Tender For External Electrification Work And Fire Fighting Works For Building No-10 (Plot No-13), Sector-28, Yea. Wc-E M-02 - 11kV Ring mains Unit (OUTDOOR TYPE) 3 Supplying,Installation, Shifting, Testing & Commissioning of11kV CT2T2 outdoor type Ring Mains Unitmade of galvanised iron, 3.0 mm thick CRCA steel sheet enclosed mounted on hot deep Galvanized , ISMC channel, IP 54 Protected & IP23D tested, proper ventilated and thermal class K10, with interlocked arrangement, with proper shade of paint and arcing withstand test of 20 kA for 1 sec. consisting of following as per specification complete as required: 4 3 way Ring main Unit (RMU) FBX- C/12-21/ CT2T2 consisting of 1No 630amp load break switchs and Two no 630 amp tee-off with SF6 circuit brakeras per specification with following : 5 Incoming – 1No. incommer each consisting offollowing 6 Machnical ON/OFF/EARTH indication. 7 Earthing switch 8 Machnical ON/OFF/EARTH indication. 9 Cable testing facility without opening the cable comparthent and without connecting the cable terminations. 10 Set of ON/OFF/EARTH semaphore indicating . 11 Live cable Indicating LEDs energized thru capacitive voltage dividers. 12 Right angle boots (Push on type) 13 Suitable space for termination of 1 No. 3 C x 185 sq.mm XLPE cable. 14 800A CU Main horizontal busbars (Inside Tank)Bus bar. 15 Outgoing Feeder 2 No. each consisting of following for 630kVA Transformer : 16 630 Amps manually operated fixed type SF6 Gas Insulated Circuit Breaker and earthing switch with full making capacity at 50 deg.C ambient and 100% humidity. 17 Earthing switch ,,aux contact for switch, 18 Anti reflex operating handle 19 Set of ON/OFF/EARTH semaphore indicating . 20 230Volt Shunt Trip coil for external tripping 21 Three over current and earth fault IDMT Microprocessor base self poweredRelay with instantaneous high set element. 22 8 Window alarm annunciators panel with hooter, push buttons, aux. Contactors etc as required as per specification. 23 Digital Ameter in built selector switch with 3No. CTS 24 Digital Voltmeter in built selector switch with protection fuse 25 Right angle boots (Push on type) 26 voltage presence indicator,Emergency trip Push Button,Aux contacts for breaker, relay trip coil, shunt trip coil,SELF-POWERED RELAY for 50/51/50N/51N,CURRENT TRANSFORMER FOR PROTECTION BUSHING TERMINALS, FAULT PASSAGE INDICATOR, BATTERY,BATTERY CHARGER,TRIVECTOR METER,PHASE INDICATING LEDs,HERMOSTAT,SPACE PANEL HEATER,AUXILLARY TRANSFORMER,MASTER TRIP RELY,TRIP CKT SUPERVISION RELAY,DOOR LIMIT SWITCH,VOLTAGE MONITORINE RELAY, 8 windoe annauncitor, Hooter etc complete as required 27 11KV H.T. Panel(IOCG ) 28 Supply, Installation, Testing and Commissioning of 11KV Indoor Floor mounted, Metal Clad 11 KV, VCB Panel with alu-zinc / GI enclosure with 4 Nos VCBs, totally enclosed & Fully interlocked horizontal drawout, vertical / horizontal isolation type breaker, dust and vermin proof, free standing, having capacities as mentioned below, single break, trip free mechanism, motorised charged and auto-cum-manual closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C supply with short circuit fault level of 500MVA, complete with self contained, fully interlocked , rack in rack out mechanism, air insulated but encapsulated copper bus bars of 800 A capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiilary switch of 4 NO + 4 NC and equipped with following switch gears and accessories etc. andsuitable for connecting 3 core 300 Sq.mm XLPE 11 KV cable heat shrinkeable end termination (Cable entry from Bottom ) etc as required. 29 Incomer-1 No. VCB Panels each having the following 30 (a) 1 No. 630A, 11KV, 3 phase, 50 Hz Vacuum Circuit Breaker 31 (b)1 No 3 phase 11 KV/110 Volts PT, class 0.5 accuracy and 100 VA burden with 1 No Voltmeter (0-15 KV), Digital type, selector switch for voltmeter and protection fuses for HT metering upto 12 KV on incomer 32 (c)1 set of dual core 3 CTs 200/5+5A of 15 VA burden and accuracy class 0.5 for metering and class 5P10 for protection 33 (d ) 1 No – multi function meter suitable for operation on 110V a.c supply with RS-485 interface for integration to BMS 34 (e ) 1 No - Digital Tri Vector Meter (Trivector meter shall have communication features for monitoring by BMS) 35 (f) 1 No. Microprocessor based numerical relay for Over current and Earth fault protection 36 (g) 1 set of phase indicating lamps with HRC fuses 37 (h) 1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP CIRCUIT HEALTHY 38 (i)6300Amps copper busbar-1 set (common) 39 (j)Test terminal block 40 (k)Trip/Neutral/close switch 41 (l) 1 set of copper bus bar for earthing (common) 42 (m) 1 set of master trip relay & trip circuit healthy supervision relay. 43 (n) Provision for padlocking the incomer VCBs in OFF position. 44 11KV H.T. Panel incomer cum outgoing Panel) as above & as per SLD 45 COMPACT SUBSTATION-1000KVA 46 Supplying, assembling, erecting, connecting, testing and commissioning of 11 KV Compact Secondary Sub Station outdoor type designed for natural cooling having type tested equipment comprising distribution transformers, SF6 insulated compact switchgear having metal enclosed robotically sealed/welded stainless steel tank , low voltage switchboard, interconnection between HT switchgear & Transformer using single core cables and Transformer to LT switchgear using Al bus bars/Cables factory built / ready for connection type,otherassociated equipment etc including necessaryfoundation and earth work etc. without oil pits complete as required conforming to detailed specification laid down in the tender documents. The enclosure shall have modular construction using 2mm thick CRCA and 4 mm thick got dipped CRCA sheets for base and shall be painted with polyurethane paint from the exterior.The enclosure for LT switchgear & HT switchgear shall be provided with IP54ingress protection. The transformer compartment will have IP34 ingress protection. Note- HT & LT Switchgear should besame make. 47 The transformer used shall be specially designed for low losses (As per IS:-1180 level-01) and shall be hermetically sealed oil immersed& with corrugated tank, oil level indicator, hermetic protection realy, pressure relief device, gas filling valve, oil temprature indicator, multi function relay (DGPT Device) etc. as required Complete in all respect.The earthing shall be suitablefor 18.3KA fault current.The varoius combinations of CSS shall be as per details below including necessaryfoundation and earth work etc 48 HT Switchgear Section 49 11KV 3 Way RMU( CCT2) type Compact switchgear unit having 2 No. Isolater load break switches and1 No SF 6 circuit breaker enclosed in robotically laser welded non-extensible type stainless steelSF6 enclosure with Self powered relay (IDMTL O/C + E/F ) as HT switchgear as per the requirement detailed in the tender documents/SLD. 50 Copper bus bars of 800 A capacity for HT 11 KV network. 51 Transformer Section 52 11KV/415V,1000KVA, hermetically sealed oil immersed Transformer suitable for CSS as per detailed specifications, with Automatic on load tap changer & RTCC .Remote tap changer circuit (RTCC) panel with all associated accessories as per schedules and specifications.Taps on HV for HV variation : +5 to - 15 % in the steps of 1.25 with AVR. 53 LV Switchgear Section 54 LT section comprising the following & as shown in the drawing: 55 1600Amps 415V, 4P, 50Hz, 50KA Manual operated drawout type Air Circuit Breaker (ACB) with overload and short circuit Protection. 56 RELAYs, METERING INDICATOR & CTs 57 On/Off Indication lamps with 6A control MCB as per fault requirement 58 R,Y,B phase Indication lamps with Control MCB as per fault requirement. 59 One Set of 5 Nos. indication panel each with 6A control MCB as per fault requirementwith ACB 60 1 No. off delay timer for manual operation. 