland and terminate al/cu cables for the given current ratings with FormB seperation for Incoming MCCB / ACB feeders and For OutgoingMCCB feeders. The Switch board cubicles shall have steel frame work enclosed on all sides and top by CRCA sheet steel of Minimum 2.00 mm thickness.The panel shall have integral base frame of100 MM ISMC base channel.removeable undrilled gland plates shall be fitted for bottom cable entry and making connections, earth work and PCC foundation complete comprising of the followings and specified herewith:- (i) Rectangular Aluminium bus bar fixed on insulated mounting arrangement 200 Amps current rating -04 Nos provided with heat shrinkable sleeve not less than one mm thick.(ii) Cable alley for 01 I/C and 06 outging feeders.(a) INCOMING (i) MCCBFour pole63 Amps Icu =16 KA at 415 volts, adjustable type withthermal magnetic release-01 No (I/C) . It should bewith adjustableover load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and with adjustable thermal setting. Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc(ii) Ammeter digital type 0 to 500 A -1 Nos(iii) Voltmeter digital type 0-500 V- 1 Nos(iv) Three way selector switch for current- 1 Nos(v) Three way selector switch for voltage- 1 Nos(vi) Phase indicating RYB light LED type- 1 set.(vii) Suitable CTs of cast resin type with necesaary CT shortlinking should be provieded . - 1 set. 66 (b) OUTGOING (i) MCCBFour pole 25 Amps Icu =16 KA at 415 volts, adjustable type withthermal magnetic release-03 No (O/G) ( 2 W + 1S) . They should bewith adjustableover load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and with adjustable thermal setting. Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etcAll accessories prewired with suitable size copper wire with stand high temperature, housed in cubical panel made out of standardMS sheetfactory made duly powder coated front and rear door open ablewith locking arrangement complete with foundation as required or recommended by manufacturer.Note:Main Aluminum busbars with 0.8Amps/sqmm current density & all internal wiring with copper FRLS wires and connections. All MCCBs are Microprocessor/Thermal Magnetic based(Icu = Ics = 100%) as given in sld, housed in separate compartments, enclosed on sides, with rotating handle. All MCB Icu=10kA where not given/mentioned.Earthing all components, frame etc. to a common internal earth bar.Painting all sheet metal works support structure etc.All accessories & supportingstructure (Hot Dip Galvanised).The panel shall be with Galvanized MS mounting base frame & the height shall not exceed more than 2100mm.The panel shall be prewired, ready for External Cable termination.All Gland Plates shall be 3 mm thick removable type.All the CTs shall be cast resin type, with necessary CT shorting link.The panel shall be in convenient sections suitable for transportation, erection & have sufficient space for Incoming & Outgoing cable terminations.The panel Incomers/Outgoings shall have Potential free Contact.3 mm thick acrylic sheet shall be provided on the top of all outgoing termination sections, for protection against live terminals.All the panel Incomers & Outgoings shall be tagged with aluminum anodized engraved name plates (Detailed tag of the feeders will be given during the final approval of panel drawings)Vendor shall arrange to configure / check / set all the meters once the panel is completely installed & in operation at site. 67 Total amount ofSch A PART-VIII (SEC-II)(LIFT ) 68 Total amount ofSch A PART-IX(STAND BY DG ) Note : This schedule is not pre priced by MES and the pre priced rate indicated as Rs. 0.00 under Col.5 signifies this fact only 69 Supply,install ,testing, commissioning of Silent type diesel generating set alongwith having prime power rating of 58.5 kVA,415Volts at 1500RPM , 0.8 lagging power factor at 415 volts suitable for50 Hz 3 phase system and for 0.85 load factor ,CPCB-4 norms complied, acoustic enclosure,realy panel for automatic starting on main failure (AMF), anti vibration mountings,control panel and foundation.The DG set should be robust in construction factory tested and assembled to ensure perfect alignment of Engine and Alternator on a common base frame.The DG set power rating indicated above is inclusive of altitude correction factor however the DG Setshall be designed and suitable to operate as per tropical condition of Srinagar (J&K) and for more details on service condition refer particualr specification.The DG set shall becomprising of following item as under:-(a)Diesel Engine : The diesel engine shall be of four stroke cycle multi-cylinder,direct injection water cooled, turbo charged with after cooler, Air to air aftercooling and optimised turbocharger for increased altitude capabilities developing required not less than 74 (BHP) @ 1500 rpm under NTP condition of BS 5514/ISO 3046 with an over load capacity of 110% for one hour in any specified 12 hrs of continuous operation,suitable for generating set application on AMF mode.The engine shall confirm to IS:10000/BS:649/BS 5514/ISO 3046. The engine shall have the following accessories: (i) Cooling fan and radiator.