supply installation testing and commissioning Of D.G. Set And Allied Work At Falakata Stadium.- 1 Supply & Installation of 125 KVA DG SetSupply, Testing & Comissioning of 125KVA Silent Diesel Generator Set, water cooled, developing of CPCB-IV+ ENGINE with 12/24 volt self starter arrangement including rated DC 12/24V battery, mechanical governor with Gen Set controller, natural aspiration having dry tye air filter couled with Alternator capable of developing 125 KVA at 415V 50 c/s 50Hz at 1500 rpm, 3-phase 4-wire conforming to BS EN 60034-1/IS:4722 and will be suitable for tropical condition brushless type, screen protected, revolving field self excited self regulator through AVR, IP protection: 23, permissible overload of 10% for one hour in 12 hrs of operation. Class-H insulation, voltage regulation+1% DG mounted on base with AVM pad complete all as direted adn housed in accoustic enclosure required for Emergency Power Supply along with suitable Control panel, fuel tank, base frame, battery with leads and canopy with AMF Panel. 2 InstallationEarth excavation of foundation trenches or drains, in all sorts of soil ( including mixed soil but excluding laterite or sandstone ) including removing, spreading or stacking the spoils with in a lead of 75 m as directed . The item includes necessary trimming the sides of trenches , levelling dressing and ramming the bottom, bailling out water as required complete. (a) Depth of excavation not exceeding 1500 mm. 3 Single brick flat soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with local sand. 4 Ordinary cement concreat (mix 1:2:4) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement , if any ,in ground floor as per relevent IS codes.(a) River bazree. 5 Brick work with 1st class bricks in cement mortar (1:6)ln foundationand plinth 6 Filling in foundation or plinth by fine sand in layers not exceeding 150 mm as directed and consolidating the same by thoroughsaturation with water, ramming complete including the cost of supply of sand. (payment to be made on measurement of finished quantity) 7 Controlled Cement concrete with well graded stone chips (20 mm graded nominal size) excluding shuttering and reinforcement with complete design of concrete as per IS : 456 and relevant special publications, submission of job mix formula after preliminary mix design after testing of concrete cubes as per direction of Engineerincharge. Consumption of cement will not be less than 300 Kg ofcement with Super plasticiser per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula. In ground floor and foundation. [using concrete mixture] (a) M 20 Grade (Pakur Variety) 8 Plaster ( to wall, floor ,ceiling etc ) with sand and cement morter including rounding off or chamfering corners as directed and raking out joints including throating , noising drip course, scaffolding / staging where neccy. (ground floor ). [ Excluding cost of chipping over concreat surface) .(a)with 1:4 cement morter 15mm thick plaster. 9 Neat cement punning about 1.5 mm thick in wall ,dado,window,sills,floor,drain etc. 10 M.S. Structural works in columns, beams etc. With simple rolled structural members (e.g. Joists, angle, channel sections conforming to IS: 226, IS: 808 & SP (6)-1964 connected to one another with bracket, gussets, cleats as epr design, direction of Engineer-in-charge complete including cutting to requisite shape and length, fabrication with necessary bolting, metal arc welding conforming to IS: 816-1956 & IS: 1995 using electrodes of approved make and brand fonforming to IS: 814-1957, haulage, hoisting and erection all complete. The rate includes the cost of rolled steel section, consumables such as electrodes, gas and hire charge of all tools and plants and labour required for the work including all incidental charges such as electricity charges, labour insurance charges etc.For Structural Works in Roof Trusses etcusing joists, channels and angles of specified section weighing less than 22.5 kg/m. 11 Galvanised corrugated iron sheet work (excluding the supporting frame work) fitted and fixed with 10 mm dia J or L hook-bolts, limpet and bitumen washers and putty complete with 150 mm end lap and one corrugation minimum side lap (Payment to be made on area of finished work) (GCI sheet to be supplied by contractor).(i) In Roof:(a) With 0.63 mm thick sheet. 12 Supply and fixing 100mm dia M.S pipe to extend the exhaust pipe line including welding,bend,reducers and all accessories as required at site or as per E-I-C. 13 Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the Ground (for Morrum soil) 14 Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. 