| 1 | B/R PORTION:-Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing and rubbish off the premises complete all as specified and directed. |
| 2 | Demolition stone slabs and tiles of any description or thickness in floors, aprons etc. as in floor surface complete all as specified and directed. |
| 3 | Demolition of cement concrete (unreinforced) as in ground floor andpavings n.exc 15cm thickness below or above ground level all as specified. |
| 4 | Demolition of brick work or stone/boulder masonary built in CM incl. all quoins, arches, pillars,etc complete all as specified & directed. |
| 5 | M & L forbrickwork with sub class B bricks, straight or curved on plan exc 6m mean radius, built in CM 1:6 complete all as specified and directed. |
| 6 | M & L forbrickwork with sub class B bricks, straight or curved on plan exc 6m mean radius, half brick wall built in CM 1:4, complete all as specified and directed. |
| 7 | M&L for RCC M-25 (design mix) using 20mm graded crushed stone aggregate as in Slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like, complete all as specified and directed. |
| 8 | Form work to soffits of suspended slab such as roof slabs, floor slabs, landings and similar work not exceeding 200mm thick for rough finished surfaces of concrete, complete all as specified and directed. |
| 9 | M&L for mild steel TMT bars 10mm dia and over, cut to length, bent to shape required, includingcranking, bending spirally for hooping for columns, hooking ends and binding with and includingmild steel wire (annealed) not less than 0.9mm dia or securing with clips, complete all as specified and directed. |
| 10 | M&L for 20mm thick granite (of approved type colour) work (table rubbed & polished) in jambs, pillars, window cills, cooking plateform laid over and including 15mm thick cement screed (1:4) and jointed with grey cement slurry and pointed with white cement (1:2) with admixture of pigment to match the colour of granite stone including cutting and and moulding the edges, complete all as specified. |
| 11 | All as per item 10 here in above but in vertical surfaces, complete all as specified and directed. |
| 12 | Providing edge moulding to 18-20mm thick stone of counters vanities etc. including machinepolishing to edge to give high gloss finish etc., complete all as specified and directed. |
| 13 | M&L for machine cut Kota stone slab flooring 18-20mm thick , bedded and jointed with grey cement slurry and pointed with grey cement with admixture or pigment to match the shade of Kota stone slab as approved by GE, laid over and including screed bed or bedding layer of mortar 20mm thick in cement mortar (1:6) including cutting, grinding and mirror polishing, complete all as specified and directed. |
| 14 | M&L for machine cut Kota stone slab flooring 18-20mm thick, as in skirting/dado etc jointed with grey cement slurry and pointed with grey cement with admixture or pigment to match the shade of Kota stone slab as approved by GE, over and including rendering of 10mm thick in cement mortar (1:4) including cutting, grinding and mirror polishing, complete all as specified and directed. |
| 15 | Taking down cement plaster from stone/brick walls including raking out joints, hacking for keys and scrubbing down with water etc, complete all as specified and directed. |
| 16 | M&L for rendering 15 mm thick on stone masonry surface or other than fair face of brick work or on one side of lathingfinished even & smooth without using extra cement in CM 1:6, complete all as specified and directed. |
| 17 | M&L for rendering 15 mm thick on stone masonry surface or other than fair face of brick work or on one side of lathingfinished even & smooth without using extra cement in CM 1:4, complete all as specified and directed. |
| 18 | M&L for 50mm thick PCC 1:3:6 Type C-1 (using 20mm graded crushed stone aggregates) laid in alternate bays (not exceeding 2 sqm each) as in plinth protection, finished the surfaces even & fair, including filled the joints with mastic filling comprising one part of bitumen 85/25 grade and three parts of sand by weight, complete all as specified and directed. |
| 19 | Taking down Chowkhats or framesexc 1.5 sqm but n.exc 4 sqm each with shutters (without taking off shutters from the frames), complete all as specified and directed. |
| 20 | Taking down Chowkhats or framesn exc 1.5 sqmeach with shutters (without taking off shutters from the frames), complete all as specified and directed. |