61 Phase Reversal relay 62 8 Window annunciator all compartment 63 Heat shrinkable cable end terminal indoor type cable box 240/300/400 Sq. mm. Size complete all as required to connect incoming and outgoing HT cables to unitized Sub-Station and interconnection of network within the unitized Sub-Station with arc proof shoes. 64 COMPACT SUB-STATION-1000KVA AS DESCRIBED ABOVE 65 H.T. Cable 66 Supplying of following size of Al conductor, XLPE insulated armoured and over all PVC sheathed, 11 KV (E) grade earthed cable as per technical specifications 67 3 core x185Sq. mm YEIDA SOR-2(B) 68 HT Cable laying 69 supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required. 70 3C X185 Sq. mm YEIDA SOR 4(G) 71 S/L of 200mm dia. H.D.P.E. pipe for drawing of power cable across the road by drilling of 220mm dia. at 1mtr. below the road level thereby doing the work of providing H.D.P.E pipe by manual Trenchless method.PE-63/PN-8 complete in all respect, as directed by Engineer in charge YEIDA SOR-23 72 S/F of 11kv HV insulating mats confirming to IS 15652-2006. The mats should have been type tested by CPRI or another third party lab of equivalent stature. The mats shall be moisture proof, fire retardant and resistant to acids, alkalies & transformer oil. Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-59 73 Supply and fixing in position the approved “Shock Treatment Charts” written in English and Local Language. These charts shall be framed in teak wood frame and covered with glass. 74 Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. 75 Supply and fixing position the approved single line diagram framed in 1000 x 100 mm size glass frame and installed in main LT Panel Room. 76 Supply of tool kit, first aid box with all accessories required for operation and maintainence for 415 volt & 11 kV equipment with 1 pair 11 kV rubber hand gloves of approved make. 77 Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. 78 SUBHEAD-II-DIESEL GENERATOR SETS 79 FOR - BUILDING NO- 10 80 Supply, installation, testing and commissioning of Prime Duty, Diesel engine driven generating Set (Silent Type) of 1010KVA capacity CPCB-IV compliance to ISO-8528-Part 1 with Genset Controller (DIEF / DeepSea / Woodward or eq) and comprising of following:- 81 The DG Set emission should be as per revised CPCB-IV norms as per the latest notification MOEFCC NOTIFICATION “GSR 804(E) DATED 03.11 .2022 [F.NO. Q-15017/05/2012-CPW 82 a) Diesel Engine 83 Engine developing minimum1010kVA Gross Engine Power at 1500 RPM rated for Prime Duty with an additional 10% overload capacity for one hour in period of twelve hours of continuous operation at standard operation conditions as per ISO 3046-1/1, ISO 15550 inclusive of all standard accessories like Silencer, After Treatment System In Front of Radiator, High Pressure Common Rail (HPCR) Fuel Injection, ECU control providing efficient performance in terms of power & fuel consumption, Electronic Governing of G3 Governing Class and with all standard accessories as per ISO:8528-5.Engine Cooling System must be designed for 50⁰C ambient 84 b) Alternator 85 Synchronous alternator 1010KVA, AC 3 phase, 415 volt, 50 Hz, 1500 RPM, 0.8 lagging power factor alternator shall be in SPDP enclosure, self excited, self regulated, foot mounted with end shield. The alternator shall confirm to IS:13364/IEC 60034 – 1 suitable for tropical conditions.Alternator shall deliver full output at 50 degree C, shall have inbuilt BTD and winding temp. detector along with space heaters. Necessary spaace provision for REF protection with separate earth fault CTs shall be provided inside alternator box. alternator should one heigher rating size for 50 degree amb. 86 c) Automatic Main Failure Panel 87 DG AMF control panel with internal access to facilitate both connection and maintenance complete with 1 No 1600Amps ACB WITH COPPER BUSBAR to loads. Ammeter, Voltmeter, frequency meter, Kh meter etc. including light Set ON/OFF battery charge etc. complete in all respect with power loom between alternator & isolator panel thru CU flexible within the Genset Canopy / Acoustic Enclosure.Engine mounted instrument panel fitted with and having digital/Analog display. 88 d) Acoustic Enclosure 89 The enclosure fabricated from high grade cold rolled close annealed (CRCA) sheet and steel members lined with high density sound absorption material to reduce the sound level to 75 dBA from the original sound level measured at a distance of 1 meter away from the GenSet, under free field conditions compliance to CPCB- IV Noise limit / guidlines for Dg Set below 1000kVA / 800Kwe. Accoustic and weather proof enclosure suitable for the DG Set with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air into the atmosphere as per CPCB-IV norms.The enclosure will be provided with durable industrial locking system with doors duly gas-keted etc., all complete with ARAI Type approval / certification. 90 e) Battery 91 2x12V, 150 Ah Battery assembly with all necessary connecting leads and terminals of reputed make and stand for lead acid Maintinance free battery. Starter Motor Power must be min 8KW 92 f) Base frame 93 Skid mounting type base frame fabricated from suitable size of MS channel / CRCA Sheet providing common bed for engine & alternator directly coupled together with AVM Pads and necessary reinforcement which shall be installed on suitable RCC foundation and vibration isolation arrangement as per recommendations of manufacturer. 94 g) Testing in Works / Factory 95 The DG sets will be tested in the works of the manufacturer for 12 hours at full load including 10% over load before dispatch in the presence of the representative of client . Testing will be crried out as per CPWDs specifications. 96 h) MISC 97 Inbuilt Capacity Day tank of standard capacity . for fuel storage with level markings inside and outside canopy. 98 After Treatment System In Front of Radiator with DEF (diesel exhaust fluid) / AdBlue storage tank of min 35L for urea dosing with proper connection etc. 99 SITC of TP,1600A, Electrical Fix ACB Isolator Panel Outside Canopy with IP4x suitable for Indoor application. Power Cabling b/w DG Set & Isolator Panel included and thes ameneeds to be done at site by electrical contractor. YEIDA RATE- 4.02 100 DG SET 1010 KVA AS PER DESCRIBED ABOVE 101 EXHAUST PIPING 102 Supply and Fixing of MS Exhaust Pipe of dia 350mm class B for 1010KVA DG Set with rain cap. With all accessories etc., complete 103 Supply and fixing of Thermal insulation on MS Exhaust Pipe of dia 350mm class B for 1010 KVA DG Set with 50mm thick LRB/Rock Wool of 96 Kg density per cub mtr. Covered with wire mesh & covered with 24 gauge AI Sheet 104 Supply,testing and commissioning ofAluminium cladding for residential silencerswith LRB Rockwool 50mm Thick, density 64 Kg/cu.mtr., wire mesh and 24 gauge aluminium cladding. complete as required suitable for 1010 Kva DG exhaust pipe temperature upto 450°C. 105 Supply and installation of SS Flexible Bellows, 8 dia. (350 mm NB), complete with counter flanges, heat resistant gaskets, nuts-bolts-washers etc., complete as required. 106 Providing & fixing for MS support structure for exhaust fume pipes from DG Sets (Exhaust pipe to be measured and paid for separately) along horizontal and vertical runs upto the height (as per CPCB norms) including cutting, welding etc and applying two coats of red oxide and two coats of synthetic enamelled paint of colour and shade as directed by client/Architect. The design of the support structure shall be done by the contractor and shall be as per CPCB norms approved , also to get the approval from the consultant before execution etc. as required. 107 Provide & fixing fuel piping with pipe supports, bends, flanges packing, hardwares and painting from main storage tank to day oil tank and day oil tank to DG Set of following sizes 108 25 mm dia Heavy duty (Class C ) MS Pipe 109 VALVES 110 Supply & fixing the following valves of approved make complete with flanges, bolts nuts and gaskets etc., 111 25mm dia gate valve 112 Supply & fixing of 990 Litre (14 SWG thick) fuel oil service tank with oil level indicator with level gauge scale, inlet/outlet connection valve, air vent, pedestal for mounting etc., including 02 Nos if hand fuel transfer pumps 113 Obtaining necessary approvals from the chief electrical inspectorate, if required for electrical safety for 1X 1010kVA Genset. 