| 1 | Taking down u/s LED/HP/SV/HPMV Security light fittings of any wattage from Poles any hieght or any descripion, for repairs, dismantling the light fitting part by part, replace the unsv parts like PVC line connector, Connection cable, LED drivers etc,reassembleing complete & refixing at the existing place or other place as directed by Engr-in-charge. (Note: (i) The Contractor must be disconnecting/remove UNSV Security lights from pole, Remove carbon from conductor, replace PVC connector & connecting wire as required length for every fittings (ii) Electrical connection should be made with 3 core aluminium wire i e Phase, neutral & Earth, proper earthing to LED fittings should be made by any alternate arrangement (iv) Quoted rates shall be included for replacement of PVC line connector 3 terminal, PVC wire 3 core with aluminium conductor upto 2.5 RM and other minor accessories. (v) Major items like LED driver, wire measured and paid separately. |
| 2 | Supply only LED drivers suitable for LED Security light fittings of 45/60 watt complete all as specified and directed. |
| 3 | Supply only LED drivers suitable for LED Security light fittings of 72 watt complete all as specified and directed. |
| 4 | Supply only LED drivers suitable for LED Security light fittings of 90 watt complete all as specified and directed. |
| 5 | Supply and fixing of35/45 Wattnew generation energy saving and environmental friendly long life LEDstreet light made up of pressure dia cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP OPENING separate driver compartment with IP 66 protection and impact resistance of IK 07 with 10 KV Built-in-SPD complete all as specified and directed. |
| 6 | Supply and fixing of 60 Wattnew generation energy saving and environmental friendly long life LEDstreet light made up of pressure dia cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP OPENING separate driver compartment with IP 66 protection and impact resistance of IK 07 with 10 KV Built-in-SPD complete all as specified and directed. |
| 7 | Supply and fixing of 90 Wattnew generation energy saving and environmental friendly long life LEDstreet light made up of pressure dia cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP OPENING separate driver compartment with IP 66 protection and impact resistance of IK 07 with 10 KV Built-in-SPD complete all as specified and directed. |
| 8 | Supply and fix in replacement of 120 Watt LED flood light ( Red,Green and Worm White colour) fitting made up of Pressure die-cast aluminium alloy housing with toughened glass, IP65 protection and impact resistance of IK07 and individual high power LEDs with secondary optics having system lumen efficacy ≥100 lm/W, Inbuilt potted electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Over Voltage protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec 13 and BIS complying including surface mounting using adjustable MS cradle of thickness 5 mm provided with the fixture including taking down existing unserviceable flood light fitting of any description complete all as specified and directed. |
| 9 | S&F LED Tricolor (Orange/White/Green) 3 in 1 Tiranga Single Strip Light with 18 Meter length,LED Decorative Pole Lighting Etc-Pack of 1,IP 65 rating withstand harsh weather poof complete all as specified and directed. |
| 10 | S&F rectangular LED Flood light fittings 170 wattwith innovative thermal mangement, and with multiple optics and equiped with IP66 protection complete with electrical connection arrangement complete all as specified and directed. |
| 11 | S&F IP65 rated LED Post Top light fittings 40 watt with moonlight effect and efficient light distribution complete with electrical connection arrangement complete all as specified and directed. |
| 12 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape and overall PVC sheathed 2 core 10 sq. mm nominal cross section in service connections complete all as specified and as directed. |
| 13 | S&F in repairs cable junction box made of thermoplastic, halogen free, weather proof with metric Knock outs for cable entry including four/five pole terminals and cable entry glands for incomming, out going and connection cable with protection grade IP-66/67 of size 205 x 255 x112 mm and suitable for LT under ground cable any size/capacity including MCB SP 10 Amps fixed inside the box for street light controlling & bracing clamp,bolts,nuts & washers complete all as specified and directed. |
| 14 | M&L for GI Brackets bending & shaping of size 40 mm dia galvanised iron pipe light grade over all length 0.60 mtr including necessary clamps, brackets and bolts etc to fixing on pole complete all as specified and directed. |
| 15 | Supply, Installation and commissioning and testing of CPRI approved Street Lght Feeder Pillar Box cubical type suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system,with canopy sloped top projected, floor mounted outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 2.8 mm thick CRCA sheet, internal cover and partition made out of 3.15 mm thick CRCA sheet with angle iton 50mm x 50mm x 6mm covered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 60 CM above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washers etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-Charge:-(a) MCCB 100 Amps, 16KA 4 pole-1 No (b) Timer switch, light sensing type with contactor 32 Amps suitable for 3 phase distribution with enclosure. (Nature timer switch 3 phase of load 03 KW) - 01 Nos (c) Aluminium busbar 200 Amps TPN- 04 Nos (02 set as incoming & outgoing) (d) Digital voltmeter 0-500 Volts with selecter switch - 01 Nos (e) Digital Amp Meter 0-500 Amp with selector switch & CT 01 No (f) Indicator lamp LED type (R, Y, B) complete with bakelite fuse fitting - 01 Set(g)Cable entry gland and two no earthing terminal |