| 21 | S&F factory made pressed steel frames of size 105x60mm made out of PBI sheet 1.25 mm thick for doors with one or more rebates including necessary fixing lugs, hinge,lock strike plate etc. with one shop coat of primercomplete all as specified and directed. |
| 22 | S&F factory made pressed steel frames of size 125x60mm made out of PBI sheet 1.25 mm thick for doors with one or more rebates including necessary fixing lugs, hinge,lock strike plate etc. with one shop coat of primercomplete all as specified and directed. |
| 23 | M&L for 35 mm thick plain, framed, panelled shutters (any number of panels), with panels of timber flat on both sides (feather edged), or of veneered particle board medium density, wood particle board with commercial face veneers,complete all as specified and directed. |
| 24 | S&F 35mm thick 2nd class hard wood Glazed and skeleton shutters, open rebated and prepared to receive glass, gauge etc (without sash bars), edges of framing plain, chamfered or rounded fitted with cut and mitered beads for securing glass etc. size of members of shutters as specified in SSR Part-I, Section 8, clause 8.24 (a) supplied and fitted to chowkats complete all as specified and directed. |
| 25 | S &F Steel windows with side hung shutters including projecting type hinges with steel handle, and steel peg stay, complete with glazing bars, dovetailed or welded, complete all as specified and directed. |
| 26 | M&L for two coats of synthetic enamel painting on new steel surfaces over 10cms width or girthover and incl a coat of red oxide primer etc complete all as specified and directed. |
| 27 | M&L for Non skid coloured ceramic tiles 7 to 8mm thick (square/ rectangular) area of each tile exc 0.11 Sqm but n exc. 0.18Sqm in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tiles, laid over and including 15mm thick screed bed in CM (1:4), complete all as specified and directed. |
| 28 | M&L for glazed ceramic coloured tiles (450x300mm) x 7mm thick, as in vertical surfaces such as in skirting and dado etc., set and jointed in neat cement slurry and pointed in white or coloured cement to match the colour of tiles over and including 10mm thick back coat layer in cement mortar 1:4, complete all as specified and directed by Engr-In-Charge. |
| 29 | S&F Sheet glass, ordinary quality, 3 mm thick and glazing with oil putty or wooden beads, in square, not exc. 0.5 Sqm pane, complete all as specified and directed. |
| 30 | S&F galvanised mild steel wire cloth 0.56 mm nominal dia of wire and average width of aparture 1.18mm and fixed with tinned tacks or galvanised wire stapple, complete all as specified and directed. |
| 31 | M&L for PCC 1:3:6, type C-1 (using 20mm graded crushed stone aggregate), for fixing of hold fast, copings, plinth bands bed blocks kerb or mud stops,rounded or chamfered angles and edges, including necessary form work complete all as specified and directed. |
| 32 | M&L for preparation of wood and wood based surfaces of any description not otherwise described over 10 cms width or girth and applying two coats of synthetic enamel paint over and incl a coats of pinkprimer all as specified and directed. |
| 33 | M&L for preparing new plastered or unplastered surfaces of walls and applying two coats ofoil bound distemper over a coat of primer,complete all as specified and as directed. |
| 34 | Material & Labour for applying two or more coats of 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives @ 1.43 litre/ 10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/ 10 sqm over new surfaces in painting on walls complete all as specified and as directed. |
| 35 | M&L for preparing new plastered or unplastered surfaces of walls and applying two coats ofdistemper oil emulsion complete all as specified and as directed. |
| 36 | S&F 150 mm long aluminium handles, cast type, anodised and fixed, complete all as specified and directed. |
| 37 | S&F 300 mm long aluminium alloy, anodised, sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extruded sections or cast aluminium alloy and fixed, complete all as specified and directed. |
| 38 | S&F 300mm, ordinary rat tail rod pattern springs including roller and roller plate, complete all as specified and directed. |
| 39 | Taking up or down steel tubing 15mm and connections, including cleaning for refixing or removal to store, complete all as specified and directed. |
