| 1 | Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, (fittings such as switches, ceiling roses, pendants, regulators, sockets etc. to be measured separately), removing materials and making good disturbed surfaces of walls, floors, etc. complete all as specified and directed. |
| 2 | M&L for Point wiring for one light point / fan point / bell point controlled by one switch with 1.5 sqmm PVC insulated unsheathed, FRLS multistranded copper conductor cable (red, yellow & blue colour) in and including non metalic rigid PVC concealed conduit ISI marked, not less than 20mm dia, medium duty with all necessary fittings such as tee, elbow, socket includingsunken steel boxes of suitable size with 3mm thick plastic laminated backelite sheet top for mounting switches sockets etc including FRLS PVC insulated unsheathed multistranded copper conductor cable of size 1.5sqmm (green colour) as continuous earth wire and connecting to earth dolly, and making good to distrubed surfaces of wall/floor to match to existing finishes etc complete all as specified and directed.Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces. |
| 3 | All as per description of serial item No. 2.00 here in before but in existing PVC Conduit. |
| 4 | All as per description of serial item No. 2.00 here in before but in & including PVC casing and capping with all the necessary fittings & accessories i.e Tee, elbow, socket etc. |
| 5 | M&L for Point wiring for one 2 way light point etc controlled by two switches with copper conductor cable FRLS multistrand of size 1.5 Sqmm (red, yellow & blue colour) PVC insulated and unsheathed with 1.5 Sqmm PVC insulated copper conductor cable as earth wire (green colour), in and including non metalic rigid PVC Conduit of medium dutynot less than 20mm dia and with sunk cast iron boxes covered with 3.00 mm thick plastic laminated sheet top cover for mountingswitches, sockets, regulators etc.connecting to earth dolly and making good disturbed surfaces all as specified and directed. Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces. |
| 6 | All as per description of serial item No. 5.00 here in before but in existing conduit |
| 7 | All as per description of serial item No. 5.00 here in before but in & including PVC casing and capping with all the necessary fittings & accessories i.e Tee, elbow, socket etc. |
| 8 | M&L for Point wiring for one socket outlet 5 Amp 3/5 pinfor independent board etc controlled by one switch with copper conductor cable FRLS multistrand of size 1.5 Sqmm (red, yellow & blue colour) PVC insulated and unsheathed with 1.5 Sqmm PVC insulated copper conductor cable as earth wire (green colour), in and including non metalic rigid PVC Conduit of medium dutynot less than 20mm dia and with sunk cast iron boxes covered with 3.00 mm thick plastic laminated sheet top cover for mountingswitches, sockets, regulators etc.connecting to earth dolly and making good disturbed surfaces all as specified and directed. Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces. |
| 9 | All as per description of serial item No. 8.00 here in before but for one 3/5 pin 5 amps socket outlet in existingConduit. |
| 10 | All as per description of serial item No. 8.00 here in before but for one 3/5 pin 5 amps socket outlet in & including PVC casing & capping with all the necessary fittings & accessories i.e tee, elbow, socket etc. |
| 11 | All as per description of serial item No. 8.00 here in before but for one 3/5 pin 5 amps socket outlet on the same board with other switches. |
| 12 | All as per description of serial item No. 8.00 here in before but for one 3/5 pin 5 amps socket outlet on the same board with other switches in existing conduit. |
| 13 | All as per description of serial item No. 8.00 here in before but for one 3/5 pin 5 amps socket outlet with other switches in & including PVC casing & capping with all the necessary fittings & accessories i.e tee, elbow, socket etc. |
| 14 | M&L for point wiring for one 15 Amp independant socket outlet using 4 Sqmm FRLS PVC insulated unsheathedmulti-strand copper conductor cable (red, yellow & blue) drawn through & including non metalic rigid PVC concealed conduit (ISI marked)not less than 20mm dia, medium duty with all necessary fittings & accessaries including sunken steel boxex of suitable size covered with 3mm thick plastic laminated bakelite sheet top incl FRLS PVC insulated unsheathed multistranded copper conductor cable of size 4 Sqmm (green colour) earth wire connected to earth dolly complete all as specified and directed.Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces. |
