Tender For PROVIDING AND INSTALLATION OF FIRE FIGHTING SYSTEM IN OLD AGE HOME IN SECTOR - 32 , URBAN ESTATE KARNAL including three years mtc/defect liability period free of costA/C-- 1 [22.181]Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. [Through Rate] 2 [4.12.1]Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead up to 50 m and lift up to 1.5 m, as directed by Engineer-in-charge. 1. All kinds of soil [Through Rate] 3 [4.31.1]Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. 1. All kinds of soil [Through Rate] 4 [11.4.2]10 mm thick cement plaster 2. 1:3 (1 cement: 3 fine sand) [Through Rate] 5 [11.5.2]12 mm cement plaster of mix : 2. 1:3 (1 cement: 3 fine sand) [Through Rate] 6 [11.6.2]15 mm cement plaster on the rough side of single or half brick wall of mix : 2. 1:6 (1 cement: 6 fine sand) [Through Rate] 7 [13.21.1]Supply and fixing Windows frames (Chowkhats) including mullions consisting frame fabricated from sheet roll formed out of 1.2mm thick galvanized sheet as per IS:277 (Base steel as per IS 513) with zinc of 120 gm/sqm and Powder coated with pure Polyester powder up to 50 microns (as per approved colour), 3 Nos. 100mm butt - hinges 2mm thick, 6 Nos. 1.2mm thick CRCA electroplated stiffner, 6 Nos. M.S hold fast with split and tail welded to stiffner plate 200mm long, receiver for aldrop, weld less corner assembly with brackets and screws, M.S tie rod 50mm x 25mm to be fixed at bottom finished with powder coated total thickness of coating 0.6mm of approved shade, fixed in position including the cost of cement concrete for 1:2:4 for fixing lugs complete in all respects as per drawing, design, specification and entire satisfaction of Engineer-in-charge. 1. Door Frame of size 80mm x 50mm with 37mm wide single rebate for 35mm door shutter [Through Rate] 8 [11.58]Providing and applying two coats white cement based putty of approved brand and manufacturer, over plastered surface and grinding the surface smooth with sand paper to get en even and smooth finish including cost and carriage of all material , labour charges, scaffolding, sundries etc. complete [Through Rate] 9 [11.64.1]Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : 1. New work (two or more coats) over and including water thinnable priming coat with cement primer [Through Rate] 10 [11.76]Preparation of ply wood surface for painting including sand papering the surface and applying filling with approved quality filler consisting of white lead, linseed oil, varnish and chalk mitti including finishing the surface to required finish complete. [Through Rate] 11 [11.78]Painting two coats excluding priming coat with synthetic enamel paint in all shades on new wood work or metallic or plastered or concrete surfaces to give an even shade. [Through Rate] 12 [11.83.1]Painting over the wooden surface with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : 1. Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture [Through Rate] 13 [12.37.1]Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 1. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws [Through Rate] 14 [23.4.1.2]COPPER WIRING WITH MODULAR SWITCHES IN PVC CONDUIT (SURFACE/RECESS) 1.2. Wiring for Light/Fan/call bell point with modular type switch/socket and GI box, Modular type face plate etcin 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick PVC conduit pipe. Group B [Through Rate] 15 [23.4.3.2]COPPER WIRING WITH MODULAR SWITCHES IN PVC CONDUIT (SURFACE/RECESS) 3.2. Wiring for Light/Fan/call bell point in 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick PVC conduit pipe, without separate control switch Group B [Through Rate] 16 [23.4.4.2]COPPER WIRING WITH MODULAR SWITCHES IN PVC CONDUIT (SURFACE/RECESS) 4.2. Wiring in PVCconduit system for 3-pin 5amp. Plug point by using 2 no 1.5 sqmm FRLS copper wire and 1 no 1.5 Sqmm FRLS copper wire , including providing 1 no 5/6 Amp 3/5 pin Modular type socket and 1 no 5/6 Amp Modular type switch required GI Box ,modular face plate etc complete as required Group B [Through Rate] 17 [12.134.4]Providing and fixing factory made uPVC white colour sliding glazed window up to 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thickgalvanized mild steel section made from roll forming process of required length (shape and size according to uPVC profile),appropriate dimension of uPVC extruded glazing beads and uPVCextrudedinterlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame and sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware`s and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rodof required size and of approved quality, all complete as per approved drawing and direction of Engineer-in-Charge.