| 1 | Supply, installation, testing and commissioning of 58.5 KVA, suitable BHP, 47 KW, 81Amps, 4 Wires, 415 Volts, 3 phase, 50 Hz, 1500 rpm, Liquid Cooled Silent Type Diesel Engine Driven Generasting Set( as per latest CPCB IV+ standards) with standard accessories coupled to Alternator mounted on a Channel Iron Base Frame complete with AVM pads and 12/24V DC Electrical Starting System with an in built Fuel Tank of minimum 120 Ltrs capacity, including AMF panel for the above DG set inside/outside the acoustic enclosure including transportation, loading and unloading of the machine at the site etc as required. |
| 2 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 3 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 4 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 5 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 6 | Providing and fixing 25 mm X 5 mm GI strip on surface or in recess for connections etc. as required. |
| 7 | Supplying and laying 25 mm X 5 mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 8 | Supplying of PVC insulated, PVC sheathed / XLPE aluminium conductor armoured under groundpower cable of 1.1 KV gradeconforming to IS 1554 part-I/7098(part-I) 1998 with up to date amendments of the following sizes. (a) 3 1/2 x 50sq mm |
| 9 | Supplying of PVC insulated, PVC sheathed / XLPE Copper conductor armoured under groundpower cable of 1.1 KV gradeconforming to IS 1554 part-I/7098(part-I) 1998 with up to date amendments of the following sizes. (a) 6 x 2.5sq mm |
| 10 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(a) 3 1/2 x 50sq mm (35mm) |
| 11 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required(OD-63 mm & ID-51 mm nominal) |
| 12 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as requiredAbove 35 sq. mm and upto 95 sq. mm |
| 13 | Up to 35 sq. mm |
| 14 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. above 35sqmm and upto 95 sqmm |
| 15 | Up to 35 sq. mm |
| 16 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge.(a) All kinds of soil |
| 17 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 18 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : (a) 1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 19 | (b) 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 20 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 21 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level (for DG Set Foundation) |
| 22 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 23 | Centering and shuttering including strutting, propping etc. and removal of form work for :Foundations, footings, bases for columns |
| 24 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 25 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin- charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 26 | CEMENT PLASTER (IN FINE SAND)12 mm cement plaster of mix : 1:6 (1 cement: 6 fine sand) |
| 27 | Applying priming coats withprimer of approved brand and manufacture, having low VOC(volatile organic compound) content :With water thinnable cement primer on wall surface having VOC less tahn 50 grams/litre |
| 28 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 29 | Supply & installation of Safety Items with First Aid Kit, short Treatment Chart, DCP Type Fire Extinguisher of 2Kgs., Rubber mat , Fire Bucket of 2nos. With Stand etc as reqd |
| 30 | Supplying, Installation, Testing, Commissioning of On Load Changeover Switch of 4 pole 160 A 415 V rating with sheet steel enclosure and other required accesories on wall surface or existing panel board including making connections, terminating incoming and out going cables etc as required. |
| 31 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections etc as required |
| 32 | 125A,36KA FPMCCB |
| 33 | Providing and fixing Sheet Steel Enclosure Box including accessories suitable for 125A,36KA FPMCCB with IP 30 Protection at site of work etc., as required |