| 15 | All as per description of serial item No. 14.00 here in before but for 15 Amp socket outlet in existingConduit. |
| 16 | All as per description of serial item No. 14.00 here in before but for 15 Amp socket outlet in & including PVC casing and capping with all necessary fittings & accessories i.e. tee, elbow, socket etc. |
| 17 | M&L for point wiring for one metal plug top for Geyser / AC using 4.0 Sqmm FRLS PVC insulated unsheathed multi-stranded copper conductor cable drawn through & including non metalic rigid PVC concealed conduit (ISI marked) not less than 20mm dia medium duty with all necessary fittings, incl FRLS PVC insulated unsheathed multistranded copper conductor cable of size 4.0 Sqmm (green colour) earth wire connecting to earth dolly complete all as specified and directed.Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces. |
| 18 | All as per description of serial item No. 17.00 here in before but for one metal plug top for Geyser / AC socket outlet in existing Conduit |
| 19 | All as per description of serial item No. 17.00 here in before but for one metal plug top for Geyser / AC socket outlet in & including PVC casing & capping with all the necessary fittings & accessories i.e tee, elbow, socket etc. |
| 20 | S&F in repairs Switch pianoflush button single pole one way 6 Amps 240 volts polycarbonate body complete all as specified and directed. |
| 21 | S&F in repairs switchpiano, flush button, single pole two way, 6 amps 240 Volt, polycarbonate body complete all as specified and directed. |
| 22 | S&F in repairs bell push switch, piano flush button single pole, one way, 5 Amps 240 volts polycarbonate body complete all as specified and directed. |
| 23 | S&F in repairs socket outletmulti purpose 2 & 3 pin, 6A, 230Volts flush type complete all as specified and directed. |
| 24 | S&Fin repairs socket outlet 2 in 1, 3 pin, 6 & 16 Amps, flush type, single pole, oneway,230 Volts complete all as specified and directed. |
| 25 | S&F in repairs switch piano, flush type, single pole, oneway, 16 Amps 230 Volts complete all as specified and directed. |
| 26 | S&F in repairs stepped type electronic mini/deluxe fan regulator 100 Wattrotary step all as specified and directed. |
| 27 | M&L for modular point wiring for one light/fan/bell point controlled by one switch complete with 1.5 Sqmm multistranded FRLSPVC insulated unsheathed, FRLS, multistranded copper conductor cable 1100 volts grade (red, yellow & blue) in and including medium duty non metallic rigid PVC concealed conduit 20 mm dia including conduit accessories like bends, tees junction boxes etc fixed concealed/recessed in wall or ceiling etc including 1.5 Sqmm single core FRLS PVC (green) insulated unsheathed multi stranded copper conductor 1100 Volts grade as earth continuity wire connected to earth dolly matching with surrouding with modular sunken steel boxes zinc oxide plated of suitable size including modular sheets of suitable module and back plates etc. complete all as specified and directed.Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces. |
| 28 | All as per description all serial item No. 27.00 here-in-before but in existing PVC conduit |
| 29 | All as per description of serial item No. 27.00 here in before but in & including PVC casing and capping with all the necessary fittings & accessories i.e Tee, elbow, socket etc. |
| 30 | M&L for modular point wiring for one 2 way light point etc controlled by two switches with 1.5 Sqmm multistranded FRLSPVC insulated unsheathed, FRLS, multistranded copper conductor cable 1100 volts grade (red, yellow & blue) in and including medium duty non metallic rigid PVC concealed conduit 20 mm dia including conduit accessories like bends, tees junction boxes etc fixed concealed/recessed in wall or ceiling etc including 1.5 Sqmm single core FRLS PVC (green) insulated unsheathed multi stranded copper conductor 1100 Volts grade as earth continuity wire connected to earth dolly matching with surrouding with modular sunken steel boxes zinc oxide plated of suitable size including modular sheets of suitable module and back plates etc. complete all as specified and directed.Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces. |