| 40 | Taking up or down steel tubing 20 mm and connections, including cleaning for refixing or removal to store, complete all as specified and directed. |
| 41 | S&F rotational moulded polyethylene water storage tankstriple layer (Cylindrical vertical with threaded closed top) hoisted and fixed in position all as spd in SSR Pt-I, of capacity1000 Ltrs incl, screwed for iron pipe or brass ferrule, incl dismentling of existing tank, complete all as specified and directed. |
| 42 | S&F 20mm dia PVC ball cock (PVC floatvalves) complete high pressure with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe and fixed as required to use reducer and check nut, complete all as specified and directed. |
| 43 | Supply & fixed in repairs Gate Valve (ISI Marked), cast copper alloy screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or for unions of 20 mm bore, complete all as specified. |
| 44 | S&Fixed in repair Bib tap 15 mm bore, Chromium Plated, fancy type (long shank). with crutch or butterfly handle screwed down screwed for iron pipe or for brass ferrule, complete all as specified. |
| 45 | S&F GI tubing of 15 mm bore ‘medium grade’ galvanized with all fittings like socket, union, elbow, bend, tees etc fixed to walls and ceilings or laid in floors, complete all as specified and directed. |
| 46 | S&F GI tubing of 20 mm bore ‘medium grade’ galvanized with all fittings like socket, union, elbow, bend, tees etc fixed to walls and ceilings or laid in floors, complete all as specified and directed. |
| 47 | S&F in repair 75mm PVC (SWR) floor trap, plain with grating including jointing with solvent cement, complete all as specified and directed. |
| 48 | S & F in repair 75mm bore PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors or fixed to walls, complete all as specified and directed. |
| 49 | S & F in repair 110mm bore PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors or fixed to walls, complete all as specified and directed. |
| 50 | S& F for 100mm bends (any radius), complete all as specified and as directed. |
| 51 | Dismantling wall and ceiling board (fibre, pulp, PVC,insulation etc) or insulation boards/slabs/blankets, any thickness including cover fillets, complete all as specified and as directed. |
| 52 | Demolition of cement concrete (unreinforced) of any description and in any position not otherwise specifically provided for, complete all as specified and directed. |
| 53 | M&L for plain cement concrete 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in surface channels and drains, complete all as specified. |
| 54 | Extra for forming fair finished drain or channel 30cm inner girth in cement concrete using extra cement, complete all as specified and directed. |
| 55 | M&L for two coats of synthetic enamel painting on old steel surfaces incl preparation of surfaces, over 10cms width or girthover,complete all as specified and directed. |
| 56 | S&F Anodised aluminium snap grid Size of grid 605 x 605mm frame work for false ceiling andHangers 6 mm dia. G.I. (upto 1200mm length) adjusting level fixed to roof slabs by means ofceilling including4mm thick Non asbestos fibre cement building boards fixed or laid/ inserted to timber/GI/Aluminium framework with screwsall as specifiedr complete all as specified and directed. |
| 57 | E&M PORTION:-Taking down carefully copper/ aluminium unserviceable/ perished point wiring (light, fan, socket or power complete including fixture and fittings such as switches, ceiling roses, pandents, regulators, sockets, light fittings,removing material from site for taking credit etc and making good disturbed surfaces of wall, floors, complete all as specifiecd and directed. |
| 58 | M&L for point wiring with two single core 1.5 Sqmm (nominal cross section area) FRLS PVC insulated unsheathed multistranded copper conductor cableand one single core 1.5 Sqmm(nominal cross section area) FRLS PVC insulated unsheathed multistranded copper conductor cable as earth continuity to common earth and connecting to earth dolly running in and including PVC casing & caping (ISI marked) of suitable size with PVC boards of appropriate sizes and all requisite accessories such as PVC elbow, Tee, collars, bends etc. with PVC terminals box & cover for mounting swtches, sockets, fan regulator etc for mounting switches, sockets, fan regulators etc complete all as specified and as directed for the following :- |
| 59 | One light/fan point controlled by one way switch 6 Amp complete all as specified and directed. |
| 60 | One 3/5 pin socket outlet 6 amp on same board complete all as specified and directed. |
| 61 | One 3/5 pin socket outlet 6 amp independent board complete all as specified and directed. |
| 62 | All as per srl item No 58 here in before but for one 3 pin socket outlet 16/20 Amp independent with two single core 2.5 Sqmm size cable as phase & neutral and one single core 2.5 Sqmm as in continuous earth wire complete all as specified and directed. |
| 63 | S&F ceiling rose, 3 terminal, surface bakelite 65 mm x 50mm, PVC/poly carbonate, insulated body, complete all as specified and directed. |
| 64 | S&F switch piano flush type 6 Amp single pole one way, (ISI marked), complete all as specified and directed. |
| 65 | S&F socket outlet2 in 1, 5 pin, 6 Amp flush type universal, complete all as specified and directed. |
| 66 | S&F Switch socket multipurpose combination 2 in 1, 5 pin, 5 and 15 Amp flush type universal, complete all as specified and directed. |
| 67 | S&F Lamp holder PVC/Polycarbonate type with back plate suitable for batten fittings, complete all as specified and directed. |
| 68 | Supply and fixing in repair inverterLED lamp, CDL 12 watt, B22 base, complete all as specified and directed. |
| 69 | Supply and fixing in repair inverterLED batten 1x 20W, with square profile and polycarbonate channel, lithium iron battery with charging time of 8 to 10 hours and backup tile upto 04 hourswith driver, holder incl LED tube light connecting up with with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed. |
| 70 | Supply and fixing in repair LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver including suitable bracket fixed to wall/ pole complete with IP 65/66 protection complete all as specified and directed. |
| 71 | Taking out old unsv exhaust fan from siteand replacement of exhaust fan, steel bodyAC single Phase. 230V of size 300m sweep with, blades, and frame and louvers incl all connecting accessories complete all as specified and directed by Engineer-in-charge. |
| 72 | Taking out old unsv exhaust fan from siteand replacement of exhaust fan, steel bodyAC single Phase. 230V of size 450m sweep with, blades, and frame and louvers incl all connecting accessories complete all as specified and directed by Engineer-in-charge. |
| 73 | S&F in repair sheet metal enclosure for DBs, SPN double door (IP43), 12 ways with 200 amps rated bus bar suitable for 240 volts, AC, 50 Hz, including connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning complete all as specified and directed. |
| 74 | S&F in repairMCBSPN 40-63 amps 415 volts 10 KA \"C\" series, complete all as specified and directed. |
| 75 | S&F in repair MCBsingle pole 6 to 32 amps 240 volts 10 KA \"C\" series complete all as specified and directed. |
| 76 | S&F Earthing complete with galvanized steel earth plate electrode 60cmx 60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to galvanized iron wire 4.0mm dia by means of bolts, nuts and washers of galvanized iron or steel, protected by GI light grade pipe 15mm bore including GI light grade water pipe 20mm dia with funnel all as shown in electric plate No. 3 of 2009 SSR Pt-I and testing complete including earth work in any type of soil, PCC 1:2:4 type B-1 as in earthing pit and cover 50mm thick reinforced with 6mm dia MS round bar @ 10cm C/C both way and MS frame, common salt, charcoal and testing on completion including dismantling unsv earthing, complete all as specified and directed. |
| 77 | S&F 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor served with PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including 4mm dia GI suspension wire, one twin core cable flat or circular of size 16 Sqmm 2 core& including taking down old old unsv service cable connection, complete all as specified and directed. |
| 78 | Supply & install steel tubular swaged poles type 410 SP-31 (9 metres long) complete with CI base plate and finial taper plug, bolts, nuts & screws as specified complete all as specified and directed.Note: Earthwork shall be measured and paid separately |
| 79 | Supply and fix GI bracket of 40 mm dia light grade incl 02 Nos of clamp, nut & bolts etc. complete all as directed by Engr-in-charge. |
| 80 | S&F in replacement factory made PVC pole mounted street light junction box, three phase and neutral, 415 volts, weather proof of size 325x220x150mm depth,accommodated with properly insulated 04 Nos of aluminium busbar of 40 Amps rated current cap, 02 Nos of insulators per each busbar, incl nut bolts & clamps (25x3) for fixing of junction box etc and including MCB SPN 6 Amps - 01 Nos, for connecting of security light fittings, with hinged door and locking bolt complete all as directed. |
| 81 | Supply and fixing in replacement LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermalmanagement in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 82 | Supply and fixing in replacement LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and directed. |
| 83 | M&L for PVC insulated PVC sheathed multi core flexible cable copper conductor 1100 volts grade conforming to IS-694/2010 of size 1.5 Sqmm 3 core incl 25 mm PVC conduit from junction box to light fittings connecting up complete all as specified and directed by EIC. |
| 84 | Supply & laying in trenches/on floor or passing through pipe/ under road incl testing of XLPE Insulated screened PVC bedded galvanized steel strip or wire armoured electric power, cable (heavy duty) with aluminium conductor, 11 KV volts grade, cross sectional area 185 sq mm, 3.5 core incl taking out old ACSR conductor from OH line, complete all as directed by Engr-in-Charge. |
| 85 | Supply & laying in trenches/on floor or passing through pipe/ under road incl testing of XLPE Insulated screened PVC bedded galvanized steel strip or wire armoured electric power, cable (heavy duty) with aluminium conductor, 11 KV volts grade, cross sectional area 25 sq mm, 4 core,incl taking out old ACSR conductor from OH line if reqd, complete all as directed by Engr-in-Charge. |
| 86 | Supply & laying in trenches/on floor or passing through pipe/ under road incl testing of XLPE Insulated screened PVC bedded galvanized steel strip or wire armoured electric power, cable (heavy duty) with aluminium conductor, 11 KV volts grade, cross sectional area 16 sq mm, 4 core,incl taking out old ACSR conductor from OH line if reqd, complete all as directed by Engr-in-Charge. |
| 87 | S&F Earthing complete with galvanized steel earth plate electrode 60cmx 60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to GI strip 32 x 6 mm by means of bolts, nuts and washers of galvanized iron or steel, protected by GI light grade pipe 15mm bore including GI light grade water pipe 20mm dia with funnel all as shown in electric plate No. 3 of 2009 SSR Pt-I and testing complete including earth work in any type of soil, PCC 1:2:4 type B-1 as in earthing pit and cover 50mm thick reinforced with 6mm dia MS round bar @ 10cm C/C both way and MS frame, common salt, charcoal and testing on completion including dismantling old unsv earthing, complete all as specified and directed. |
| 88 | Supplying, installing, testing and commissioning of LT outdoor type panel board factory fabricated cubical kiosk type weather, dust & vermin proof, CPRI approved with locking arrangement and made out of powder coated CRCA sheet of 3.15 mm thick & angle iron frame of size 40 x 40 x 6 mm and suitable size of channel for base complete with 400 Amps rated Aluminium bus bar and separate cabinet for housing mounting for each MCCBs, starter, change over, metering eqpt etc. and prewired with suitable size of copper conductor, cable glands etc. incl mounted on PCC (1:4:8) type plateform 600mm on above GL and incl connecting up complete with the following:- |
| 89 | Incoming: (a)MCCB 160 Amps Cap 35 KA, 4 pole - 01 No(b)On load changeover 160 amps, 4 pole - 01 NoOutgoing : (a)MCCB 100 Amps Cap 25 KA, 4 pole - 01 No(b)MCCB 63 Amps Cap 16 KA, 4 pole - 01 No(c)MCCB 32 Amps Cap 16 KA, 4 pole - 2 Nos(d)MCB 40 Amps Cap 10 KA, 2 pole - 05 No(e)Digital type Ammeter flush pattern type square dial 96 X 96 mm along with selector switch01 No. and suitable CT ratio. (f)Digital type Volt meter flush pattern type square dial 96 X 96 mm along with selector switch & LED indicator - 01 No.(g) Digital timer switch for street light along with suitable contactor, relay, MCB, selector switch incl bypass arrangemets suitable for 0 to 40 Amps |
| 90 | M&L for Plain cement concrete 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) as in foundations filling and mass concrete, complete all as specified and directed. |
| 91 | M&L for Plain cement concrete 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in foundations of pole, stay and mass concrete, complete all as specified and directed. |