15 Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe. 16 Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl.earthing attachment and painting as required – (As per Drawing no. 470 of PWD SpecificationBook – May 1991)200A Capacity 415 Volt 4 bar AL busbar of bars size50mmX5mmX1mtr-1 No. 17 Supplying and fixing 415V, 200A TPN SFU with sheetsteel enclosure on flat iron/angle iron frame on wallwith nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(L&T) 18 Supplying & Fixing of 40 mm GI pipe (ISI-M) 19 Supply and filling of diesel oilfor trial run of the set. 20 Installation of the Generator above the foundation as required . 21 Supplying and fixing 415V,200A FP Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc. 22 SITC of Cable 1.1 kV grade 3.5Cx95 sq.mm, Aluminium conductor, XLPE insulated, PVC sheathed, armoured cable as per IS 7098 (Part-1) - 1988 (to latest amendment) 23 1.1 kV grade 3.5Cx50 sq.mm, Aluminium conductor, XLPE insulated, PVC sheathed, armoured cable as per IS 7098 (Part-1) - 1988 (to latest amendment). 24 4core 10 sqmm 25 Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed 26 Laying of one No. cable above 35 sqmm and upto 185 sqmm inunderground trench 460mm wide x 760mm average depth, withbrick protection on the top of the cable with 8 (eight) Nos. bricksper Mtr. including filling the space between the bricks and cableand also the trenchwith shifted soil, leveling up and restoringsurface duly rammed 27 1.1 kV grade 3Cx2.5 sq.mm, stranded copper conductor, PVC insulated cable as per IS 694 - 1990 (to latest amendment). 28 1.1 kV grade 3Cx6sq.mm, stranded copper conductor, PVC insulated cable as per IS 694 - 1990 (to latest amendment). 29 Fixing of Cable along the lenth of O.H. pole incl. S & F MS poleclamps fabricated from 25 mm x 6 mm MS flat incl. painting 30 Supplying and fixing compression type gland complete with brassgland, brass ring & rubber ring for dust & moisture-proof entry ofXLPE/PVC armoured cables as below :i) 3.5 core X 95 sq.mm. 31 ii) 3.5 core X 50 sq.mm. 32 4core 10 sqmm 33 Finishing the end of following XLPE/PVC armoured cables bycrimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials :i) 3.5 core X 95 sq.mm. 34 ii) 3.5 core X 50 sq.mm. 35 4core 10 sqmm 36 Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes 2.5 sqmm 37 Supplying & fixing medium gauge 50 mm dia GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required 38 (a) Supply of Hot dip Galvanized mast of mean height of 12.5 m suitable for mounting LED Flood Light fittings symmetrically. Mast will include heard- frame, lantern carriage with required Luminaire arms suitable for mounting luminaires symmetrically , winch with wire ropes ( 2 w rope system), lightning spike bolted on head-frame, Junction box, trailing cable 5c x 2.5 sq mm cable-1 nos., carriage supports foundation accesories , required no. of foundation bolts + 50% TP +1 Ap. No. of Section 2; Base and Top Outer dia. in OAF is 360mm and 100mm respectively; Thickness of sections 3/3 mm; Base Plate dia. 520x25mm and PCD 45 mm.The slip- stress fit type of joint is provided for sections; Raising/lower speed 3m/min. The lubricant is permanent oil bath of SAE 90/140 type. SS wire rope is AISI 316, 7/19 const. Dia. of rope 5mm and breaking load capacity: 2350kg/rope. The tailing cable is ERP/PCP Sheathed Multi core flexible copper. The power tool is 440V, 50HZ, 1HP/1.5HO Reversible. The mast should comply IS: 875 (Part-III, 1987) for wind loading;SEN 10025 / IS: 2062 for grades of MS plates. BS ISO 1461/IS 4759 for galvanizing; IS: 800 (1984, Rev 2) for Code ofpractice for general construction of steel; TR No. 7 (2003) of ILE, UK for specification of Mast & Foundation; SABS: 0225 (1991) for Mast natural frequency calculation; IS: 3459/2266 for stainless steel wire rope; IS: 9968 (Part-I) for trailing cable. 3.9 IS: 325 for motor. IS: 5135 for welding; IS:1367 for foundation accessories. 