| 1 | Operation and routine maintenance of sub-station equipment having Oil type transformers 315 KVA - 1 no. (11 KV/415 V Indoor type) i/c HT panel, L.T. panels, capacitor panels & Floor panels etc. and 1 No. of 125 KVA D.G. setsi/c other allied panels and Running Maintenance & Operation ofInternal Electrical Installations (IEI) and ExternalLighting including high mast lighting by deploying following staff as per inventory andadditional Terms and conditions attached etc.complete as reqd.a)Electrician cumOperator-3 Nos.(1 No. in each shift total three shift i.e. 6 AM to 2 PM & 2 PM to 10 PM & 10PM to 6AM )b) Khallasi - 2 Nos. ( 1 No. in each shift total two shift i.e. 6 AM to 2 PM & 2 PM to 10 PM ).(Note:All Tools and Plants (T&P) including tower wagon suitable to maintained fittings mounted up to height 12 Mtrs. shall be made available at the site throughout the contract period by agency.) (biometric machine should be installed |
| 2 | Servicing (B-Check Maintenance) of 125 KVA DG set by OEM / authorised dealeras complete as required at RSKP.a) Fuel filter- 2 No.b) cartridge and lubricant oil filter -2 No.c)Water Separator from fuel- 1 No.d)Inhibitor -3 Nos.e)Coolant test Kit-1 No.f) Radiwash - 3 Ltrg)Air filter(Safety)-1 No.h) Air filter(Primary)-1 No.i)Valvoline Premium blue 7800 plus 1/50 Ltr.- 1 No. |
| 3 | Servicing of H.T. OCB Complete with dismantling, Cleaning, alignment, adjustment of gaps between phases, lubricating all moving parts adjustment for smooth mechanical operation etc complete as required. |
| 4 | Testing and Calibration of IDMT relay with secondary injection test set i.e. cleaning servicing of contacts tightening of loose contacts testing repair etc., complete as required. |
| 5 | Servicing / Overhauling 800/1000 Amp ACB\"s with dismantling, cleaning, alignment, adjustment of gaps between phase, lubricating all moving parts adjustment for smooth mechanical operation etc complete as required. |
| 6 | Dehydration & filtration of transformer oil (315 KVA transformer indoor ONAN) to upgrade the dielectric strength of oil upto 50 KV as required including topup of transfer oil etc. complete as required. |
| 7 | Supplying and filling of fresh transformer oil in existing transformer etc complete as required. |
| 8 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 9 | 63 A,30KA,FPMCCB |
| 10 | 100 A,30KA,FPMCCB |
| 11 | 125A,36 KA, FP MCCB |
| 12 | 250 A,36KA,FPMCCB |
| 13 | Supplying and making straight through joint with heat shrinkable kit includingferrules and other jointing materials for following size of PVC insulated and PVC sheathed/ XLPE aluminum conductor cable of 1.1KV grade as reqd. |
| 14 | 3½ Cx 185 sq.mm |
| 15 | 3½ Cx 95 sq.mm |
| 16 | Labour and T&P charges for locating fault in LT cable by fault locating equipment including pin pointing of particular location of fault etc as required. |
| 17 | Digging of Pit for providing cable joint as per site located by fault Locator machine including refilling of soil complete as required. |
| 18 | Supplying and replacement(including deduction of cost for replaced item) of PVC insulated copper wire offollowing sizein the existing surface/ recessed conduit i/c connection, testing etc.as required. |
| 19 | 3x 1.5 sq.mm |
| 20 | 3x 2.5 sq.mm |
| 21 | 3x 4.0 sq.mm |
| 22 | Supplying and fixing following modular switch /Socket on the existing modular plate & switch box including connection but excluding modular plate etc. as required. |
| 23 | 5/6 Amp Switch. |
| 24 | 15/16 Amp Switch. |
| 25 | 3 pin 5/6 Amp Socket outlet. |
| 26 | 6 pin 15/16 Amp socket outlet. |
| 27 | Supplying of following MCB\"sfor Electrical Panel Board/ feeder pillar/ pole including testing etc as required. |
| 28 | 6 to 32 AmpSP MCB \"C\" series. (10 KA Capacity) |
| 29 | 32 AmpDP MCB \"C\" series. (10 KA Capacity) |
| 30 | Supply of PVC insulated and PVC sheathed / XLPE armoured aluminium conductor power cable (As per IS 7098 (Part-1) of 1.1 KV grade i/c connection testing etc.as required. |
| 31 | 3.5 x 50 sq.mm |
| 32 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.a) upto 35 sqmm |
| 33 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.a) Above 35 sq. mm and upto 95 sq. mm |
| 34 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.a)90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 35 | Supplyof 2 x10 sq mm al armoured XLPE power cable etc complete as required. |
| 36 | Comprehensive (Semi) Annual Maintenance of 6 Nos. RO System 50 LPH capacity connected with water coolers i/c three mandatory services (cleaning of All Filters), repair/ replacement of all electrical and electronic spare parts and one time replacement of consumables once in a year like Particulate Filter 20” or (2 x 10”), Sediment Filter 20” or (2 x 10”), Pre Carbon Filter 20” and Post Carbon Filter 20” (except membranes), attending complaints within 24 working hourswith complete overhauling and servicing etc. as required.Dismantle retained to contracter. |
| 37 | Replacement of RO TFC Membrane 75 GPD i/c testing, commissioning etc. as required old dismantle shall be retained by the contractor |
| 38 | Extra Filters Required to be replaced after using its life to enhance the funcioning of the machines.i/c Leak testing, commissioning etc complete as reqd at site. old dismantle shall be retained by the contractor |
| 39 | 20\" Particulate / Sediment Filter |
| 40 | Supply and replacement of 20\"\" pre filter spun 5 micron forRO system etc complete as required. |
| 41 | Supply and replacement of feed water pressure generating pump with automated switch for 50 LPH capacityRO system etc complete as required. |
| 42 | Supply and fixing of 20\"\"x 2.5 bowl for pre filter 50 LPH capacity RO etc complete as required |
| 43 | Supplying and fixing of Automated on/ off Switching Device for Level monitoring of Water cooler in existing 50 LPH RO at site. |
| 44 | Supply, Replacement, Testing & Commissioning of Mushroom BellBrass Nozzle in existing fountain etc complete as required. |
| 45 | Supply, Replacement, Testing & Commissioning of Adjustable Type Fountain Nozzle Size 3mm Ball Joint Jet Brass Nozzle in existing fountain etc complete as required |
| 46 | Service of following type air conditioner of 2.0 ton capacity i/ccleaning of cooling coil & condenser with chemical, washing the complete air-conditioner, painting of sheet metal parts hose plate with synthetic enamel i/c painting of exposed cooling & condenser pipes with anti corrosion paint, oiling of fan motor, etc as required. |
| 47 | split type |
| 48 | Servicing of water cooler 40/80/120/150 ltr. Capacity oiling in fan motor, Cleaning of base plate and condenser coil with chemical and cleaning of water tank etc. complete as required. |
| 49 | supply andreplacement of burnt compressor withnew compressor including flushing thesystem, leakage, testing, vacumising, cleaning of condenser, gas charging, cartage i/c testing and commencing complete as required. |
| 50 | rotary compressor |
| 51 | Supplying & replacement of condenser coil suitable for various make of split type air-conditioner of 2.0 Ton capacity having copper piping, i/c welding, pressure testing etc as required. |
| 52 | Supplying & replacement of Evaporatingcoil suitable for various make of split type air-conditioner of 2 ton capacity having copper piping, i/c welding, pressure testing etc as required. |
| 53 | Supply and charging of refrigerant for 2.0 Ton capacity following type air conditioner of various make i/c testing of pressure and cooling etc. complete as required. |
| 54 | Split Type /Ref Charging |
| 55 | Repairing of PCB of Split type ACi/c connection, testing etc. complete as required. |
| 56 | Rewinding of fan motor 2.0 Ton capacity Air conditione i/c replacement of Gun Metal bushes and testing etc. Complete as required. |
| 57 | Routine preventive maintenance of Air conditioners upto 2 ton capacity & water coolers i/c attending & removal of day day complaints, cleaning of filters & grills of A.C. cleaning of water tank ,complete as required by deputing 1 no of A.C. mechanic and 1 no. khallasi for 1/2 day or as and when required. |
| 58 | Supplying and replacement of following part of air conditioner i/c connection, testing etc complete as required. |
| 59 | Front grill suitable for existing Air Conditioners. |
| 60 | Running capacitor (36 MFD/50 MFD) |
| 61 | Capacitor 6 MFD |
| 62 | Rewinding of fan motor suitable for 150 Ltr capacity water cooler i/c replacement of bushes, testing, commissioning etc. complete as require. |
| 63 | Supply and replacement of following part in water cooler i/c connection, testing etc. complete as required |
| 64 | Thermostat |
| 65 | Over load protection with relay box |
| 66 | Float Valve Assembly |
| 67 | Water tap |
| 68 | Supplying and installation of Copper refrigerant piping(Liquid + gas)with suitable size of insulation ,tie rod ,hanger etc.complete as required. |
| 69 | Supplyingand installation of suitablemotor for idu/odu uints. i/c connection,testing etc. complete as required. |
| 70 | Installation of Split/window type air conditioner including providing and fixing wooden frame for fixing the housing of air conditioner on the existing window testing etc. complete as required. |
| 71 | Supplying and replacement of unserviceable pair of PCBfor both indoor unitand out door unit of air conditioner,suitable for various make of 2 Ton inverter type air conditioneri.c connection,testing etc. complete as required. |
| 72 | Supply and fixing of CO2 typeFire Extinguisher of 4.5 Kg, Duly ISImarked conforming to IS: 15683, complete with delivery hose horn , wheel type release valve, locking arrangement, pressure gauge, operation manual and bracket etc. complete as required. |