| 31 | All as per description all serial item No. 30.00 here-in-before but in existing PVC conduit |
| 32 | All as per description of serial item No. 30.00 here in before but in & including PVC casing and capping with all the necessary fittings & accessories i.e Tee, elbow, socket etc. |
| 33 | M&L for modular point wiring for one socket outlet 5 Amp 3/5 pinfor independent board etc controlled by one switch with 1.5 Sqmm multistranded FRLSPVC insulated unsheathed, FRLS, multistranded copper conductor cable 1100 volts grade (red, yellow & blue) in and including medium duty non metallic rigid PVC concealed conduit 20 mm dia including conduit accessories like bends, tees junction boxes etc fixed concealed/recessed in wall or ceiling etc including 1.5 Sqmm single core FRLS PVC (green) insulated unsheathed multi stranded copper conductor 1100 Volts grade as earth continuity wire connected to earth dolly matching with surrouding with modular sunken steel boxes zinc oxide plated of suitable size including modular sheets of suitable module and back plates etc. complete all as specified and directed.Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces. |
| 34 | All as per description all serial item No. 33.00 here-in-before but in existing PVC conduit |
| 35 | All as per description of serial item No. 33.00 here in before but in & including PVC casing and capping with all the necessary fittings & accessories i.e Tee, elbow, socket etc. |
| 36 | All as per description of serial item No. 33.00 here in before but for one 3/5 pin 5 amps socket outlet on same board with other switches. |
| 37 | All as per description of serial item No. 33.00 here in before but for one 3/5 pin 5 amps socket outlet on same board with other switches in existing conduit. |
| 38 | All as per description of serial item No. 33.00 here in before but for one 3/5 pin 5 amps socket outlet on same board in & including PVC casing & capping with all the necessary fittings & accessories i.e tee, elbow, socket etc. |
| 39 | M&L for modular point wiring but for one 15 Amp independant socket outlet using 4 SqmmPVC insulated unsheathed, FRLS, multistranded copper conductor cable 1100 volts grade (red, yellow & blue) in and including medium duty non metallic rigid PVC concealed conduit 20 mm dia including conduit accessories like bends, tees junction boxes etc fixed concealed/recessed in wall or ceiling etc including 1.5 Sqmm single core FRLS PVC (green) insulated unsheathed multi stranded copper conductor 1100 Volts grade as earth continuity wire connected to earth dolly matching with surrouding with modular sunken steel boxes zinc oxide plated of suitable size including modular sheets of suitable module and back plates etc. complete all as specified and directed.Note: The unit rate quoted include the cost of cutting chases in surfaces for conduits and fixing of sunken boxes and making good the distrubed surfaces to match the existing surfaces. |
| 40 | All as per description all serial item No. 39.00 here-in-before but in existing PVC conduit |
| 41 | All as per description of serial item No. 39.00 here in before but in & including PVC casing and capping with all necessary fittings & accessories i.e Tee, elbow, socket etc. |
| 42 | S&F in repairs modular switch, one module,1 way, 10 Amps 240 volts complete all as specified and directed. |
| 43 | S&F in repairs modular switch, one module,1 way, 16 Amps 240 volts complete all as specified and directed. |
| 44 | S&F in repairs modular bell push 6A, 240 volts, 1 Module complete all as specified and directed. |
| 45 | S&F in repairs modular switch, two way,6A, 240 volts, 1 Module complete all as specified and directed. |
| 46 | S&F in repairs modular socket 6A, 240 volts 2 & 3 pin,2 Module complete all as specified and directed. |
| 47 | S&F in repairs modular socket, 6A & 16A, 240 volts, 2 & 3 pin, 2 Module complete all as specified and directed. |
| 48 | S&F in repairs modular step type fan regulator 120W, 240 volts,2 Module,complete all as specified and directed. |