114 SUBHEAD-III- 15 KVA UPS 115 Supply, installation, testing and commissioningof IGBT Rectifier & Inverter basedUPS system comprising of 1 no 15 kVA units with batterybank backup of 30 minutes duration for full load with all standards fittings, accessories, protection, instruments, indications and controls including but not restricted to transformer, rectifire, inverter, SMF battery with float cum boost battery charger, static bypass switch, maintenance bypass, output isolation transformer, interconnections etc.including warranty and free all inclusive comprehensive maintenance services for two years for UPS and battery bank after the date of handing over complete as per specification and as required.YEIDA RATE - 45.03 116 SUBHEAD-IV-LTPANEL& DISTRIBUTION BOARD 117 Supply,Installation, Testing and Commissioning of dust, damp and vermin proof IP- 4X / 5X free floor standing /wall mounted, Indoor type, form 3B/4A complied factory assembled in sheet steel enclosed modular construction, extendable from both side, fabricated out of CRCA grade d or equivalent sheet steel for load bearing member in 2mm thick and 1.6mm for non-load bearing members and doors with covers, 3mm thick for gland platescomplete with 9 tank pre treatment process for powder coating with minimum 80 to 100 micron electro static powder coating coverage in approved shade of RAL 7032/7035 in elasto polymer type powder, complete with Aluminium bus bars designed for proper temperature rise withstand capacity, inter-connection with copper conductor wires / aluminium strips, neutral links, earth bus etc. including control wiring with 1.5sqmm. & 2.5sqmm. PVC insulated FRLS copper conductor S/C cable for voltage & current respectively, cable alleys, cable gland plates in two half for acb panels, etc. suitable for operation on 415 ±10% volts, 50 Hz AC 3 phase 4 wire system necessary metering protections & indications and mounted with the following switch gears etc. complete as required complying with IEC-61439 Part1&2 . 118 (Each MCCB will have variable current setting for over current and short circuit, front extended lockable handle, pad lockable in off position, indication light for ON, shrouding on incomer side, termination shall be suitable for aluminium bus bars. All MCCBs shall be microprocessor based only otherwise as specified in the boq. 119 All Switchboards shall have provision for entry of cables from the top or bottom as required 120 All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The Busbars shall be fully insulated with heat shrinkable sleeves and should withstand busbar temp. The busbar support insulators should be SMC. Padlocking isolating switches and load break switches lockable in OFF position. The panel shall meet criterias as per Client EHS guideline. 121 All kA ratings indicated shall be Ics = Icu = Icw values 122 Ics value should be 100% 123 GA drawings shall be got approved from Owners/Architects/ Consultants before fabrication. 124 Tube based Clean Agent Fire suppression systemshall be taken for all panels as specified in the boq. 125 All Panel should be Form 4b (For ACB Compartment) &3b combination. 126 MAIN L.T PANELIcs = 50KA 127 Incomers :- 3 Nos numbers (2 x 1600A, 4P EDO ACB from CSS + 1 x 1600A 4P EDO ACBDG. 128 Incomer from CSS of 1010 kVA 129 2 Nos.1600A 4P EDO ACB with microprocessor based communicable release, over current with different time settings, short circuit with time delay & earth fault release with time delay, instantaneous current setting . Suitable links shall be provided for cable termination. ON/OFF/TRIP indication shall be wired through potential free contact up to terminal strip of breaker for hooking to BMS. Each incomer shall have following. 130 1 no. 0-500V 96 sqmm digital voltmeter with selector switch, 3 No. phase indicating lamps to show the incoming power with control 2A TP MCB. 131 3 Nos. indicating lights for ACB on/ off/ trip position. 132 1 No.phase reversal relay with matching cast resin CTs 133 1 no. 3 phase voltage monitoring relay cum phase sequence meter 134 1 No. APFC relay with matching cast resin CTs. 135 Incomer from DGs 136 1No. X 1600A 4P EDO ACB with microprocessor based, over current with different time settings, short circuit with time delay & earth fault release with time delay. Suitable links shall be provided for cable termination. ON/OFF/TRIP indication shall be wired through potential free contact up to terminal strip of breaker for hooking to BMS. Each incomer shall have following. 137 This release shall have RS-485 including showing all parameters on the software before integrating to IBMS 138 1 no. 0-500V 96 sqmm digital voltmeter with selector switch, 3 No. phase indicating lamps to show the incoming power with control 2A TP MCB. 139 3 Nos. indicating lights for ACB on/ off/ trip position. 140 1 No. ON/OFF push buttons. 141 1 No. reverse power relay with matching cast resin CTs 142 1 no. 3 phase voltage monitoring relay cum phase sequence meter 143 Bus Couplers 144 One number 1600A 4 pole EDO ACB microprocessor based over current, short circuit release type as bus coupler. Necessary contacts shall be wired upto terminal strip for breaker ON/OFF/TRIP, providing potential free contact ON/OFF/TRIP for status monitoring in BMS. 145 Bus Bar Section-I & II 146 Two set ofTPN Aluminium bus bar rated for 2000A (after considering all necessary deratings) 3 phase 4wire, 50Hz. A minimum derating factor of 0.80 must be taken for calculation of bus bar sizes. The bus bar size after derating shall be equal to the ampere given in the BOQ. current density of bus-bars shall not be more than 0.8 Amps/sq.mm for Aluminium and earth bus size shall be suitable of system fault level. 147 Outgoings Sections 148 4 Nos. 800A 4P feeder each having one no. 800A 4P EDO ACB 149 3 Nos. 500A 4P feeder each having one no. 500A 4P MCCB. 150 2 Nos. 100A 4P feeder each having one no. 100A 4P MCCB 151 5 Nos. 63A 4P feeder each having one no. 63A 4P MCCB 152 Other items such as 153 PLC for Necessary electrical Interlocking through advance contacts / contactorsin MCCB/ ACBs (Incomers & Bus couplers)should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed & as required. 154 Panel with auto and manual operation and Load Manager for both Mains and DG power, whose function will be to determine the Load. Supplier to submit the Bill of materials for the above functions also provide motorised potential meter for each generator for voltage correction. 155 1kVA online UPS with minimum 15 minutes backup built in battery for PLC system. 156 1 Lot of control wiring. 157 1 Set of designation plates 158 Tube based Clean Agent Fire suppression systemshall be taken for panels. 159 MAIN L.T PANEL as describe above and shown in SLD. 160 BUILDING PANEL-01 Ics = 35KA 161 Incomer:- 162 2Nos. X 800A 4P EDO ACB with microprocessor based, over current with different time settings, short circuit with time delay & earth fault release with time delay. Suitable links shall be provided for cable termination. ON/OFF/TRIP indication shall be wired through potential free contact up to terminal strip of breaker for hooking to BMS. Each incomer shall have following. 163 1 no. 0-500V 96 sqmm digital voltmeter with selector switch, 3 No. phase indicating lamps to show the incoming power with control 2A TP MCB. 164 3 Nos. indicating lights for ACB on/ off/ trip position. 