39 b) Supply, installation, testing & commissioning of Outdoor type dust and vermin proof powder painted Sub Panel board having fixed with front side double door with railway type locking arrangement suitable 415V 3 phase, 4 wire 50 Hz AC supply made out of 2 mm thick MS sheet so asto accommodate the following mountings complete with bus bar of 315 Amp capacity & channel base at the bottom connection & interconnection by copper wire & strip along with necessary nuts & bolts complete as reqd. (Make-L&T/Siemens/ABB make).a) 32A 415 Volt 4P MCB-1 nob)63 Capacity 415 Volt 4 bar AL busbar of bars size 50mmX10mmX1mtr c) 6-20A 415 Volt TP MCB-2nod)6-20A 250 Volt DP MCB -2 nose)ANALOG TIMER - 1nof)32 A 4 POLE CONTRACTOR AND 3 A SP MCB FORCOIL SUPPLY-1 nog)AUTO MANUAL SELECTOR SWITCH-1 no j) 0-500 digital Voltmer-1 nok) LED Indicating Lamp -3 nol)Caution board-1 no 40 (c) Supply of BIS Certified make in India 200W LED Floodlight made of pressure die cast aluminium housing and heat resistant toughened glass. Rated Supply voltage: 240V, 50Hz AC, System Luminous Efficacy> 110 Lumen/Watt, CRI> 70, CCT: 5700K, PF >0.95, THD< 10%. The Luminaire must have IP66 and IK07 protection. The screws and Connections should be corrosion resistant and must withstood an applied torque of 8Nm for five times. The Luminaire should have Provision for earthing with Earth contact Resistance < 0.5 Ohm and Leakage Current <1 mA. The Insulation Resistance Shall be > 2MΩ on application of 500V DC. The LED Driver is BIS Certified Potted Driver of >85% efficiency with 5KV Internal and 10KV External Surge Protection and Protection from Over Voltage, Short Circuit, Open Circuit and Reverse Polarity. The LED Chip is LM80 Certified OSRAM/ LUMILEDs make LED Chip with free all photobiological hazards and a burning hours of L70@50000 Hours. Conforming Standards: IS 10322(Pt.5/Sec.5)-2013. IS 16103 (Pt.1& Pt.2):2012, IS 16104:2012, IS 16105:2012, IS 16107(Pt.2/Sec. 1):2012, IEC 60598, IEC 61347-2-13, IEC 62384 & 62031, LM79. 41 Erection and commissioning of the High Mast with help of suitable equipments by contractors own arrangement and Supply, erection & design and casting of suitable shallow foundation with 1:2:4 concrete for the High Mast considering the safe soil bearing capacity at site as 10T/m2 at 2 metre depth. 42 Supply & erection of Feeder Pillar Box Front And Back Both Side Openable type dust and vermin proff and gasket shall be provided as per IP 66 degree of protection powder coated painted including provision for service connection meter and200A MCCB with comparmentalise arrangement for sub panel board suttable for 415 Volt, 3 phase 4 wire 50 Hz A.C Supply made out of 2mm chanel base at the bottom connection & interconnection with suitable size stranded coper wire & strip along with necessary nuts & bolts making the same as per direction of EIC.A) 200A 4P 415V MCCB 36 kA - 2 nos b) 200A 4P 415 V Change Over-1 no.C) 200A FP Copper bus ber - 1 set, D) 63 A 4P MCCB - 4 Nos,E) LED Indicator Lamp Including Sliding fuse - 24 Nos,F)Voltmeter With selector switch - 1 Set,G)Ammeter with selector switch - 1 NoH)63/5A CT -03 Nos, I)M P Caution Board - 1 NoJ)Timer Along type GIC Make - 1 setK)Three phase Contactor Circute (ML4) - 1 No L)6A SPMCB for Contector power supply - 1 No, M) Auto Manual Switch - 1 No 43 Sign BoardSupply & lnstallation of 6 depth box type M,S. structure duly fabricated &.welded by 40 mm x 40 mm M.S. square pipe 3 mm thick lSI mark frame with back side & four sides covered by 24SWG MS sheet including Aluminium channel and fixing arrangement without ACP sheet includiug painting,. slze :20 x 6.5 to be made such a manner that it can be opened towards up direction for taking maintenance. 44 S&F 4mm thick white ACP sheet on MS structure. Size 20 ftX 6.5 ft 45 Supply & fixing of special type imported acrylic letter suitable height as per site requirment fixed on ACP sheet.The letter front( English/Bengali bold) letter colour- Blue 46 Supply & fixing ofLED inside the acrylic letters.the specification of lED is given below; a) LED white samsung (Korea) module. ( 3 nos. LED in a module)b) type:double line fixed.c) Life:70,000 burning hours.d) Intensity- same & smooth through out no brighter or light or dark patches.e) Visibility: 50 mtr. at least for normal eye.f) Power supply: required amp (mean well LRS·< >-12)g) Ambient air 0-50 c 100% relative humidity.h) Power consumpdon: 1.08 watt per module. 47 S & F water proof 350 watt power supply system [P65. 50/60 Hz frequency 108 to 305 VAC power supply, >.095 power factor for LED lamp, (Make: Meanwell /Groen) 48 S&F 50mm X 50mm X 6mm MS angle on wall including painting for fixing of sign board. 49 Distribution wiring in 1.1 KV single core stranded FRPVC insulated & unsheathed copper wire (Brandapproved by EIC) in 20mm size PVC rigid conduit FR(Precision make) incl. necy. fittings as required. 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC