| 1 | Attending daily complaints of area of Jhansi Military station incl Caleb Vihar and AAU by deputing adequate number of Skilled teams of qualified Electrician and helper any time of the day ( Minimum 01 Skilled Electrician & 02 Helper ) for repair / tightening of end terminals of street light fitting, Flood light, LED strip on poles , High Mast light , Post top lanten of any size/capacity at anyheightand repair the street lights, Flood lights and Post Top lanten having minor faults i.e loose connections, carbon deposition , Shiftingand refixing the same etc and makethe light functional.After rectifying the defects of the electricalsystemreplace the U/S items such as street light , flood lights, LED strips, MCBs TPN ,connection plate , thimbles and timmersmall pieces of electrical cables PVC insulated copper multistranded conductor of sizes 2.5 Sqmm to 6 Sqmm twin core and length not increasing 1.5 mtrs completeall as specified and directed by Engr-in-Charge. (Complaint slip shall be part of the bill) and In Addition one 16 mtrs height hydraulic vehicle with driver & operatorof the same team will operate and manage day to day street light Complaints and update the status of complaints on daily basis and confirmed through concerned JE E/M daily as directed by Engr-in Charge. |
| 2 | Note:- (i) Complaint shall be done within 24 hrs afterintimation by JE E&M and Engineer-in-Charge failling whichpenalty of Rs 250.00 per day per complaint will be levied on contractor.(ii) One supervisorwill report to JE E/M , Engineer -in-Charge on daily basis with complaint register. (iii) Contractor shall be fully responsible for Complaint slip/ Job card prepared and submitted on daily basis ( Format as per provided by the Engineer in Charge).(iv)This item pertains to attending complaints ofstreet light/flood light/LED strips on poles/High mast, MCB, & timer panel including other minor items such as insulating tape, screws etc as required to attend the complaint to the entire satisfaction of user/Engr-in-Charge.(v)Spare parts shall be measured and paid seperately under respective item of Sch \"A\" |
| 3 | Taking down the defective LED street light fitting/security light fitting of various wattage from 45 to 120 watt from 9m/11m pole etc from any position/height and indentifying the fault and replacing the defective LED driver/replacing the burnt wiring and re-assembling the fittings and re-fixing in its original position and testing for proper functioning complete all as directed by Engineer-in-Charge.Note :-LED driver and cable shall be measured and paid separately under relevant items of BoQ. |
| 4 | Supply and fixing in replacement of LED driver as per sample suitable for existing make & model of 120 watt LED street light fitting complete all as specified and as directed. |
| 5 | Supply and fixing in replacement of LED driver as per sample suitable for existing make & model of 90 watt LED street light fitting complete all as specified and as directed. |
| 6 | Supply and fixing in replacement of LED driver as per sample suitable for existing make & model of 70 watt LED street light fitting complete all as specified and as directed. |
| 7 | Supply and fixing in replacement of LED driver as per sample suitable for existing make & model of 60watt LED street light fitting complete all as specified and as directed. |
| 8 | Supply and fixing of 120 Watt LED street light fitting made up of Pressure die-cast aluminium alloy housing with toughened glass, IP66 protection and impact resistance of IK07 and individual high power LEDs with secondary optics having system lumen efficacy ≥100 lm/W, Inbuilt potted electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Over Voltage protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec 13 and BIS complying including taking down of existing unserviceable street light fitting of any description complete all as specified and directed by Engineer-in-Charge.Note :- LM 79test report, LM 80 report with minimum 9000 hrs testing to support 50K life TTC and dirver NABL accreditated report shall be submitted before execution of work to the Engineer - in - charge. |
| 9 | All as per item No. 7.00 here-in-before but of 90 Watt LED street light fitting. |
| 10 | All as per item No. 7.00 here-in-before but of 70 Watt LED street light fitting. |
| 11 | All as per item No. 7.00 here-in-before but of 60 Watt LED street light fitting. |
| 12 | All as per item No. 7.00 here-in-before but of 45 Watt LED street light fitting. |
| 13 | Supply and fixing in replacement of sensor LED street light of 60 W, operating voltage 120 V, input current 195 MA, power factor more than 0.95% lumen efficiency 110 lm/w, PC lens, IP 66 High power LED SMD, connecting the light fitting to electric source with suitable size of PVC insulated copper conductor cable complete all as specified and directed.Note :- warranty as per manufacturer\"s instructions should be printed on light fitting and necessary certifcae to this effect shall be submitted to Eng-in-Charge. |
| 14 | All as per item No. 12.00 here-in-before but of 70 Watt LED street light fitting. |
| 15 | All as per item No. 12.00 here-in-before but of 90 Watt LED street light fitting. |