165 1 No.phase reversal relay with matching cast resin CTs 166 1 no. 3 phase voltage monitoring relay cum phase sequence meter 167 Bus Bar 168 One set of TPN, AL. bus bar rated 1000Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 169 The outgoing feeders are as follows : 170 3 Nos. 200A 4P feeder each having one no. 200A TP MCCB. 171 4 Nos. 160A 4P feeder each having one no. 160A TP MCCB. 172 Tube based Clean Agent Fire suppression systemshall be taken for panels. 173 1 set of complete wiring 174 Necessary electrical Interlocking through advance contacts / contactorsin MCCB/ ACBs (Incomers & Bus couplers)should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed & as required. 175 BUILDING PANEL-01 Ics = 35KA as describe above and shown in SLD. 176 BUILDING PANEL-02Ics = 35KA 177 Incomer:- 178 2Nos. X 800A 4P EDO ACB with microprocessor based, over current with different time settings, short circuit with time delay & earth fault release with time delay. Suitable links shall be provided for cable termination. ON/OFF/TRIP indication shall be wired through potential free contact up to terminal strip of breaker for hooking to BMS. Each incomer shall have following. 179 1 no. 0-500V 96 sqmm digital voltmeter with selector switch, 3 No. phase indicating lamps to show the incoming power with control 2A TP MCB. 180 3 Nos. indicating lights for ACB on/ off/ trip position. 181 1 No.phase reversal relay with matching cast resin CTs 182 1 no. 3 phase voltage monitoring relay cum phase sequence meter 183 Bus Bar 184 One set of TPN, AL. bus bar rated 1000Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 185 The outgoing feeders are as follows : 186 3 Nos. 250A 4P feeder each having one no. 250A TP MCCB. 187 3 Nos. 160A 4P feeder each having one no. 160A TP MCCB. 188 1 No. 125A 4P feeder each having one no. 125A TP MCCB. 189 Tube based Clean Agent Fire suppression systemshall be taken for panels. 190 1 set of complete wiring 191 Necessary electrical Interlocking through advance contacts / contactorsin MCCB/ ACBs (Incomers & Bus couplers)should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed & as required. 192 BUILDING PANEL-02 Ics = 35KA as describe above and shown in SLD. 193 COMMON PANELIcs = 35KA 194 Incomer 195 1 No. Incomer 160 Amps 4P MCCB with thermal magnetic releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 196 Bus Bar 197 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 198 The outgoing feeders are as follows : 199 1 No. 125A 4P feeder having one no. 125A 4P MCCB . 200 7 Nos. 63Amps 4P feeders each having one number 63 Amps 4P MCB. 201 2 Nos. 40Amps 4P feeders each having one number 40 Amps 4P MCB. 202 Tube based Clean Agent Fire suppression systemshall be taken for panels. 203 1 set of complete wiring 204 COMMON PANEL Ics = 25KA as describe above and shown in SLD. 205 METER BOARD-01 &03 (G.F&F.F )Ics = 35KA 206 Incomer 207 1 No. Incomer 200 Amps 4P MCCB with thermal magnetic releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 208 Bus Bar 209 One set of TPN, AL. bus bar rated 250Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 210 The outgoing feeders are as follows : 211 1 Nos. 400MM (H) x 375MM(W) Glass window compartment each with Lock & key arrangement including backelite sheet for mounting provided digital Three Phase pre-paid duel source CT operated Energy Meter with RS485 Port for BMS connectivity. Incuding providing and fixing of din channel monted 4P, 100A, MCCB, 25kA with 100A, connecters in cable alley and power wiring between meter and connector via MCCB. 212 6 Nos. 300MM (H) x 375MM(W), Glass window compartment each with Lock & key arrangement including backelite sheet for mounting provided digital Three Phase pre-paid Energy duel source Meter with RS485 Port for BMS connectivity. Incuding providing and fixing of din channel monted 4P, 40A, MCB, 10kA with 63A, connecters in cable alley and power wiring between meter and connector via MCB. 213 2Nos. 40Amps 4P feeders each having one number 40 Amps 4P MCB. 214 Tube based Clean Agent Fire suppression systemshall be taken for panels. 215 1 set of complete wiring 216 METER BOARD-01 &03 (G.F&F.F )Ics = 35KA as describe above and shown in SLD. 217 METER BOARD-02&04 (G.F & F.F )Ics =35KA 218 Incomer 219 1 No. Incomer 160 Amps 4P MCCB with thermal magnetic releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 220 Bus Bar 221 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 222 The outgoing feeders are as follows : 223 10 Nos. 300MM (H) x 375MM(W), Glass window compartment each with Lock & key arrangement including backelite sheet for mounting provided digital Three Phase pre-paid Energy duel source Meter with RS485 Port for BMS connectivity. Incuding providing and fixing of din channel monted 4P, 40A, MCB, 10kA with 63A, connecters in cable alley and power wiring between meter and connector via MCB. 224 2 No. 40Amps 4P feeders having one number 40 Amps 4P MCB. 225 Tube based Clean Agent Fire suppression systemshall be taken for panels. 226 1 set of complete wiring 227 METER BOARD-02&04 (G.F&F.F )Ics =35KA as describe above and shown in SLD. 228 METER BOARD-05&07 (S.F & T.F )Ics = 35KA 229 Incomer 230 1 No. Incomer 200 Amps 4P MCCB with thermal magnetic releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 231 Bus Bar 232 One set of TPN, AL. bus bar rated 300Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 233 The outgoing feeders are as follows : 234 1 Nos. 400MM (H) x 375MM(W) Glass window compartment each with Lock & key arrangement including backelite sheet for mounting provided digital Three Phase pre-paid duel source CT operated Energy Meter with RS485 Port for BMS connectivity. Incuding providing and fixing of din channel monted 4P, 125A, MCCB, 25kA with 125A, connecters in cable alley and power wiring between meter and connector via MCCB. 235 1 No. 300MM (H) x 375MM(W), Glass window compartment each with Lock & key arrangement including backelite sheet for mounting provided digital Three Phase pre-paid Energy duel source Meter with RS485 Port for BMS connectivity. Incuding providing and fixing of din channel monted 4P, 63A, MCB, 10kA with 63A, connecters in cable alley and power wiring between meter and connector via MCB. 236 1 Nos. 125Amps 4P feeders each having one number 125 Amps TP MCB. 237 Tube based Clean Agent Fire suppression systemshall be taken for panels. 238 1 set of complete wiring 239 METER BOARD-05&07 (S.F & T.F )Ics = 35KA as describe above and shown in SLD. 240 METER BOARD-06&08 (S.F&T.F )Ics = 35KA 241 Incomer 242 1 No. Incomer 250 Amps 4P MCCB with thermal magnetic releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 243 Bus Bar 244 One set of TPN, AL. bus bar rated 250Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 245 The outgoing feeders are as follows : 246 2 Nos. 400MM (H) x 375MM(W) Glass window compartment each with Lock & key arrangement including backelite sheet for mounting provided digital Three Phase pre-paid duel source CT operated Energy Meter with RS485 Port for BMS connectivity. Incuding providing and fixing of din channel monted 4P, 125A, MCCB, 25kA with 125A, connecters in cable alley and power wiring between meter and connector via MCCB. 247 1 Nos. 125Amps 4P feeders each having one number 125 Amps TP MCB. 248 Tube based Clean Agent Fire suppression systemshall be taken for panels. 249 1 set of complete wiring 250 METER BOARD-06&08 (S.F&T.F )Ics = 35KA as describe above and shown in SLD. 251 PRESSURIZATION PANELAT TERRACE (OUTDOOR TYPE)Ics = 25KA 252 Incomer 253 1 No. Incomer 63Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 254 Bus Bar 255 One set of TPN, AL. bus bar rated 200 Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 256 The outgoing feeders are as follows : 257 1 No. of 7.5 amp rating of TP MCCB of 50 kA breaking capacity with 2.2 KW DOL motor starter type iico-ordination along with TP power contactors (AC3) with inbuilt 2NO + 2NC contact with necessary additional potantial free auxiliary contactor oprate starter ON/OFF and remote switching, Red, Green & Yellow Indicating Lamps, Start/Stop Push buttons LED type, Auto/Manual/Off selector switch Complete as required. 