| 1 | DDC Panel-1: Supply, Installation, Testing and Commissioningof Automation stations/DDC Controller with I/O module etc., The controllers shall be net workable type with real time clock and historical database of min 2 Mb.DDC panelwith Suitable Control Panel enclosure and accessories (MCB, TBs, DIN rail, PVC channels, PVC double compressoin glands, etc) including DDC controller with minimum 80 I/Os as per technical specifications. All the internal wiring using FRLS wire shall be part of the item.DDC panel shall be as per the following configuration: DDC controller with min. 80 I/Os -1 No.230V AC/24 VACTransformer- 2 Nos. Power supply for controller 24 V / 10 A - 1 No. 10 inch HMI - 1 No.Min. 4- port ethernet switch - 1 No.5 A relays with base - 20 Nos. Seperate power supply (24V DC supply, 10 A rating) for field equipments- 1 No. 230V AC power supply for field equipments- 1 No.Note: The software development (like DDC programing, BMS GUIs, etc) required for the project will be within the scope of the supplier. |
| 2 | DDC Panel-2: Supply, Installation, Testing and Commissioningof Automation stations/DDC Controller with I/O module etc., The controllers shall be net workable type with real time clock and historical database of min 2 Mb.DDC panelwith Suitable Control Panel enclosure and accessories (MCB, TBs, DIN rail, PVC channels, PVC double compressoin glands, etc) including DDC controller with minimum 200 I/Os as per technical specifications. All the internal wiring using FRLS wire shall be part of the item. DDC panel shall be as per the following configuration: DDC controller with min. 200 I/Os -1 No.230V AC/24 VACTransformer- 2 Nos. Power supply for controller 24 V / 10 A - 1 No.10 inch HMI - 1 No. Min. 4- port ethernet switch - 1 No. 5 A relays with base - 20 Nos.Seperate power supply (24V DC supply, 10 A rating) for field equipments- 1 No.230V AC power supply for field equipments- 1 No. Note: The software development (like DDC programing, BMS GUIs, etc) required for the project will be within the scope of the supplier. |
| 3 | SITC of Programming software (s) for DDC of suitable I/O capacity. Software shall be able to program above DDC and HMI. Also provide SCADA as per the requirement. |
| 4 | SITC of Compact and Portable Programming Terminal: intel i5, 8 MB cache, 16 GB DDR4, 512 GB SSD, 1 TB HDD, 15 inch display, latest MS Operating system suitable for DDC programming software/ SCADA. |
| 5 | SITC of BMS workstation along with the Software : suitable for BMS software,intel i5, 8 MB cache, 16 GB DDR4, 512 GB SSD, 1 TB HDD, 32 inch display (2 nos.), latest licensed MS Operating system suitable for DDC programming software. BMS Software / SCADA : Shall be able to communicate all the sub-systems / DDC panels and provide required interlocks. |
| 6 | SITC of Server Computer: Intel Xeon E-2200 series (4 core, 3.4GHz, 8MB, 71W)S100i SW RAID with 4 SATA ports,4 PCIe 3.0 slots HPE 350W E-star 1.0 Pwr Supply FIO Kit Embedded 2-Port 1GbE HPE Ethernet 332i Adapter. 32GB (2x16GB) Dual Rank x8 DDR4-2666 Unbuffered Standard Memory Kit (2 Nos)HPE 2TB 6G SATA 7.2K rpm LFF (3.5in) Non-hot Plug Entry 512e, MS WinSvrSTDCore 2019 OLP 16Lic NL CoreLic, SQLSvrStd 2019 SNGL OLP NL, SQLCAL 2019 SNGL OLP NL UsrCAL, 32 inch Display (2 Nos.), wireless Mouse and wireless keyboard |
| 7 | Voltage to Current convertor: SITC of Muti-channel 4-20mA output, Input: 0-5V, 0-10 V, loop powered 24V, deviation: 0.1 % of full-scale value along with mounting Box |
| 8 | Current to Voltage convertor: SITC of Muti-channel 0-5V, 0-10V output, Input: 4-20mA loop powered 24V, deviation: 0.1 % of full-scale value along with mounting Box |
| 9 | Design, Fabrication, Supply, Installation, Testing & Commissioning of floor/wall/MS stand mounted, MS fabricated and powder coated, Power Distribution Board Panel as per following details & our tender specifications: |
| 10 | Incomer: 100A FP MCCB (Ics≥25kA) with microprocessor based trip release for o/c, s/c & e/f (LSIG) protection having independent adjustable current & time settings for o/c, s/c & e/f protection Outgoing: a) 63A TP MCB: 08 Nos. b) 32/25/20A SP MCB: 12 Nos.VTPDB, 12-way per phase |
| 11 | Incomer: 63/32A FP RCBO (10kA, 30mA sensitivity) Outgoing: 10/16/20A SP NCB: 36 Nos. VTPDB, 12-way per phase |
| 12 | Supply, laying, testing and commissioning of following instruments cables suitable for DDC system, complete with end terminations, junction boxes, supports etc., all as per system requirements. |
| 13 | 500 Volt, 3 pair, 1.0 sqmm, twisted pair, annealed plain stranded circular shaped copper conductor, individual pair & overall screened with drain wire, GI round wire armoured, FRLSH PVC outersheathed instrument cable |
| 14 | 500 Volt, 2 pair, 1.0 sqmm, twisted pair, annealed plain stranded circular shaped copper conductor, individual pair & overall screened with drain wire, GI round wire armoured, FRLSH PVC outersheathed instrument cable |
| 15 | Un-armoured FRLS PVC insulated CAT-6 UTP Ethernet cable |
| 16 | Supply, laying & installation of 25 mm dia wire reinforced PVC Conduit complete with all fittings(PVC Glands/Coupling accessories etc) and other hardware & accessories. |
| 17 | Supply, Instaaltion. Testing & Commissioing of loackable powder coated relay box with 4 No. Heavy Duty 230V AC relay/ auxilliary contact having 2NO+2NC potential free contact, gland plate & all other required hardware & accesories. |