| 92 | M&L for cement concrete (1:2:4) type-B-1 (using 20mm graded stone crushed aggregate) as in plinth courses, string courses, lacing courses, copings, bed block, kneelers, apex stones, bed plates, roof kerbs round or chamfered on edges, water troughs, in edging of path (interlocking paver) and the like including weathering, slightly rounded or chamfered angles and throatings etc.including necessary form work complete all as specified and directed by Engineer-in-Charge. |
| 93 | Excavation in trenches n.exc 1.5m wide and exc 1.50m in depth and getting out in any type of soilcomplete all as specified and as directed. |
| 94 | Excavation in trenches n.exc 1.5m wide and for each additional 1.5m or partthereof in depth beyond the first 1.5 m and getting out in any type of soilcomplete all as specified and as directed. |
| 95 | Returning, filling in surplus spoilincluding spreading, leveling, watering and well rammingin layers n. exc. 25 cm thick complete all as specified and directed. |
| 96 | Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 97 | Supply, laying and fixing DWC HDPE pipe for protection of power cable (orange in colour) of size 50 mm dia, complete with fittings and incl cutting, jointing and clamping, complete all as specified and directed. |
| 98 | Dismantling and taking down carefully unserviceable LT overhead line LT AB cable from existing pole complete all as specified and as directed. |
| 99 | M&L for Cross arms, bracings, supports, clamps and back fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bots , in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint. |
| 100 | Supply and fix LT overhead lines on existing poles with XLPE insulated AB cable 3 core x 70 Sqmm +1 core x50 Sqmm including all jointing kits, nut, bolts etc complete including taking down old cable /conductor all as specified and directed. |
| 101 | S&F in replacement XLPE Insulated screened PVC bedded galvanized steel strip or wire armoured electric power, cable (heavy duty) with aluminum conductor, 1100 volts grade, cross sectional area 25 sq mm, 4 core in trenches/on floor or passing through pipe/ under road incl testing ofpassing through pipeor on pole or on wall or crossing the road, complete all as specified and as directed. |
| 102 | M&L for double wall corrugated pipe (DWC) HDPE of 75mm dia conforming to IS: 16205 Part-24 and IEC 61386 (Part-24) for cable protection of cable under/ above ground surface all as specified and directed. |
| 103 | S&F 40mm bore galvanised steel water tubing, light grade including all fittingslaid in trenches / fixed to pole / along wall / floor etc for protection of cable/strip incl fixing to pole with M.S. clamp, nuts, bolts etc complete all as specified and as directed. |
| 104 | Supplying, installing and commissioning of Feeder pillar boxmade of angle iron 65mmx65mmx6mm on all sides welded to 3.15mm thick CRCA steel sheet (Outdoor type) with openable shutters on both sides (Front and rear) having locking arrangement totally enclosed weather proof, spray painted internally & externally with two coats of synthetic enamel paint over a coat of primer, danger notice sticker complete suitable for 440 volts, 3 phase, 4 wire, 50 Hz, with properly insulated colour coated aluminium bus bar, AC supply, Current transformer, selector swtch, Multi Function Metres, LED type indicator lamps, timers, contactors etc. electrically connected complete as per norms and fitted with providing the following switch gears. Notes :-(i)General arrangement and schematic drawings to be approved by the GE before start of fabrication.(ii)All MCCB shall have adjustable overload, short circuit, earth fault with adjustable time delays and instantaneous short circuit. All MCCB shall have ICS = 100% ICU & Each MCCB\"s having seperate enclosures.(iii)Set of Current transformer, selector switch, Multi Function Metres etc. as per incoming and outgoings. (iv)All CTs and PTs shall be cast resin type.(v)All indicator lamps should be of LED type.(vi) The height of panel should be 0.60 mtr from ground level with PCC foundation and the cost for foundation is deemed to be included in quoted rate. |
| 105 | Incoming: (a)MCCB 63 Amps Cap 25 KA, 4 pole - 01 No(b)On load changeover 160 amps, 4 pole - 01 NoBus Bar : (a)01 Set of 200 amps, TPN aluminium bus bars(b)On load change over switch 415 V, 4 pole of capacity 63 amps-01 No(b)MCCB 415volts of cap 32 Amps Cap 25 KA,- 03 Nos(c)MCB SPN, 240 volts of cap 10 Amps, 10 KA - 05 Nos(d)3 ph multifunction meter(e)LED indicator lamp - 01 No (Set of three) |