258 1No.7.5 Amps TP MCCB with DOL Starter .(Space only) 259 1 set of complete wiring 260 PRESSURIZATION PANELAT TERRACE (OUTDOOR TYPE)Ics = 25KA as describe above and shown in SLD. 261 COMMON AREA VRV PANEL AT TERRACE(OUTDOOR TYPE)Ics = 35KA 262 Incomer 263 1 No. Incomer 125 Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 264 Bus Bar 265 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 266 The outgoing feeders are as follows : 267 2 Nos. 40Amps 4P feeders each having one number 40 Amps 4P MCB along with 40 4P ELCB (100mA). 268 4 Nos. 32Amps 4P feeders each having one number 32 Amps 4P MCB along with 40 4P ELCB (100mA).. 269 1 set of complete wiring 270 COMMON AREA VRV PANEL AT TERRACE(OUTDOOR TYPE)Ics = 35KA as describe above and shown in SLD. 271 PLUMBING PANEL Ics = 35KA 272 Incomer 273 1 No. Incomer 63Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 274 Bus Bar 275 One set of TPN, AL. bus bar rated 200 Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 276 The outgoing feeders are as follows : 277 2 Nos. of 12 amp rating of TP MCCB of 50 kA breaking capacity with 5 HP DOL motor starter type iico-ordination along with TP power contactors (AC3) with inbuilt 2NO + 2NC contact with necessary additional potantial free auxiliary contactor oprate starter ON/OFF and remote switching, Red, Green & Yellow Indicating Lamps, Start/Stop Push buttons LED type, Auto/Manual/Off selector switch Complete as required. (For Sump Pump -1working&1 standby). 278 2 Nos. of 10 amp rating of TP MCCB of 50 kA breaking capacity with 3 HP DOL motor starter type iico-ordination along with TP power contactors (AC3) with inbuilt 2NO + 2NC contact with necessary additional potantial free auxiliary contactor oprate starter ON/OFF and remote switching, Red, Green & Yellow Indicating Lamps, Start/Stop Push buttons LED type, Auto/Manual/Off selector switch Complete as required. (For Domestic Transfer Pump -1working&1 standby). 279 2 Nos. of 10 amp rating of TP MCCB of 50 kA breaking capacity with 3 HP DOL motor starter type iico-ordination along with TP power contactors (AC3) with inbuilt 2NO + 2NC contact with necessary additional potantial free auxiliary contactor oprate starter ON/OFF and remote switching, Red, Green & Yellow Indicating Lamps, Start/Stop Push buttons LED type, Auto/Manual/Off selector switch Complete as required. (For Flusing Transfer Pump -1working&1 standby). 280 2Nos. of 7.5 amp rating of TP MCCB of 50 kA breaking capacity with 2 HP DOL motor starter type iico-ordination along with TP power contactors (AC3) with inbuilt 2NO + 2NC contact with necessary additional potantial free auxiliary contactor oprate starter ON/OFF and remote switching, Red, Green & Yellow Indicating Lamps, Start/Stop Push buttons LED type, Auto/Manual/Off selector switch Complete as required.(For Flusing Booster Pump -1working&1 standby). 281 2No. of 7.5 amp rating of TP MCCB of 50 kA breaking capacity with1 HP DOL motor starter type iico-ordination along with TP power contactors (AC3) with inbuilt 2NO + 2NC contact with necessary additional potantial free auxiliary contactor oprate starter ON/OFF and remote switching, Red, Green & Yellow Indicating Lamps, Start/Stop Push buttons LED type, Auto/Manual/Off selector switch Complete as required.(1working&1 standby). 282 1No.32 Amps DP MCB 283 1 set of complete wiring 284 PLUMBING PANEL Ics = 35KA Ics = 35KA as describe above and shown in SLD. 285 320KVAR Capacitor PanelIcs = 35KA 286 320KVAR CAPACITOR PANELS (5X50 KVAR + 1X25KVAR + 3X10KVAR+ 3X5KVAR) 287 Supplying, installation, testing & commissioning of factory built floor mounted auto-manualpower factor correction system panel of 320KVAR capacity having 3 phase, Mixed Die Electric(total power loss not exceeding 0.50 W/ KVAR) power capacitor in eleven steps, filled with suitable oil and; provided with 10KVAR fixed capacity and balance Electronic Thyristor switching & detuned filters (min.7%) to supress switching of inrush current and reducing harmonics to improve capcitor life. 288 The system Shall be provided with required capacity master MCCB, to control its main operating parameters such as over loads, short circuit, etc. 289 The panel shall be fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, having 800 Amp capacity extensible type TPN Aluminium Alloy bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 35 MVA for I Sec., bottom base channel of MS section not less than 100mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common GI earth bar of size 75 mm x 10 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears/ accessorieswith required size of Al. bus bars and control wiring with 2.5 sq.mm. PVC insulated FRLS copper conductor Single Core cable, of2 mm thick MS Sheet, provided with exhaust fans (with thermostat) and grills for proper ventilation, interconnections with suitable size conductor cables & lugs and accommodating the following swicthgears & accessories: 290 800Amp 3 Pole ACB- 1 No. 291 LED Indicating light - 12 Nos. 292 One numbers dual source, dual setting, binary typeautomatic power factor sensing and correction relay (12stages) complete with its all accessories etc. asrequired. 293 MCCBof following capacity with spreader link and phase barrier 294 125 A, 3P,MCCB - 5Nos. 295 63 A, 3P,MCCB - 1 Nos. 296 32 A, 3P,MCCB- 6 Nos. 297 L.T. Powerfactorimprovingcapacitor of indoortypesuitable for operation on415 volts AC 3 phase 50 Hzcomplete with bankingarrangement, interconnections with suitable size ofcopper conductor PVCinsulated PVC sheathedunarmoured cable, dischargeresistance etc. as required. 298 Bank of50 KVArrating -5 Sets 299 Bank of 25 KVAr rating -1 Set. 300 Bank of 10 KVAr rating -1 Set. (FIXED TYPE). 301 Bank of 10 KVAr rating - 2 Set 302 Bank of5 KVAr rating -3 Set 303 APFC Panel as described above and shown in SLD 304 OFFICE PANEL-1&5 AT S.F & T.FIcs = 35KA 305 Incomer 306 1 No. Incomer 125 Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 307 Bus Bar 308 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 309 The outgoing feeders are as follows : 310 2 Nos. 100Amps 4P feeders each having one number 100 Amps 4P MCCB. 311 2 Nos. 63Amps 4P feeders each having one number 63 Amps 4P MCB. 312 1 set of complete wiring 313 OFFICE PANEL-1&5 AT S.F & T.FIcs = 35KA as describe above and shown in SLD. 314 OFFICE PANEL-2,3&7 AT S.F & T.FIcs = 35KA 315 Incomer 316 1 No. Incomer 125 Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 317 Bus Bar 318 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 319 The outgoing feeders are as follows : 320 1 Nos. 100Amps 4P feeders having one number 100 Amps 4P MCCB. 321 4 Nos. 63Amps 4P feeders each having one number 63 Amps 4P MCB. 322 1 set of complete wiring 323 OFFICE PANEL-2,3&7 AT S.F & T.FIcs = 35KA as describe above and shown in SLD. 324 OFFICE PANEL-6 ATT.FIcs = 35KA 325 Incomer 326 1 No. Incomer 125 Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 327 Bus Bar 328 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 329 The outgoing feeders are as follows : 330 2 Nos. 100Amps 4P feeders each having one number 100 Amps 4P MCCB. 331 2 Nos. 63Amps 4P feeders each having one number 63 Amps 4P MCB. 332 1 set of complete wiring 333 OFFICE PANEL-6 ATT.FIcs = 35KA as describe above and shown in SLD. 334 OFFICE PANEL-4&8 ATS.F& T.FIcs = 35KA 335 Incomer 336 1 No. Incomer 100 Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 337 Bus Bar 338 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 339 The outgoing feeders are as follows : 340 2 Nos. 63Amps 4P feeders each having one number 63 Amps 4P MCB. 341 1 No. 40Amps 4P feeders having one number 40 Amps 4P MCB . 342 1 set of complete wiring 343 OFFICE PANEL-4&8 ATS.F& T.FIcs = 35KA as describe above and shown in SLD. 344 HVAC PANEL-1ATTERRACEIcs = 35KA(Outdoor Type) 345 Incomer 346 1 No. Incomer 100 Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 347 Bus Bar 348 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 349 The outgoing feeders are as follows : 350 2 Nos. 63Amps 4P feeders each having one number 63 Amps 4P MCB along with 63Amp. 4P ELCB (100mA). 351 1 No. 32Amps 4P feeders having one number 32 Amps 4P MCB along with 40Amp 4P ELCB (100mA). 352 1 set of complete wiring 353 HVAC PANEL-1ATTERRACEIcs = 35KA (Outdoor Type) as describe above and shown in SLD. 354 HVAC PANEL-2,3&7ATTERRACEIcs = 35KA (Outdoor Type) 355 Incomer 356 1 No. Incomer 100 Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 357 Bus Bar 358 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 359 The outgoing feeders are as follows : 360 2 Nos. 40Amps 4P feeders each having one number 40 Amps 4P MCB along with 40 Amp. 4P ELCB (100mA). 361 1 No. 32Amps 4P feeders having one number 32 Amps 4P MCB along with 40Amp 4P ELCB (100mA). 362 1 set of complete wiring 363 HVAC PANEL-2,3&7ATTERRACEIcs = 35KA (Outdoor Type) as describe above and shown in SLD. 364 HVAC PANEL-5 &6ATTERRACEIcs = 35KA (Outdoor Type) 365 Incomer 366 1 No. Incomer 100 Amps 4P MCCB with microprocessor based releases for O/C, S/C, 3 Nos. phase indicating lamps to show the incoming power with control 2A TP MCB,and 1 no. digital multifunction meter with matching cast resin CTs. 367 Bus Bar 368 One set of TPN, AL. bus bar rated 200Amps (after considering necessary deratingsof 80%) for phases and neutral for half capacity of phases. 369 The outgoing feeders are as follows : 370 3 Nos. 63Amps 4P feeders each having one number 63 Amps 4P MCB along with 63Amp. 4P ELCB (100mA). 371 1 No. 32Amps 4P feeders having one number 32 Amps 4P MCB along with 40Amp 4P ELCB (100mA). 372 1 set of complete wiring 373 HVAC PANEL-5 &6 ATTERRACEIcs = 35KA (Outdoor Type) as describe above and shown in SLD. 374 Design, Manufacture, Supplying, loading & unloading assembling at site, installation, fixing on the position, testing & commissioning of the following cubical type, dead front, 2.5mm thick sheet steel enclosed, 1600Amp, 4P, MDO, ACB-50kA, without protection relays in 2.5 MM Thick sheet metal enclosed Out door to be located near D.G Set, including emergency push bottom with key lock and provide 5 Nos indicating lamps for status indication ON,OFF , tripped due to fault, DC supply healthy and spring charged complete as required. confirm to degree of protectio IP:55. Also provide M.S. Stand made height 600mm. Maximim height of panel should not be more then 2000mtr. 375 S & F surface/Flush mounting 4ways TPN distribution board with additional metal door without MCB complete in all respect,as directed at site by Engineer in charge. (For Lift). 376 S & F surface/Flush mounting 4ways V TPN distribution board with additional metal door without MCB complete in all respect,as directed at site by Engineer in charge. (For UPS O/P) 377 S&F of 80 to 100 Amp 4 pole MCCB (16 KA) Thermal Magnetic release (For UPS O/P DB Incomer) 378 S&F of 63 Amp. 4 pole MCB(10 KA) C Curve (LIFT DB ICOMER) 379 S&F of 6 Amp. to 32 Amp. TP MCB (10 KA) C Curve ( For UPS O/PDB & LIFT DB Outgoing ) 380 S&F and making connection of 40 Amp. 4 pole 30mA ELCB/RCCB of Din Rail Mounting complete in all respect as per direction and satisfaction to the Engineer in charge. (For Lifts) 381 Prepaid Meters 382 Supply , Installation & Commissiong of Dual source- 3 Phase, BIS-13779,BIS 15884 approved, class-1,Static meter 10-60Amp, including software license with RS 485 communication protocols and load manager including thimbling of power and control cables. Metere display show all the basic electrical parameters (V, A,KW,KVA,P.F, KWH / KVAH ).Model No. PE5120 383 Supply , Installation & Commissiong of Dual source- 3 Phase, BIS-13779,BIS 15884 approved, class-1,Static meter ct operated , including software license with RS 485 communication protocols and load manager including thimbling of power and control cables. Metere display show all the basic electrical parameters (V, A,KW,KVA,P.F, KWH / KVAH ).Model No. PE5120 384 Supply , Installation & Commissioning ofGateway RS485 to Ethernet Converter( Ethernet converter make : Elmeasure) MODEL NO :- GW1500 L 385 Supply , Installation & Commissioning of Software for pre / post metering with facilities:-1. Option configure meter for sanctioned load, terrif, happy hours day2. Option to recharge meter/ bill payment generation.3. Online portals for flat owners to check meter detail & online payment4. Report generation.Mobile app for administrators as well as individuals (Price of this item is excluded in energy meter price) (Make :- Elmeasure) 386 Energy meter sensing Cable :-Supply , Installation & Commissiong 2 Core 0.5 Sq.RS 485, tinted copper communication cablein conduit (meter to meter loop and connected to gateway) 387 DG sensing cable:-Supply , Installation & Commissiong 2 core 1.5mm flexible power cable for DG sensing 388 Supply , Installation & Commissiong of 9 Port Unmanaged switches as per the requirement. 389 SITC of Payment gateway for online recharge facility.(MYgate or NoBrokerHood)including SMS gateway for one year for alerts,(SMS alert if DG sensing is not done in any energy meters). 390 Supply, installation, testing & commissioning of Computer System with Configuration: System Processor - HP ML10, XEON E3 or Higher Version, Operating- System - Windows 10, RAM- 16GB or More, HDD 1 TB, Monitor 17 inch, Keyboard and Mouse. Standard warranty 3 yrs. direct from HP or equivalentThe software should be inclusive of the following:- 1) Connectivity to all meter to the PC.2) Monitoring the Grid & Supply Enery based on real time data.3) Generate the Electricity Bill for Clients.4) Pre paid system with Meter charging app to charge the meter through Paytm, Internet banking, Gpay, Phonepay, Bhim etc as per current payment scenario. Also it shall be capable to show the real time data i.e balance amount, daily basis consumption etc on user / client mobile / any other devices.5) Automatically Maintenance charges deduction. 6) Check & Balance of total energy and energy losses.7) Automatic Alert / Massage to Client / Users for Low Balance. 391 Supply , Installation & Commissiong of Cat 6 cable supply for for network end to end connectivity between meter board and server room 392 Supply , Installation & Commissiong of Cat 6 patch cord for network connectivity between DLC & MC. 393 SUB HEAD-V-STREET LIGHTING ELECTRICAL WORKS 394 Supply,unloading at site of following Outdoor type feeder pillar double door lockable type with epoxy paint. This panel shall be mounting on MS/brick pedestal support upto 400mm high from ground level,cubical, dust, vermin proof and outdoor type (IP65) fabricated as per specification laid in document with following incomming and outgoing feeders including making connections/inter-connections testing and earthing etc. required. 395 Feeder Pillar-01(Outdoor Type - IP 65)Ics=25 KA (FOR EXTERNAL LIGHTING) 396 Incomer:- 397 1 No. Incomer 63Amps 4P, MCCBwith microprocessor based O/C, S/C protections having 3 Nos. phase indicating lamps to show the incoming power control with MCB & 1 no. digital voltmeter with separate selector switch, 1 no. ON/OFF indication 398 63A TP,Cont with ON/ OFF indication lamp,ON/ OFF /TRIP,A/M Switch,Start/Stop push button and along with synchronizing 24 hours timer in auto mode. 399 Bus Bar : 400 A set of TPN, Cu. bus bar rated 150 Amps (after considering necessary deratings of minimum 0.80) for phases and neutral for half capacity of phases. 401 The outgoing feeders as follow: 402 4 Nos.16A 4P outgoing feeder each having 1 no. 16A 4P MCB 403 4 Nos.16A DP outgoing feeder each having 1 no. 16A DP MCB 404 3 Nos. 32 DP outgoing feeder each having 1 no. 32A DP MCB. (connected Before Timer and contector) 405 2Nos.16A 4P outgoing feeder each having 1 no.16A DP MCB(Spare) 406 1 set of complete wiring 407 External Lighting Panel as described above and shown in SLD 408 CABLE SUPPLY, LAYING & TERMINATION 409 Supply & laying of PVC insulated PVC sheathed armoured / unarmored aluminium/copper conductor cable directly in ground.The laying involves digging, making sand cushion cover on top and bottom of cable, providing brick support and filling with excavated earth for following sizes. 