(ii)DM water cooling systems with pre-mix anti-corrosive additive(iii) Turbocharger.(iv) Fly wheel with fly wheel housing.(v) Electrical engine starter motor (disengagement after start-up) with Batteries.(vi) Battery charging systems.(vii) Stainless steel exhaust flexible elbow.(viii) Thermal sealing of exhaust pipe and aluminium cladding for complete exhaust pipe and silencer.(ix) Required filters for fuel, lube oil, air etc.(x) Sets of flexible hoses as required.(xi) Suitable rubber coupling to Alternator with guard.(xii) Suitable Engine controller for protection of the engine.(xiii)Coolant heater and crankcase heater.(xiv) Oil drain Pump (xv) Heavy duty air cleaner. 70 (b) Engineprotections:(i) High coolant temperature warning & trip (ii)Low lubricating oil pressure warning & trip (iii) Low coolant level warning & trip(iv) Fail to crank trip (v) Over crank trip(vi) High and Low speed trip (vii) Low or High battery voltage alarms.(viii)Clogged filter warning and Lack of fuel(ix) High Canopy Temperature(x) Set fail to start protection after failure of the set to start after successfulthree consecutive start attempts. c)Starting system :The engine starting shall be by means of totally enclosed axial type electric starter suitable for 12 voltsDC starting systemcomprising of starter motor, voltage regulator and arrangement for initail exciation complete withbattery of suitableAH Sealed Maintenance Free (SMF) Lead-Acid type as required as per specifications.The battery AH and plates shall be as per OEM standards .the connections shall bewith copper conductor battery leads of required len(d ) Alternator :58.5 kVA 3 phase 0.8 PF 415V, 4 wire 1500 rpmself-excited and self regulatedthrough AVR confirming to IS :4722/BS 2613 suitbale for tropical condition with brush less exciter, housed in screen protected drip proof enclosure. The alternator shall be confirmingto IS 13364 Part-2 & IS 15999 Part-1/ IEC 60034 Part-1 capable of delivering rated output at rated power factor with,a. Terminal voltage differing from the rated value by not more than +/- 5%.b. Frequency differing from the rated value by not more than +/-0.5%.c. Short circuit capacity of 300% for 10 seconds.d. Over load capacity of 110% for one hour. The insulation class of the Alternator shall be class F/ H. The temperature rise shall be limited to class B andIngresses enclosure protection shall IP23 or better. The alternator shall be fitted with suitable Nos. Resistance Temperature Device (RTD) & Bearing Temperature Device (BTD) along with space heaters. 71 (e) Alternator Protection :Alternator should have following protections (i) Over and Under voltage Under and Over frequency warning and trip(ii) Loss of excitation Over current and Earth Fault and Short Circuit Protection(iii) Unbalanced loads Restricted Earth Fault Protection. Differential protection. Diode Failure.(f)Voltage regulator :A rapid response voltage regulator shall be provided to regulate the generated voltage.The overall regulations from no load to full load,including cold to hot variation and load power factor of 0.8 lag to unity shall be within 2% of the normal voltage. The excitation system shall be designed to promote rapid voltage recovery following sudden application and disconnection of load.(g) Acoustic enclousure : The acoustic enclosure should be supplied along with DG set from the manufacturer outlet itself as per CPCB norm.Acoustic enclosure shall be of powder coated and fabricated out of 2mm thick CRCA MS sheet. The canopy shall have four hinged doors, one door with glass window to view proper parameters on the control panel. The canopy and doors shall have inside lining of fire retardant foam/glasswool as acoustic materials. The base frame shall be fabricated in ISMC channel or in sheet metal, with lifting hooks for convenient lifting of complete set i.e. along with canopy, engine and alternator. The sound level shall have less than 75 db (A) at a distance of 1 meter.High quality noise absorbant and fire-retardant grade acoustic Insulation material (P.U. Foam) complying to IS 8183. The allowable temperature raise inside the canopy is 5 to 7 deg. Centigrade. The Measurement of noise should be as per ISO 3744/ ISO 8528 (Part 10) standard.The canopy has the provision of emergency push button, external to the canopy(h) Governor :The governor (Governing Class G2 as per ISO 8528 Part-V) shall be of electronic type suitable for monitoringconstant engine speed within the specified limits for auto parallel and auto load sharing operation.