| 73 | Supply and fixing of mechanical foam (AFFF) Fire Extinguisher stored pressure typeDuly ISImarked conforming to IS: 15683, capacity 9 Ltr complete with delivery hose , squeeze grip release valve, locking arrangement, pressure gauge, operation manual and bracket etc. complete as required.operating temperature +5 degree to +60 degree |
| 74 | Refilling of fire extingusher including re-installing the same of following type and capacity etc complete as required. |
| 75 | Trolly Mounted ABC DRY powder based fire extingusher 25Kg. |
| 76 | Carbon dioxide (CO2) type fire extingusher 4.5Kg |
| 77 | ABC DRY powder based fire extingusher 2 Kg |
| 78 | ABC DRY powder based fire extingusher 4 Kg |
| 79 | ABC DRY powder based fire extingusher 5 Kg |
| 80 | mechanical foam type 9 Ltrs capcity |
| 81 | providing and installation one set (6 nos buckets set) galvanized mild steel fire buckets with stand and canopy suitable for 6 buckets, bucket should be as per IS-2546 etc complete as required. |
| 82 | Lifting out of submersible pump set from the exiting bore well up to the required depth along-with existing G.I. pipes and accessories etc. i/c dismantling of G.I pipe and disconnecting the sub. cable etc. complete as reqd. |
| 83 | Lowering of sub. pump set in the existing bore well up to the required depth along with existing G.I pipe and sub. cableetc , water proof jointing of sub. cable. Replacement of reqd. nuts, bolts, washers and packing, nipple, reducer, connection testing, etc. complete as reqd. |
| 84 | Supplying of copper conductor flat submersible cable offollowing sizei/c testing,connection etc. complete as reqd. |
| 85 | 3 x 2.5 sq.mm |
| 86 | 3 x 10 sq.mm |
| 87 | Supplying of following size of double G.I. flanged (ISI marked ) GI pipe \"B\" class duly threaded & welded with necessary pipe fittings, bends, elbow etc. complete as reqd.a) 65 mm dia. |
| 88 | Supplying of following size of double G.I. flanged (ISI marked ) GI pipe \"B\" class duly threaded & welded with necessary pipe fittings, bends, elbow etc. complete as reqd.a) 50 mm dia. |
| 89 | Repairing & rewinding of 3 phase sub./single phase motors of following capacity with cartage, dismantling, reassembling i/c supply &replacememt / repairing of damaged parts of motors and making good for operation i/c connection, testing, painting etc. complete as reqd. |
| 90 | 5 HP sub. motors |
| 91 | 3 HP sub. motors |
| 92 | Repairing of sub. pump of the following stages &dia with cartage, dismantling, reassembling, supply & replacement / repairing of damaged parts of pump and making good for operation i/c testing painting etc. complete as reqd. |
| 93 | Up to all stages 6\"dia submersible pump sets. |
| 94 | Up to all stages 4\"dia submersible pump sets |
| 95 | Repairing & rewinding of following capacity 3 phase open well sub pump sets including cartage, dismantling, reassembling, supplying & replacement/ repairing of damaged parts of pump sets and making good for operation including connection testing, painting etc. complete as required. |
| 96 | 5 H.P |
| 97 | Repairing, Rewinding & servicing of sub. Dewatering pump set i/c repairing / replacement of following worn out part and testing etc as required. i) .5KW/.75 KW/1.1KW pump set. |
| 98 | Supplying & replacement of following control gear / accessories in the existing installation for electric panel boards, motor starters, connection, testing etc. as reqd. |
| 99 | Single Phase Preventer |
| 100 | D.O.L starter (9-14 Ampere) |
| 101 | Supplying of sub. Pump set duly coupled with suitable rating 3 phase, 415 volt, 50Hz, sub. Motor. The pump sets shall be suitable for the following duties. a) Head Range:- 72-24 Mtr. Discharge Range :- 130-500 LPM. Minimum HP/Stage:- 5 HP/6 Stage. Outlet Size:- 50 mm |
| 102 | Supplying of sub. Pump set duly coupled with suitable rating Three phase, 415 volt, 50Hz, sub. Motor. The pump sets shall be suitable for the following duties. a) Head Range:- 6-55 Mtr. Discharge Range :-450-100 LPM. Minimum HP/Stage:- 3 HP/5 Stage. Outlet Size:-50 mm |
| 103 | Taken out of fallen & stuck sub. pump set from the existing bore well up to all depth including sub. cable, G.I. Pipe etc. complete as reqd. |
| 104 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 105 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required |
| 106 | Supplying and fixing 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of triple pole & neutralin the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 107 | Supplying of following size of XLPE insulated & PVC sheathed, aluminium conductor armoured power cable of 1.1KV grade, connection testing etc. as reqd.a) 4x 25 sq mm |
| 108 | Supplying and replacementofoutdated/wornout LED with200 WattLED floodlight fitting complete with suitable lens & other accessorieshighly efficient made ofpressure die cast aluminium housing ,extruded aluminium heat sink& enclosed with toughened glassIP-66 protection and achieving 26000 Lumens & fitting not more than 200 watt i/c existing bracketi/c connection testing complete as per technical specifications attached etc as required |