| 49 | S&F in repairs ceiling rose, 3 phase PVC / polycarbonate, isolated body complete all as specified and directed. |
| 50 | S&F in repairslamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete complete all as specified and directed. |
| 51 | S&F in repairs LED Lamp of 9W, Base B22, BEE 3 Star complete all as specified and directed. |
| 52 | S&F in repairs electronic driver for LED bldg security lightafter taking down bldg security light, ISI approved company made as per existing make and size for suitable for LED fittings of cap upto 45 watts any type and make, and refixing the same complete all as specified and directed. |
| 53 | Supply & fix in repairs LED tube light fittings (4 feet long), wall mounted 1x20 watt6500K, Decorative, ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficientwith all accessories and making connection using 2 core, 0.50 Sqmm PVC insulated and overall sheathed flexible copper conductor cable from ceiling rose/PVC connector to light fitting and testing etc complete all as specified and directed. |
| 54 | S&F in repairs LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V, AC, recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. |
| 55 | S&F in repairs Energy efficientLED ceiling light 15W of size 1 feet x 1 feet complete withhigh efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. |
| 56 | S&F in repairs Energy efficientLED ceiling/surface light of 12W to 15W, circular shape complete withhigh efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. |
| 57 | S&F in repairs LED light fitting, mirror type with high out put diffuser, 2 feet,10 watt, 220 volt, AC, decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 58 | S&F in repairs LED Bulk Head luminaries, 10W complete with all accessories and including connector andconnecting up with twin core twisted flexible copper conductor cable with suitable size of 230V, 50 HZ complete all as specified and directed. |
| 59 | S&F in repairs decorative wall light white in colour made up of poly carbonate including 9 watt retrofit LED Lamp complete all as specified and directed. |
| 60 | S&F in repairs building security LED lightluminaire 30 W, IP 66, IK-07, AC 230 volts, made up of pressure di-cast iron housing complete making connectionusing PVC insulated and sheathed3 core multi stranded copper conductorcable of size 0.50 Sqmm from ceiling rose including MS bracket made of 25/32mm GI pipe bent to shape, fixed to wall with clamps and nurs & bolts for mounting fittings complete all as specified and directed. |
| 61 | Note for srl item No 51 to 60 above:- 1. Driver shall be potted anti-vibration types. 2. LM-79 and LM-80 test report with 1 Lakh burning hours LED life from NABL lab shall be provided. 3. CRI (Colour Rendering Index) of fixture shall be > 70.4. CCT (Colour Co-related Temperature of fixture shall be 5700K + 300 K. 5. System Lumen Efficacy shall be > 100 Lm/W.6. 10 KV separate Surge Protection shall be provided as a part of fitting. 7. Lenses shall be Modular Type. 8. PCB used shall be MC PCB type. 9. CA No. shall be written on each fitting before installation. 10. The name of manufacturer to be embossed on the fitting. |
| 62 | Note for srl item No 51 to 60 above (Contd...):-11. The fittings shall have arrangement so that maintenance required, if any can be carried out from Top cover.12. The defect liability period of LED lights shall be 05 years from the certified date of completion & the contractor shall replace/repair the defective fitting within 07 days after handing over for replacement. 13. A guarantee of 05 years shall be provided by contractor supported by OEM covering all parts of luminaire. Contractor shall deposit security on this account @ 5% of work done against these items otherwise the same shall be deducted from the dues payable to him in RAR/Final Bill. |
| 63 | S&F in repairs Bell, Ding Dong AC, 230 volts, single pole complete all as specified & directed. |
| 64 | S&F in repairs sheet metal enclouser,single pole and neutral 240 volt, 20 to 32 Amps with two pin and earth plug and socket plug top complete with single pole MCB complete all as specified and directed. |
| 65 | S&F in repairs sheet metal enclousre for DBs double door single pole and neutral with 200 amps rated bus bar 8 way, 240 volts complete all as specified and directed. |