(Single / double glass panes, wire mesh and silicon sealant shall be paid separately). Variation in profile dimension in higher side shall be accepted but no extra payment on this account shall be made. 4. Three track three panels sliding window with fly proof S.S wire mesh (Two Nos. glazed & one no. wire mesh panels) made of (big series) frame 116 x 45 mm & sash 46 x 62 mm both having wall thickness of 2.3 ± 0.2 mm and single glazing bead / double glazing beadof appropriate dimension. (Area of window above 1.75 sqm). [Through Rate] 18 [23.7.6.2]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia. [Through Rate] 19 [23.8.4]FITTING AND ACCESSORIES 4. Supply and erection of 10.5 cm dia M.S.Fan box including 8 mm dia 30 cm long M.S. Road made into suitable suspension hook and erected in R.C.C. slab for the erection of fan complete with all labour and material required to complete the job. [Through Rate] 20 [7.22.2]Brick work with common burnt clay non-modular bricks of class designation 10.5 in superstructure above plinth level up to floor IV level in all shapes and sizes in : 2. Cement mortar 1:6 (1 cement : 6 coarse sand) [Through Rate] 21 [22.91.6]Providing and fixing G.I. pipes complete with G.I. fittings including trenching up to 0.30m to 1.00m depth and refilling etc.External work 6. 50 mm dia nominal bore [Through Rate] 22 [22.94.6]Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work): 6. 50 mm nominal bore [Through Rate] 23 [22.98.5]Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 5. 50 mm nominal bore [Through Rate] 24 [6.1.2]Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work below plinth level and up to Floor IV level: 2. 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size) [Through Rate] 25 [6.24.1]Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer-in-charge. 1. All works up to plinth level [Through Rate] 26 [6.24.2]Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer-in-charge. 2. All works above plinth level up to floor IV level [Through Rate] 27 [6.29.1]Centering and shuttering including strutting, propping etc. and removal of form work for : 1. Foundations, footings, bases for columns [Through Rate] 28 [6.30.2]Centering and shuttering including strutting, propping etc. and removal of form for 2. Walls (any thickness) including attached pilasters, buttresses, plinth and string courses etc. [Through Rate] 29 [6.30.3]Centering and shuttering including strutting, propping etc. and removal of form for 3. Suspended floors, roofs, landings, balconies and access platform [Through Rate] 30 [20.71.1]Supply, erection, testing of Ceiling fansIS marked (as per IS code 374) with suitable GI pipe complete in all respects complete as per directions of Engineer-in-charge 1. 48 (1200mm) [Through Rate] 31 [20.72]Supplying, errection, testing of Exhaustfan (as per IS code 374) having a capacity of 45 cubic metre per minute complete with suitable G.I sheet ducting in structureconfirming to latest IS specificationscomplete in all respect to satisfaction of Engineer-in-charge. [Through Rate] 32 [6.34.6]Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect above plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding & placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement. 