410 4c x 16 sqmm Al. Arm xlpe cable 411 3c x 4 sqmm cu. Arm xlpe cable 412 3c x 2.5 sqmm cu. Arm xlpe cable 413 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 414 4c x 16sqmm Al. Arm xlpe cable 415 3c x 4 sqmm cu. Arm xlpe cable 416 3c x 2.5 sqmm cu. Arm xlpe cable 417 POLES 418 Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness with single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect. 419 Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 45 watt to 50 Watt. Confirming to IP 66 protection complete in all respect. 420 CAT- AAA 421 Supply and fixing of decorative 8 to 16 Watt LED bollard luminaire with driver set confirming to IP 65 protection complete in all respect. 422 SUBHEAD-VI-LIGHTNING CONDUCTOR 423 Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. 424 Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. 425 Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) 426 Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) 427 Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. 428 Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. 429 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. 430 SUB HEAD VII- EARTHING 431 Supply and burying of 40mm dia x 4.5 metres long G.I. Pipe vertically for earthing having 12mm dia. Holes spaced 75mm apart drilled up to 2 metre from the bottom complete with earthing lead of No. 6 to 8SWG GI wire in G.I. Pipe up to appron (and from appron to switch board the cost of G.I. wire and pipe will be extra) upto switch board, 30cm square C.I. box with hinged cover masonary enclosure, funnel at top, alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing. 432 Supply and burying of 600mm x 600mm x 6mm G.I.plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead of two no. 8 to 10 SWG GI wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc.as per directions of Engineer-in-charge complete in all respect. 433 Supply and burying of 600mm x 600mm x 3mm copper plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and two earthing lead of two no. 8 SWG copper wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. pipeand copper wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc.complete in all respect. 434 Supply and laying of 32mm x 6mm copper strip from earth electrode directly in the ground as required complete in all respect. 435 Supply and laying of 25mm x 5mm G.I. strip from earth electrode directly in the ground as required complete in all respect. 436 Supply and fixing of one number 8 SWG G.I. wire in 15mm dia. G.I. pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand, labour, T&P other material required for proper completion of the work as directed at site. 437 Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. 438 Providing and fixing earth bus of 50 mm X 5 mm G.I strip on surface for connections etc. as required. 439 SUBHEAD-VIII-MV CABLE SUPPLY, LAYING AND TERMINATION 440 Supply of the following 1100 volts grade, Aluminium/Copper conductor, XLPE insulated, PVC sheathed, steel armoured/Unarmoured cables as per IS 7098 Part-1and as per technical specifications of this tender and directions of Engineer-in-Charge. 441 4 CORES AL. CONDUCTOR 442 16 sq.mm. Al Ar. XLPE cable 443 25 sq.mm. Al Ar. XLPE cable 444 3.5 CORES AL. CONDUCTOR 445 35 sq.mm. Al Ar. XLPE cable 446 50 sq.mm. Al Ar. XLPE cable 447 70 sq.mm. Al Ar. XLPE cable 448 95 sq.mm. Al Ar. XLPE cable 449 185 sq.mm. Al Ar. XLPE cable 450 300 sq.mm. Al Ar. XLPE cable 451 4 CORES Cu. CONDUCTOR 452 10 sq.mm. Cu. PVC Ar. cable 453 Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. 454 MV CABLE JOINTING & END TERMINATION 455 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(Y-34) 456 3½ X 35 sq. mm (32mm) 457 3½ X 50 sq. mm (35mm) 458 3½ X 70 sq. mm (38mm) 459 3½ X 95 sq. mm (45mm) 460 3½ X 185 sq. mm (57mm) 461 3½ X 300 sq. mm (70mm) 462 4 X 16 sq. mm (28mm) 463 4 X 25 sq. mm (28mm) 464 Supplying and making end termination with brass compression gland andCu lugs for following size of PVC insulated and PVC sheathed / XLPEcu conductor cable of 1.1 KV grade as required. 465 10 sq.mm. Cu. PVC Ar. cable 466 Supply, Unloading, shifting, Storing, Laying, Fixing, Testing, Commissioning & Single compression heavy duty glandsoffollowing sizes of Control Cables, Solid Copper conductor single stranded conductor, XLPE Insulated, cores laid up, PVC tape / Extruded Inner sheathed ,Glavanised round wire Armour, extruded PVC Type, 650V grade on existing cable trays/ in existing hume pipes/ PVC pipes/ GI pipes/ on surface of slabs, walls or masonary/ RCC trenches/ ducts including cables ties, GI saddles, clamps and necessary hard ware. 467 6 core x 2.5 sq. mm cable 468 10 core x 2.5 sq. mm cable 469 24 core x 2.5 sq. mm cable 470 SUBHEAD-IX-CABLE TRAYS 471 Hot Dipped Galvanized Iron Cable Tray 472 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 473 150 mm width X 50 mm depth X 1.6 mm thickness 474 300 mm width X 50 mm depth X 1.6 mm thickness 475 450 mm width X 50 mm depth X 2.0 mm thickness 476 600 mm width X 50 mm depth X 2.0 mm thickness 477 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray bends (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 478 150 mm width X 50 mm depth X 1.6 mm thickness 479 300 mm width X 50 mm depth X 1.6 mm thickness 480 450 mm width X 50 mm depth X 2.0 mm thickness 481 600 mm width X 50 mm depth X 2.0 mm thickness 482 Supplying and installing following size of perforated hot dipped galvanised iron cable tray tee (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with g.i. suspenders including g.i. bolts & nuts, etc. as required. 483 150 mm width X 50 mm depth X 1.6 mm thickness 484 300 mm width X 50 mm depth X 1.6 mm thickness 485 450 mm width X 50 mm depth X 2.0 mm thickness 486 600 mm width X 50 mm depth X 2.0 mm thickness 487 SUB-HEAD X-GAS Suppression System for Panels 488 SITC of DLP Direct Low Pressure with UL-Listed Lightweight Non-Corrosive Aluminium Cylinder with High grade Stainless Steel 304 Valve Body, Highgrade Brass Isolation Ball Valve 40 bar, High stainless steel Cylinder Mounting Bracket, UL Listed Pressure switch with factory-set for operation, double-throw configuration provides versatile control. The switch is equipped with an O-ring connection for secure, leak-free operation.,High Grade Stainless Steel 304 End of Line (EOL) adaptor with slip-on straight union and Pressure gauge, Stainless Steel 304 Schrader Adaptor with (removable) Pressure Gauge (to indicate pressure of the cylinder) Stainless steelsyphon Tube. Valve filled with CLEAN AGENT 3M NOVEC 1230/AFX-FK-1230 Gas and All components must have ATEX,UL,UKAP,LPCB and IAF approvals.Bidder or supplier must have to submit the OEMsAuthorisation letter and product approvals at the time of bid submission for the warrenty and product assurence. Approved make list- Regulas, AFX-(T), Janus. 489 DLP 4 KG System filled with 3M Novec-1230/AFX-FK-1230 (UL approved) Clean Agent Gas. 490 DLP 2 KG System filled with 3M Novec-1230/AFX-FK-1230 (UL approved) Clean Agent Gas. 491 DLP 1 KG System withfilled with 3M Novec-1230/AFX-FK-1230 (UL approved) Clean Agent Gas. 492 SITC offire detection tube The tube shall be UL Listed, made of modified polyamide, has an internal diameter of 4mm and an external diameter of 6mm. It operates under pressures ranging from 15 to 18 bar, with a minimum burst pressure of 123 bar. The tube is designed with excellent resistance to ozone and UV degradation test certificate to be attached. The bend radius of the tube is 42mm, making it flexible and adaptable to various installation environments. 