(j) Exhaust : The exhaust piping system shall be supplied with a hospital grade silencer and catalytic converter suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB.The exhaust piping and the silencer shall be wrapped with rock wool and/or calcium silicate. The outside shall be neatly wrapped with aluminum cladding. The exhaust line shall be extended beyond the height of the utility building roof as required by pollution control norms.Suitable supporting structure for installation shalll be provided. 72 (k) Hot air exhaust (Radiator cooling): GI duct shall be provided for hot air exhaust from DG set up to designated place of duct outlet. The duct shall be made of 14 Gauge thick Class-8, Galvanized Iron (GI) Sheet.Galvanised Iron (GI) duct shall be provided for venting hot exhaust air out of the DG room, from radiator hot air outlet point of the DG Acoustic enclosure through nearest brick wall.(l) Fuel Tank : Inbuilt/internal bottom mounted (with-in DG set or with-in base frame) diesel tank of suitable capacity with mounting brackets, complete with fuel inlet, out let, air vent, drain plug, level indicator, inter connection pipes from tank to diesel generator as required. Suitable barrier shall be provided between Diesel tank and the Engine. Fuel tank shall befabricated as per tropical condition of Srinagar with 165 Litres approx. capacity or designed capacity shall be suitable for 8 hrs continous operation. (m) AMF Control Panel :The control panel shall be designed for Automatic ON Mains Failure Operationof the Generator sets. The Panel will be totally enclosed, Dust tight, vermin proof, floor mounted, free standing, cubical compartmentalized type with hinged doors, fabricated from 16 SWG CRCA Steel metal having separatecompartments . The Panel will be epoxy painted powder coated with light grey shade, After Seven Tank treatment, and the Panel / compartment will be fitted with the following instrument and pre-wired with colour coded flexible copper cable with ferule Numbers for easy identification & maintenance. The panel shall be complete with interconnections, insulators, two nos. of earthing lugs and with suitable rating of MCCB at both the end & shall incorporate the followings 73 (i)Neutral contactors.(ii) AMF logic unit having protection for over frequency, under frequency, over voltage, under voltage, Low lube-oil, and high water temperature for Engine.The AMF unit will have provision for Auto Start, Auto Stop of the D.G.Set,with 3 attempts cranking relay.(iii) Main supply voltage monitor.(iv)Combined Meter (MFM) for Voltage, Current, Frequency, KVA,KWH & P. F.(v) CT’s of suitable rating (vi) Static Battery chargerconnected on mains consisting of Transformer, Rectifier, D.C. Voltmeter, D.C.Ammeter, charging rate selector switch (Trickle/Boost, Indicating Lamp, onoff switch)(vii) Auto / Manual mode switch(viii) Miniature Circuit Breaker for Fuses(ix) Hooter 12 volt(x) Annunciations, Alarms & Trips for High water Temperature,Over speed,Set fails to start and D.G. overload (xi) Push Buttons for Breaker on-off,D.G. Start / stop,Engine Trip,Hooter Accept and For Reset (xii)Indicating Lamps for Load on mains,Load on D.G. Set,Low lube oil pressure and High water temperature (xiii)Suitable size of Tinned Copper bus bar will be provided with current density of 1.2 Amp per mm².(xiv) Set of relays and contractor of suitable capacity with along withMCCB of capacity 100 Amps, adjustable (incoming)- 1 Nosand 63 Amps, adjustable (2 Nos) for outgoing , 4 pole,415 Volt. 50 KA for automatic start & automatically shut down of DG set or as per manufacturer recoomendation of suitable rating & capacity. (xv)By pass arrangement by providing on laod change over switch 100 Amps 4 pole to be installed with AMF- 01 Nos.Note : 1.AMF Panel shall be installed outside the acousticenclousre .(ii) Cost of DG set foundation deemed to be included in cost of item.(iv) Contractor should submit necessary drawing to GE/Engr-in-Charge before placing the order. 74 Total amount ofSch A PART-IX ( STAND BY DG SET ) 75 Total amount ofSch A PART-X (SEC-I)(SEWAGE DISPOSAL) 76 Total amount ofSch A PART-X(Sec-II) (SEWAGE DISPOSAL ) Note : This schedule is not pre priced by MES and the pre priced rate indicated as Rs. 0.00 under Col.5 signifies this fact only 77 M&L for RCCSeptic tanks, designed to carry sewage and sullage water, excavation in any type of soil, RCC M-30 design Mix in walls,base slab,baffle walll , roof slb including beams etc PCC (1:4:8) typed D2 (using 40mm graded crushed stone aggregate) below foundation, Vent shaft, connection etc., complete for 150users complete all as specified and directed by Engineer-in-Charge 78 M&L for Soakage wells excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 2.4 M dia X 4.50 M deep(effective depth) complete all as specified and directed by Engineer-in-Charge. 79 Total amount ofSch A PART-X (Sec-II)( SEWAGE DISPOSAL) 80 Total amount ofSch A PART-XI (AREA DRAINAGE)