6. Thermo-Mechanically Treated bars of grade Fe-500D or more. [Through Rate] 33 Supplying, installation, testing and commissioning of Terrace Pump f 450 LPM @ 36 mtr Head Pressure not less than 3.5 kg/sqcm at the topmost Hydrant suitable for firefighting and confirming to IS:12469-1988 complete with totally eclosed drip proof squirrel cage indication motor with bronze impeller, pressure gauge, pressure switch complete to operate on 3 phase, 415 volts, 50 Hz. complete including PCC foundation block complete 34 Supplying , Installation , testing and commissioning of Pressure switch of approved make for Hydrant pump , Jockey Pump and Diesel Engine Driven Pump including necessary wiring and cut off valve up to central panel and other materialas described in specification 35 Supply, installation, testing and commissioning of Air cushion tank (air – vessel) 250mm dia x 1200mm high with dished top, made of minimum 6mm thick M.S. pipe/plate complete with 20mm dia. Brass Air Valve (Ball type), 20mm dia. stop valve, pressure gauge with brass stop cock, nipple, tees elbows and all accessories as required. 36 Providing, fixing and testing black mild steel heavy duty (class `C’) pipes (IS:1239 Part-I) and fittings like flanges, tees, elbows, bends junctions, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports. ( FOR HYDRANT SYSTEM and SPRINKLERS SYSTEM) 37 Providing, fixing and testing black mild steel heavy duty (class `C’) pipes (IS:1239 Part-I) and fittings like flanges, tees, elbows, bends junctions, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports. ( FOR HYDRANT SYSTEM and SPRINKLERS SYSTEM) 32 mm dia 38 Providing, fixing and testing black mild steel heavy duty (class `C’) pipes (IS:1239 Part-I) and fittings like flanges, tees, elbows, bends junctions, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports. ( FOR HYDRANT SYSTEM and SPRINKLERS SYSTEM) 40 mm dia 39 Providing, fixing and testing black mild steel heavy duty (class `C’) pipes (IS:1239 Part-I) and fittings like flanges, tees, elbows, bends junctions, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports. ( FOR HYDRANT SYSTEM and SPRINKLERS SYSTEM) 50 mm dia 40 Providing, fixing and testing black mild steel heavy duty (class `C’) pipes (IS:1239 Part-I) and fittings like flanges, tees, elbows, bends junctions, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports. ( FOR HYDRANT SYSTEM and SPRINKLERS SYSTEM) 65 mm dia 41 Providing, fixing and testing black mild steel heavy duty (class `C’) pipes (IS:1239 Part-I) and fittings like flanges, tees, elbows, bends junctions, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports. ( FOR HYDRANT SYSTEM and SPRINKLERS SYSTEM) 80 mm dia 42 Providing, fixing and testing black mild steel heavy duty (class `C’) pipes (IS:1239 Part-I) and fittings like flanges, tees, elbows, bends junctions, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports. ( FOR HYDRANT SYSTEM and SPRINKLERS SYSTEM) 100 mm dia 43 Providing, fixing, testing and commissioning of 100 mm dia. flanged end basket of cast iron Y-strainer made from MS body with bottom and top removable flanges with nuts, bolts etc. having filtration area at least 6 times the cross-sectional area of the pipe complete in all respect to the entire satisfaction of Engineer-in-Charge. 44 Providing, fixing, testing and commissioning of cast iron butterfly valve complete confirming to IS :13095 with flanges, nuts and bolts and washers complete for the following sizes. (PN 1.6 rating) complete in all respect to the entire satisfaction of Engineer-in-Charge. 100 mm dia 45 Providing and fixing cast iron wafer type horizontal/ vertical non return valve complete with flanges tested to 16 Kg. /m2 complete in all respect. 100 mm dia 46 Providing, fixing, Installation and testing of stainless steel pressuregauge with isolation cock suitable for a calibration of 0-15 Kg/ Sqm complete in all respect. 47 Providing, fixing, testing and commissioning of cubical type floor mounted fire control panel fabricated from 1.6 mm gauge sheet duly painted with enameled finish of approved shade and comprise of the following One Isolation fuse Switch Unit One 63 amp fuse switch unit with 63 amps HRS Fuse D.O.L. Starter suitable for main pump motor with overload relay timer , push buttons and auto manual selector switch 48 Supply, laying, testing and commissioning of 1100 Volt grade XLPE aluminum conductor armored cables including the cost of providing required gap between adjacent cables (minimum one cable dia.) and including the cost of providing identification tags saddle etc. complete as per specification, as required. 