493 SITC of End of line plug for automatic fire suppression system used for fitting at tube end to terminate the point. Fitting made by brass nickel plated material. 494 SITC of Tee connection 6/6mm Dual Seal Slip-on Swivel Tee High grade Brass Nickle plated material with maxmium pressure 25bar. 495 The stainless steel end-of-line adapter is equipped with a non-return valve and is compatible with 4/6mm tubing. It operates within a pressure range of 13–25 bar, with a maximum pressure of 72 bar, and is designed to withstand temperatures from -20°C to +120°C. 496 SITC of Master Control Unit 2 Zone with audio visual alarm control panel, 2 NO/NC potential free relay contacts discharhe LED indicator, Battery LED indicator system stuts indicator and AC power On LED indicator. 497 SUB HEAD - I - (WET RISERSYSTEM - PUMPING EQUIPMENTS) 498 Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : 499 Horizontal type, multistage, centrifugal, split casing pump of cast iron body & steel Stainless impeller with stainless steel shaft, mechanical seal complete. 500 Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-F insulation, conforming to IS-325. 501 M.S. fabricated Common base plate, coupling, coupling guard, pressure switch , pressure gauge , vibration eliminator pads , foundation bolts etc. as required. 502 Suitable cement concrete foundation duly plastered with anti vibration pads. 503 2280 lpm at 70 m Head 504 Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) 505 Horizontal type, multistage, centrifugal, split casing pump of cast iron body & steel Stainless impeller with stainless steel shaft, mechanical seal complete. 506 Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 15 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. 507 M.S. fabricated Common base plate, coupling, coupling guard, pressure switch , pressure gauge , vibration eliminator pads , foundation bolts etc. as required. 508 Suitable cement concrete foundation duly plastered and with anti vibration pads. 509 2280 lpm at 70 m Head 510 Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) 511 Horizontal type, multistage, centrifugal, split casing pump of cast iron body & steel Stainless impeller with stainless steel shaft, mechanical seal complete. 512 Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-F insulation, conforming to IS : 325. 513 M.S. fabricated Common base plate, coupling, coupling guard, pressure switch , pressure gauge , vibration eliminator pads , foundation bolts etc. as required. 514 Suitable cement concrete foundation duly plastered and with anti vibration pads. 515 180 lpm at 70 m Head 516 Supplying and fixing air vessel made of 250 mm dia, 8mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shadeas required. . 517 Providing, installation, testing and commissioning of stainless steel Ystrainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange 518 80 mm dia 519 150 mm dia 520 250 mm dia 521 Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : 522 250 mm dia 523 200 mm dia 524 150 mm dia 525 80 mm dia 526 Providing and fixing of Rubber Flexible Coupling with Control Unit PN:16 including Matching flanges & fastner. 527 150 mm dia 528 80 mm dia 529 SUB HEAD - II - (HYDRANTS SYSTEM) 530 Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : 531 Single headed Stainless steel 532 Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : 533 Stainless Steel (Grade 304) 534 Supplying & fixing 63 mm dia gun metal short branch pipe with 20mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: 535 Stainless Steel (Grade 304) 536 Providing, installation, testing and commissioningweatherproof lockable cabinet of size not less than0.90 x 0.60 x 0.30 mtr made out of M.S. sheet 2mm thick havingcentral openingand 6 mmthick glazedglass doors (Two nos.)suitably markedon the outside with the letters FIRE HOSE including necessary lockingarrangement and shall be painted with one coat of primer and two coats of synthetic enamel paint of approved shade as required as per specifications. 537 Supplying, installation, testing and commissioning of fire brigade connection of cast iron body with gun metal male & female instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 538 2 way - 100 mm dia M.S. Pipe 539 4 way - 150 mm dia M.S. Pipe 540 Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. 541 Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required 542 SUB HEAD - III - (PIPING, VALVES AND ACCESSORIES) 543 MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 544 150 mm dia 545 200 mm dia (wall thickness 6.3 mm) 546 250 mm dia (wall thickness 6.3 mm) 547 Providing, laying, jointing, testing & commissioning of heavy classM.S. pipes conforming to IS: 1239/3589 complete with fittings including trenching ,refilling and wraping coating etc.(external work) including all fittings andaccessories like tees, elbows, flanged joints, rubber insertion, nuts, bolts or cutting and welding joints. Providing thrust block at distance specified as per specifications. (Pipe shall be provided with anti corrosive protective treatment with coal tar/asphalt tape confirming to IS: 10221 standard complete as per specification). All work complete as per specification and as directed by Engineer-In-Charge. (All the fitting i.e. tee /elbow etc. for Valve connections etc. will be flanged joints). 548 150 mm dia 549 Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 550 80 mm dia 551 Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 552 80 mm dia 553 150 mm dia 554 200 mm dia 555 Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronzeworkingpartscomprisingofwatermotor alarm, bronze seat clapper, clapper arm and hydraulically drivenmechanical gong bell to sound continuousalarmwhen thewet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve completewith drainvalveandbypass, test control box, ball valves, MSpipeof requiredsize, flanges,orificeplate,gasket etc of follwing sizes as required : 556 150mm dia 557 SUB HEAD - IV - (FIRE EXTINGUISHERS) 558 Supply, installation, testing and commissioning of ISI marked Fire and wall suspension bracket fire Extinguisher, Trolley mounted carbon-dioxide type capacity 25 Kg. conforming to IS: 2878 Flat base including valve, discharge hose of not less than 10mm dia 1m long complete in all respects including wheeled trolley, carrying handle and initial fill with CO2 gas as per IS: 307-1996 filled to a filling ratio of not more than 0.667. 559 Supply, installation, testing and commissioning in position approved make fire bucket of 24 gauge, galvanized steel, standard 9 liters capacity and of round bottom shape, painted white inside and red outside and black on bottom dome with letters ‘FIRE’ in black and gold with all mounting bracket and screws. 560 Supply, installation, testing and commissioning of fire Bucket Stand including sheet metal (16 gauge) shade for 5 buckets. Platform and associated civil works complete. 561 SUB HEAD - V - (ELECTRICAL PANEL) 562 Fire Fighting Main Panel 563 Incoming 564 800A, 50kA 4 Pole MCCB, Ics=100% Icu rating 565 Digital Voltmeter 0-500V with selector switch 566 Digital Ammeter (0-800 A) with selector swtich & CTs etc. 567 LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps 568 Set of Copper Bus Bar 300A 569 OUTGOING 570 ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) 571 Main Fire Pump 572 250 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 100 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2sets 573 Jockey Pump 574 63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2sets 575 DIESEL ENGINE CONTROL 576 Control for diesel engine comprising - 577 Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode 578 Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication 579 Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter 580 All standard relays and accessories for automatic operation of diesel engine 581 System Controller 582 Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification. Fire panel as above