| 66 | S&F in repairs sheet metal enclousre for DBs double door single pole and neutral with 200 amps rated bus bar of 12 way, 240 volts complete all as specified and directed. |
| 67 | S&F in repairs MCCB, 4 pole,63 Amps, 240 volts, 50 KA rupturing capacity complete all as specified and directed. |
| 68 | S&F in repairs MCCB, 4 pole,100 Amps, 240 volts, 50 KA rupturing capacity complete all as specified and directed. |
| 69 | S&F in repairs MCB single pole and neutral 63 Amps, 240 volts, B-series complete all as specified and directed. |
| 70 | S&F in repairs MCB single pole and neutral, 40 Amps, 240 volts, B-series complete all as specified and directed. |
| 71 | S&F in repairs MCB single pole 16 to 32 Amps, 240 volts, B-series complete all as specified and directed. |
| 72 | M&L for earthing complete with galvanised steel earth plate electrode, 600mmx600mmx6mm size,buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electric plate No 3connected to earth test point/MCB DBs all as specified and indicated complete with funnel, charcoal, dust, salt etc and GI protection pipe, medium grade 15mm bore and GI watering pipe 20mm bore light grade, precast RCC cover 40mm thick, M-15 (nomial mix), reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover, PCC pit M-15 (Nominal mix), excavation and earth work in any type of soil and connected, complete all as specified & directed. Note:- 1. Earth lead & protection pipes upto & including 7.50 metre length is deemed to be included in the unit rate quoted by the contractor.2. Earth filling shall be free from stones, boulders, aggregate, gravels etc |
| 73 | S&F in repair sub main wiring with two runs of 6.0 sqmm copper conductor cable multistranded, FRLS PVC sheathed two run (as phase and neutral) and one run 6.0Sqmm multistrand PVC sheathed copper conductor cable for earth continuity drawn in existing surface /recessed steel/ PVC conduit complete all as specified and directed. |
| 74 | S&Fsub main wiring with two runs of 6.0 sqmm copper conductor cable multistrand, FRLS PVC sheathed two run (as phase and neutral) and run 6.0Sqmm multistrand PVC sheathed copper conductor cable for earth continuity drawn in & including PVC rigid non metalic concealed conduit 20mm dia with fittings & accessories including cutting chases in walls by using electric cutter andmaking good the disturbed surface by providing cement plaster & white wash/colour wash to match complete all as specified and directed.Note ;- The cost of cutting chases in walls by using electric cutter andmaking good the disturbed surface by providing cement plaster & white wash/colour wash to match the existing surface/ finishes shall be deemed included in unit quoted rate |
| 75 | S&F in repairs modular cover plate with back plate 2 modules on sunken box for fixing of switches and sockets complete all as specified and directed. |
| 76 | S&F in repairs modular cover plate with back plate 3 modules on sunken box for fixing of switches and sockets complete all as specified and directed. |
| 77 | S&F in repairs modular cover plate with back plate 4 modules on sunken box for fixing of switches and sockets complete all as specified and directed. |
| 78 | S&F in repairs modular cover plate with back plate 6 modules on sunken box for fixing of switches and sockets complete all as specified and directed. |
| 79 | S&F in repairs modular cover plate with back plate 8 modules on sunken box for fixing of switches and sockets complete all as specified and directed. |
| 80 | S&F in repairs bakelite sheet of size 5\"x5\" including cutting to required shape for fixing of existing switches and sockets complete all as specified and directed. |
| 81 | S&F in repairs bakelite sheet of size 8\"x5\" including cutting to required shape for fixing of existing switches and sockets complete all as specified and directed. |
| 82 | S&F in repairs bakelite sheet of size 10\"x12\" including cutting to required shape for fixing of existing switches and sockets complete all as specified and directed. |
| 83 | S&F in repair bakelite sheet of size 8\"x10\" including cutting to required shape for fixing of existing switches and sockets complete all as specified and directed. |