3 C x 6 Sq. mm Cable 49 Supply, laying, testing and commissioning of 1100 Volt grade XLPE aluminum conductor armored cables including the cost of providing required gap between adjacent cables (minimum one cable dia.) and including the cost of providing identification tags saddle etc. complete as per specification, as required. Control Cable 4 C x 1.5 Sqmm 50 Supplying of all materials and making terminations of 1.1 KV grade copper/aluminium multicore cables of the following sizes.The work includes cable glanding using brass plated single compression glands, sizing the core leads, removing insulation, fixing suitable crimping type copper/aluminum lugs/thimbles by using hydraulic crimping tools with correct size of the dies, shaping the leads and neatly connecting the same to the equipment terminals. 3 C x 6 Sq. mm Cable 51 Body earthing of the various equipment`s / motors / switchgears supplied by the bidder with suitable sizes of earthing strip / wire etc. as per IS:3043 and as required including provisions for connection of earthing to main earthing pits. 52 Excavation for pipe lines in trenches and pits in open areas where disposal of surplus earth is done along the alignment,including trimming and dressing sides, leveling of beds of trenches to correct grades, cutting joint holes, refilling consolidation and dewatering of refill in 15 cm layers and restoration of unmetalledor unpaved surface to its original condition. The rate including the cist of necessary timbering dewatering of rain water, diversion of traffic, night signals, fixing caution boards, watching fencing etc. Pipes , exceeding 80 mm dia. But not exceeding 300 mm dia. 53 Providing pipe protection for underground pipes from corrosion painting pipe with 4 mm thick PYPKOTE primer and covered with PYPKOTE anticorrosive tape (4mm thick) as per specifications. 100 MM DIA. 54 Providing and fixing firehydrant valve with single outlet, gunmetal IS:318-LTB2, grade with100mm N.B. flanged inlet, brass spindle, 63mm female instantaneous outlets, complete with gunmetal blank caps chains, bearings IS:6290 mark and having TAC approved flange O.D. 220mm PCD 180mm eight 19mm dia holes. 55 Providingand fixing 63 mmdia15 mtr. long Reinforced rubberlined hose pipe includinggunmetal male andfemale instantaneous type coupling machine wound with G.I. Wire complete in all respects. Hose shall percaline hose and coupling to IS:903-1975 with ISI certification (two hose per Hydrant) approved by fire authority. 56 Providingand fixingstandard SS 63 mm dia. Branch Pipe with Nozzle of 20 mm nominal Bore outlet as per IS:903 suitable to fit with standard instaneously type 63 mm dia. Coupling ISI market ( IS:903 ) complete in all respect and all other works contingent thereto. 57 Providing and fixing TAC approved fire hose cabinet to house standpost fire hydrant, including all other related accessories fabricated from 16 gauge M.S. sheet of fully welded construction having front door with locking arrangement, partially glazed with 4 mm thickglass. Cabinet shall be painted with post office red colour of size 750 x 600 x 250. 58 Providing and fixing of air release valve of 25 mm dia. And 25 mm dia. Gun metal valve with fittings etc. to be installed at risers complete in all respect. 59 15mm dia, quartzoid bulb type G.M. Chrome plated side wall extended range (4.5mtr to 6.5 mtr) sprinkler head set to operate at 68OC (UL/FM/LPC/TAC listed/Approved) complete with decorating plate(Ressette). 60 Providing and fixing gunmetal fire brigade inlet connection to fire tank consisting of 2 nos. 63mm dia instantaneous type male couplings with 150mm dia flanged outlet complete with bolts, nuts, and rubber insertions as required and as per IS:904-1983 complete in all respect. 61 Installing ISI marked (IS:2878) Fire Extinguisher, Carbon-di-oxide type capacity 4.5 Kgs. flat base including valve, discharge hose of not less than 10mm dia., 1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 filled to a filling rate of not more than 0.667 and wall suspension bracket complete in all respect. 62 Installing ABC (Powder Type) Fire Extinguisher HP Mild Steel Cylinders ISI marked TAC approved fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and confirming bracket and confirming to IS:1349-1993 complete in all respect. 6 Kgs. 63 Supply, installation, fixing, testing and commissioning ofdust tightpush buttonmanualcall boxes to initiate audio visual alarm with a breakable glass cover in the front as per specifications complete as required with small steel hammer attached with steel chain complete in all respect. 64 Supply, installation, fixing, testing and commissioning ofFireAlarmhooterand speaker(6W)having an audible rangeof25 meters withlinematching transformers for PA talk back system as required including chase cutting and making good complete in all respect. a) In custom built cabinet for service areas. 65 Providing and fixing of PVC Conduit 20 mm dia. Soze with all accessories such as bend , tee and giti and screw etc. complete in all respect. 66 Supply , Installation , testing and commissioning of copper wire 2 x 1.5 sqmm wire complete in all respect. 67 Supply of bed matters complete in all respect. Single Bed Mattress (Dunlop / Sleepwell 68 Supply of Cotton Bed Sheet complete in all respect. 69 Supply of Pillow with cover complete in all respect. 70 Supply of Mink Blanket (Single Bed) complete in all respect. 71 Supply of Plastic Bath Tumbler Set complete in all respect. 72 Supply, installation, fixing, testing and commissioning of floor mounted, free standing cubicle type, totally enclosed, fully compartmentalized main fire control panel, Microprocessor based, Networkable, fabricated out of 16 gauge powder coated CRCA sheet confirming to IS 5113 amended to date with built in annunciation to indicate fire and fault, LED lamps for visual indications, audio alarm unit, push buttons for manual acknowledge, test, reset, 2X12V 24AH capacity sealed maintenance free batteries with enclosure, mimic panel complete with power supply unit for 24V D.C. from 230v A.C. and backed up by a battery and battery charger etc. complete as per detailed specifications. The main control panel should also have 6 nos. NO and NC contacts for interlocking. 6 zone main fire control panel. (For Faculty Residential Block) 73 Providing and fixing 100 LPH Water Coolerwith inbuilt RO System (60 ltr PH),Structure NSF Approved Frame SS 304 steel, Pre Filter (Ist stage):-10 Micron Sediment—20`,Carbon Filter-IIIRD stage:-GAC NSF with 20” Housing Kemflo (USA)1100 id value,Booster Pump IV th stage :-1.8 LPM1 No—Kemflo (USA) 48 volt, Transformer:-48 Volt 2 No—Delta with 36v additional output, Production Rate 60 LPH, Membrane (Vth Stage)1 No TFC 200 GPD Inline Post carbon 10 “ (VI th stage):-2 % Silver Impregnated Carbon(Kemflo / shurflo) - USA, Anti Scalant Dosing (VII th stage):-Balls with Sediment Filter USA Autom, ation Circuit CCK, Tubing:-Imported cck /Kemflo, Low Pressure Switch:-cck (USA),Float with micro switch:-cck (USA),Inlet Water assembly:-3 way with flow control, Fittings and Pipes :-All Push Fit with NRV facility, Solenoid Valve:-24 /36 Volt,, inlet Pressure Range 5/2.5 kg/cm2,Rejection of TDS 90 /95 %,Recovery 25/40 %,Operating Voltage 230 V AC. 74 Supply and laying of Water Geyser 10 Ltr. Capacity as per ISI Marked 75 Supplying and fixing TAC approved first aid hose reel (swinging type) including 36 meter long 20 mm internal dia rubber lined hose reel tubing, 25 mm dia stop valve, shut off nozzle of sufficient length at one end of this hose and leaded tin, bronze rings and adapter to get into the instantaneousfemalecoupling complete with suitable drawn brackets, hub etc as required. The hose reel strictly confirm to IS:884-1985 complete in all respect to the satisfaction of Engineer-in-Charge. 2