| 16 | Supply and fix in replacement of 250 Watt LED flood light fitting made up of Pressure die-cast aluminium alloy housing with toughened glass, IP65 protection and impact resistance of IK07 and individual high power LEDs with secondary optics having system lumen efficacy ≥100 lm/W, Inbuilt potted electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Over Voltage protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec 13 and BIS complying including surface mounting using adjustable MS cradle of thickness 5 mm provided with the fixture including taking down existing unserviceable flood light fitting of any description complete all as specified and directed by Engineer-in-Charge. |
| 17 | All as per Serial Item No. 15.00 here-in-before but of 200 Watt LED flood light fitting. |
| 18 | All as per Serial Item No. 15.00 here-in-before but of 150 Watt LED flood light fitting. |
| 19 | All as per Serial Item No. 15.00 here-in-before but of 100 Watt LED flood light fitting. |
| 20 | All as per Serial Item No. 15.00 here-in-before but of 80 Watt LED flood light fitting. |
| 21 | All as per Serial Item No. 15.00 here-in-before but of 50 Watt LED flood light fitting. |
| 22 | Supply and fixing energy saving LED INVERTER TYPE STREET LIGHT 45 WATT AND BATTERY BACK UP OFMINIMUM 8 HOURS environmental friendly, long life , exclusive innovative die-cast aluminium IP 66 security light with high power LEDs as light source ,Suitable for 40 mm GI pipe, 5700K LED ofHavells or equivalant ofSurya/ Philips/ Halonix/ Crompton/ BAJAJ and ,connecting up with twin core twisted flexible copper conductor cableall as directed.Note :- LM 79test report, LM 80 report with minimum 9000 hrs testing to support 50K life TTC and dirver NABL accreditated report shall be submitted before execution of work to the Engineer-in-Charge. |
| 23 | Supply and fixing Semi Integrated Solar Street light 15 Watt, inbuilt Lethium Ion Battery, Input Voltage 12.8V, Lumen efficiency - 110 lm/w, PC lens, IP 66, High power LED SMD complete all as specified and directed by Engineer-in-Charge.Note :- warranty as per manufacturer\"s instructions should be printed on light fitting and necessary certifcae to this effect shall be submitted to Eng-in-Charge. |
| 24 | Supply, fixing installation & testing of All-in-one integrated Solar Street light with built in 40 Watt LED light, Mono Crystalline SPV Panel, Lithium Ferro Phosphate (LifeP04) battery, MPPT charge Controller and PIR sensor with colour temparature 6000-6500K including taking down existing unserviceable solar street light fitting of any description complete all as specified and directed by Engineer-in-Charge. |
| 25 | All as per Serial Item No. 23.00 here-in-before but of 60 Watt. |
| 26 | Supply and fix in replacement of LED Post top light fitting 40 Watt / 45 Watt, made in die-cast aluminum housing with decorative clear opal acrylic diffuser, IP 65 protection, spun aluminum powder coated canopy, low power Warm White (WW) LEDs connected in series and parallel combination with better heat dissipation arrangement with LED color temperature- 3000K ±300K, Highly efficient constant current electronic driver having operating voltage range from 140-280 Volt AC, provided with high voltage, open and short circuit protection, Voltage surge protection 5KV complete suitable for up to 60mm OD pipe entry with fixing bolts including taking down existing unserviceable post top light of any description complete all as specified and directed by Engineer-in-Charge. Note :- LM 79test report, LM 80 report with minimum 9000 hrs testing to support 50K life TTC and dirver NABL accreditated report shall be submitted before execution of work to the Engineer - in - charge. |
| 27 | All as per Serial Item No. 25.00 here-in-before but of 25 Watt LED Post top light. |
| 28 | All as per Serial Item No. 25.00 here-in-before but of 18/20 Watt LED Post top light. |
| 29 | All as per Serial Item No. 25.00 here-in-before but of 12 Watt LED Post top light. |
| 30 | Supply and fix of Circular LED Highbay light fitting 150 Watts, Integral product with LED, driver, aluminium heat sink for better thermal management, Polycarbonate high transmitivity lens and 3 core wire out for input power, with IP65 degree of protection, including taking down existing highbay light fitting of any description at any height from workshops / aircraft hangars complete all as specified and directed by Engineer-in-Charge. Note :- LM 79test report, LM 80 report with minimum 9000 hrs testing to support 50K life TTC and dirver NABL accreditated report shall be submitted before execution of work to the Engineer - in - charge. |
| 31 | Supply and fix in replacement of GI pipe bracket made out of 40mm dia medium grade GI pipe of 1.50mtr long bent to required shape and fixed to steel tubular / PCC pole with clamps made out of 40mm x 5 mm MS flat fixed with suitable nuts, bolts and washers etc including taking down existing unserviceable bracket of any description complete all as specified and directed by Engineer-in-Charge. |
| 32 | Supply and fix SMC (Sheet Moulded Compound) outdoor type junction box of size 200mm x 140mm x 95mm (Outside Dimensions) with 63Amps rated four pole connector, one single pole MCB of 6 Amps rating mounted on DIN rail, stainless steel cable glands of suitable size for incoming and outgoing cables including fixing on steel tubular poles / PCC poles with 25mm x 4mm MS clamps (02 Nos), nuts & bolts etcincluding taking down existing unserviceable junction box of any type and size complete all as specified and as directed. |
| 33 | Making holes (02 Nos - one near cable junction box and other near street light bracket) on existing steel tubular poles of any type, thickness & height through drilling / gas welding work having smooth and chamber edge of hole, for drawing street light control cable through inside of pole complete all as specified and directed by Engineer-in-Charge. |
| 34 | Supply and connect in replacement of PVC insulated and PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volts grade, conforming to IS 694, three core, 2.5 sqmm for connecting from junction box to street light fitting complete all as specified and directed by Engineer-in-Charge. |
| 35 | Supply and connect in replacement of 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor and overall PVC sheathed in service connections one twin core cable flat or circular of size 4 sqmm complete all as specified and directed by Engineer-in-Charge. |
| 36 | Supply and connect in replacement of 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor and overall PVC sheathed in service connections one twin core cable flat or circular of size 6 sqmm complete all as specified and directed by Engineer-in-Charge. |
| 37 | Supply and fix outdoor type street light panel board 25-30 KW capacity, 3 Ph, 4 Wire, made out of 3.15mm thick CRCA Sheet Steel with front openable door fitted with necessary hinges, door locking by Panel lock and provision for Pad Locking duly phosphatized and powder coated with 7 tank process and conforming to IP 54 degree of protection,complete suitable for wall mounting/ pole mounting with suitable clamps, nuts & bolts etc, internally pre-wired with suitable guage of copper wires and connecting up all incoming and outgoing cables with suitable cable glands, lugs, nuts, bolts and washers complete suitable for accommodating and including provision of following switchgears/ components :-a) Incoming MCB, TPN, 100 Amps, 10KA - 01 No.b) 4 pole contactor, 63 Amps - 01 No.c) MCB SP, 6-32A, 10 KA - 04 Nos.d) Astronomical time switch- 01 No.e) Auto/Manual selector Switch - 01 No.f) Terminal block 3 Ph, 4 wire for incoming & outgoing - 01 set |
| 38 | Supply and fixing in repairof three phase8 KW Automatic street light control switch using Infrared Sensor based NATURE SWITCH for automatic switching of street lights. Natureswitch operation should be based on Natural Light Lux level. Switching offilluminance level should be of minimum 30 Lux and Switching off illuminance should be greater thanor equal to 10 LUX. The sensorshould also have part night operation facility of min 4 hrs to maximum 12 hrs. Thecircuit shall have a provision for manual over ride operation. Thesensor along with suitable power contactors and incoming outgoing MCBs should be enclosed in a pole/wall mountable enclosure made of rust proof, electric shock proof , termite proof andFR grade with Hensel Enclosures, conforming to IP66 complete all as directed byEngr-in-charge. The Make of Nature switch Kaatiya Energy Systems,/ Havells/Healer Enterprises. Contactor : BCH/L&T/Schneider, MCBs: Hager/Schneider/L&T/C&S, SMCenclosure and circuit sheet \" Hensel or equivalent approved |
| 39 | Material and labour for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI wire 4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 15mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II |
| 40 | M&Lfor Earthing complete with galvanised steel pipe electrode, 40 mm bore medium grade medium grade, 15 meters length bored & burried directly into ground and preferably vertically in ground with top edge not less than 13.75 meter below the ground level connected with earthing lead of 32x6 mm galvanised iron strip all as shown in Plate No. 2 to the eaarthing test point all as specified or indicated and testing on completion including provision of earth srtip protection by 32x6 mm strip,medium grade GI pipe and watering pipe shall be 40 mm bore medium grade GI pipe including boring & earth work, PCC pit with RCC cover with handle, charcoal, salt, funnel, complete all as specified and directed by Engineer-in-Charge. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II |
| 41 | Excavation in post holes (or similar holes) each not exc 0.5 Cum, getting out, returning filling in and ramming earth or broken rubble mixed with earth around, in layers not exc 25cm, watering, and removing surplus soil to a distance not exc 50m and making good surface complete in any type of soil. |
| 42 | Supply and erection in replacement of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 meters long) including painting of poles with two coats of aluminium paint over a coat of red oxide primer on all exposed surfaces and black bituminous paint on embedded portion and Zebra marking on pole with black paint up to one meter height above PCC coping including pasting of radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and writing the pole number in black colour on yellow background at a suitable place on the pole including taking down existing unserviceable pole of any description complete all as specified and directed by Engineer-in-Charge. (Note: Excavation and concrete shall be measured and paid separately under relevant items of this BOQ). |
| 43 | M&L for PCC 1:4:8 type D2 using 40mm graded stone aggregate as in foundations of pole/ stay assembly complete all as specified and directed by Engineer-in-Charge. |
| 44 | M&L for PCC 1:3:6 type C1 using 20mm graded stone aggregate as in coping of pole including necessary form work complete all as specified and directed by Engineer-in-Charge. |
| 45 | Supply and fix LED curb stone light ( RED,Yellow , Blue , White , Amber ) fittings of lentgh 500mm, height 200mm and width 150mm, with curb angle 45 degree, operating voltage 36 volts DC power supply, having foundation height 40mm, foundation width 20 mm, foundation stand hole 10 mm dia with 2 Nos of foundation rod having 8 mm dia to make curb stone theft proof and immovable,with load carrying / bearing capacity upto 800 Kgs , in each curb stone LED strip length 465mm , Nos of LED in each strip 22, power consumption 2.34W per curb stone having one connectors with 2 Nos (1 male & 1 Female) with 2 core wire, Complete all as specified and directed by Engineer in charge. |
| 46 | Supply and fix in replacement of 80mm dia bore tubes, \"medium grade\" galvanized, with all fitting and fixed complete to walls/ poles or laid in trenches/ floors for cable protection complete all as specified and directed by Engineer-in-Charge. |
| 47 | M&L for pruning of tree branches up to 2.0 meter clearance all around HT/LT overhead lines and depositing where directed at a distance not less than 50m complete all as specified directed by Engineer-in-Charge. Note: The item will be measured in span length between poles. The approx span length is 50m. |
| 48 | M&L for painting of PCC Pole (cross arms,clamp etc) with two coat of aluminium paint and including preparation of surface and painting up to the height of 1.2 M pole 9 m long with two coats of synthetic enameled paint including preparation of old surfaces and making colour bands and rewriting the pole number complete all as directed |
| 49 | M&L for preparation of old painted surfaces of LT 9.0m long poles and painting with one coat of aluminium paint on all steel surfaces such as poles, channels, angles, clamps, nuts, bolts and washers of any description including replacement of old radium stickers of any description with new radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and numbering of pole shall be done in black colour on yellow background at suitable place on the pole complete all as specified and directed by Engineer-in-Charge. |
| 50 | M&L in replacement of Power Cables, Aluminum Stranded Conductor 16 sqmm, 4 core, XLPE Insulated, Cores laid up, PVC Inner sheathed, Armoured with galvanized wire or galvanized steel strip, overall PVC Sheathed, 1100V Grade as per IS 7098(Part 1) 1988 complete laid in trenches / floors / fixed to poles / walls / drawn through pipes etc including provn of lugs, glands, nuts, bolts & washers etc for connecting in LT feeder pillar box / transformer bushings/LT OH lines and testing on completion all as specified and directed by Engineer-in-Charge. Note: Excavation, earth work and provn of cable covers / protection pipe etc shall be measured and paid separately under relevant items of BOQ. |
| 51 | All as per Serial Item No. 49.00 here-in-before but of 25 Sqmm, 4 Core. |
| 52 | All as per Serial Item No. 49.00 here-in-before but of 10 Sqmm, 2 Core. |
| 53 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting in hard / dense soil for laying of cables complete all as specified and directed by Engineer-in-Charge. |
| 54 | Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed by Engineer-in-Charge. |
| 55 | Removing surplus excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 56 | Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etcfor protection of LT cable XLPE grade 1100 volts complete all as specified and directed by Engineer-in-Charge. |
| 57 | Supply and fix LED strip light 24 Watt warm / coolwhite/ tricolour, 18 meter length, flexible PBC body incl driver, IP 20 Protection with accessories such as 06 Amp plug Top, flexible cable etc complete all as specified and directed by Engr-in-Charge.Make: Phillips/ Havells/Bajaj |
| 58 | Supply and fix LED strip light 24 Watt warm / coolwhite/ tricolour, 45 meter length,decorative lighting fixture featuring small light bulbs linked together and incased in a PVC jacket to create a string of lights with flexible PBC body incl driver, IP 65 Protection with accessories such as 06 Amp plug Top, flexible cable etc complete of Make: Phillips/ Havells/Bajaj |
| 59 | Supply and fix inreplacment of LED Bollard light having step profile placed on top ideal for archistripectural outdoor lighting typically giving off light from the sides suitable to illuminate walkway,steps or pathway with rated power 10 W complete all as specified and directed. |