| 84 | S&F as in repairs sunken steel box, zinc oxide plated of size 4\"\"x4\"\" including cutting the wall to required shape and making good the disturbed surfaces to match existing one complete all as specified and directed. |
| 85 | S&F as in repairs sunken steel box, zinc oxide plated of size 7\"\"x4\"\" including cutting the wall to required shape and making good the disturbed surfaces to match existing one complete all as specified and directed. |
| 86 | S&F as in repairs sunken steel box, zinc oxide plated of size 9\"\"x11\"\" including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed. |
| 87 | S&F as in repairs sunken steel box, zinc oxide plated of size 7\"\"x9\"\" including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed. |
| 88 | S&F as in repairs prewired VTPN Distribution board of size not less than 750mmx470mm with provision for & including MCCB as incommer 63 Amp, 04 pole IP 54, 04way (for incomming MCCB & outgoing MCBs), with copper busbar for each phase, withNeutral bar,Earth bar and cable ties for cable managemet, fully insulated busbar & shrouded Neutral bars, with 63 Amps MCCB, 50 KA, 4 pole, as incomer and SP MCB\"s of capacity 6-32amps as outgoing complete all as specified and as directed. Note: Cost of MCCBs and MCBs, cutting chases, grouting in wall shall be deemed included in unit quoted rate of this item. |
| 89 | Supply, laying, jointing & and testing of XLPE insulated screened, PVC bedded galvanized steel strip or wirearmoured electric power cables (heavy duty) with aluminium conductor cross sectional area 50 sqmm 3.5 core, 1100 volts grade complete all as specified and directed.Notes:- Excavation & earth work, sand cushioning, brick protection shall be measured and paid separately. |
| 90 | All as per description of serial item No. 87.00 here in before but cross sectional area 35 sqmm 3.5 core |
| 91 | All as per description of serial item No. 87.00 here in before but cross sectional area 25 sqmm 4 core |
| 92 | All as per description of serial item No. 87.00 here in before but cross sectional area 16 sqmm 4 core |
| 93 | Supply, laying ,jointing & and testing1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of 16 sqmm 2 core. |
| 94 | All as per description of serial item No. 91.00 here in before but cross sectional area 10 sqmm 2 core |
| 95 | All as per description of serial item No. 91.00 here in before but cross sectional area 4 sqmm 2 core |
| 96 | Exacavation in trenches in hard/dense soil not exceeding 1.5 m wide and not exceeding 1.5m deep and getting out for laying of underground cables complete all as specified and directed. |
| 97 | Returning filling in hard / dense soil including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed. |
| 98 | Removing excavated material (soil) to a distance n.exc. 50 m and depositing where directed at a level n.exc. 1.5 m above the starting point complete all as specified and directed. |
| 99 | M&L for dry clean fine river sand as in sand cushioningto underground cable including punning down ofsand layer complete all as specified and directed. Note :- Punnedthickness shall only be measured and paid. |
| 100 | Supply & laying sub class B bricks old size, in trenches, laid dry, flat, over sand cushioning for protection of cable, with length of brick equal to width of protectioncomplete all as specified and directed.Note:- Sand cushioning shall be measured and paid for separately. |
| 101 | S&F 40 mm bore galvanised steel tubing, light grade, with all fittings, for protection of cable, laid in trenches/road crossing/floor or fixed to pole/wall with and including 02 Nos. MS clamp of size 25x4 mm, nuts, bolts and washers complete all as specified and directed. |
| 102 | M&L for repair to unservicable defective electric meter 10 to 20 Amps single phase through an company authorised service provider by replacing defective PCB Board, indicator display control push wiring and sealing the meter & terminal connections including taking out defective meter from existing location & refixing in same position after repair complete all as specified and directed. Notes:- (i) Cost of PCB Board, indicator display control push wiring and sealing shall be deamed included in unit rate. (ii) Contractor shall provide the written warranty of repaired meter for one year. |