| 16 | S&F XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sq.mm with 4 Core complete all as specified and directed. |
| 17 | Description all as per item No. 16 above but of size 16 Sqmm 4 core complete all as specified and directed. |
| 18 | Description all as per item No. 16 above but of size 25 Sqmm 4 core complete. |
| 19 | Excavation in trenches not exceeding 1.5m wide and not exc 1.5m depth and getting out in any type of soil complete all as specified and as directed. |
| 20 | All as per item No. 19 above but exceeding 1.5 mtr but not exceeding 3 mtrs in depth complete. |
| 21 | Returning, filling, including spreading, leveling, watering and well ramming in layers not exc. 25cmin soft/loose soil complete all as specified and as directed. |
| 22 | Removal of excavated soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as directed. |
| 23 | M&L for sand cushioning in trenches for cable protection including consolidation complete all as directed. |
| 24 | S&F brickwork, old size sub class `B\" laid in trenches with width wise along the alignment of the cable as protection complete. |
| 25 | M&L PCC 1:2:4 type B1 (using 20mm graded stone aggregate) as in foundation forincluding necessary form work complete all as specified and directed. |
| 26 | Supply and Fix HT SFU of 11 KV LBSF panel outdoor complete with, 630A load break switch, 200 Amps D. O set, Earth switch, PVC sleeved, copper busbar for incoming, Door interlocking mechanism, Tripping Mechanism, Epoxy insulator for busbar supports, HV cable box provided, for end termination at incominng side, End plate provided at outgoing side for end termination etc Including taking out old unsv GOD mechanisum complete all as specified and directed.Note:- LBSF should be placed/grouted on brick masonary plateform of size 3.0x3.0x 1.2 mtr Height. The rates for construction to plateform are maesuered and paid separately under relevant of BOQ |
| 27 | M&L for construction transformer/LBSF plateform of size 3.0x3.0 mtr and hieght 1.2 mtr from normal ground level using brick masonary wall, PCC 1:4:8 type D2 using 40 mm graded stone aggregate in foundation and top of the plateform and plastering all visible surface by using 1:3 cement mortar, 15mm thick plaster all as specified and directed. |
| 28 | Supply, jointing, fixing or passing through pipe, trenches or ducts, commissioning and testingXLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (Heavy duty) with aluminium conductor, 11000 Volts grade, cross sectional area 95Sqmm, 3 core, suitable for 11 KV earthed system confirming to IS 7098 Part-2 for insulation and for conductors Class 2 to IS 8130-84, in trenches, floors, ducts passing through pipe for road crossing etc,including connecting & testing and disconnecting and taking down of old unserviceable HT cable complete all as specified and directed. (Note : Excavation, earth work, Cable cover, sand cushioning and GI pipe etc shall be measured &paid for separately). |
| 29 | Renewal ofcable jointing kit for 11 KV (Earthed) grade cable for outdoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cableof size 95sqmm including cutting and removing existing unserviceable joint, including earth work complete, all as specified and as directed. |
| 30 | M&Linspection, checking and repair of APFC panel by cleaning of dust inside with blower, cleaning of moving part/contract from CT cleaner, tightening of loose parts/electrical wiring , cleaning of contractors, relays and capacitor juction points, oiling of cooling fan , complete testing of APFC relay with necessary settings with CTs /load adjustments to match with the APFC load management systemcomplete with replacement of burnt/worn out unserviceable components /burnt wires thimbles /lugs etc for APFC panel capcity 50 KVAR to 150 KVAR completeall as specified and directed. Note : All unserviceable parts shall be measured and paid seprately as supply only. Replacment of small nuts/screws, wires lugs or thimbles and cleaning material cost included in this item. |
| 31 | SupplyonlyMCB, TP 6 to 32 Amp 10 KA C curve for existing APFC panel complete all as specified and directed. |
| 32 | SupplyonlyMCB, TP 40 to 63 Amp 10 KA C curve for existing APFC panel complete all as specified and directed. |
| 33 | Supplyonly Auxillary contractor 1 NO+1NC TP 415 volts suitable for 25 KVAR ratingfor existing APFC panel complete all as specified and directed. |
| 34 | Supplyonly Auxillary contractor 1 NO+1NC TP 415 volts suitable for 50 KVAR ratingfor existing APFC panel complete all as specified and directed. |
| 35 | Supplyonly capacitor 440 volts 50 Hz 15 KVARfor existing APFC panel complete all as specified and directed. |
| 36 | Supplyonly capacitor 440 volts 50 Hz 25 KVARfor existing APFC panel complete all as specified and directed. |
| 37 | Supplyonly capacitor 440 volts 50 Hz 50 KVARfor existing APFC panel complete all as specified and directed. |
| 38 | Supplyonly APFC relay square flush type with protection devices intelligent auto processor based on electronic controller unit 6 stagesfor existing APFC panel complete all as specified and directed. |
| 39 | Supplyonly APFC relay square flush type with protection devices intelligent auto processor based on electronic controller unit 8 stagesfor existing APFC panel complete all as specified and directed. |
| 40 | S&F draw ACSR Weasel conductor of size 06 strands of aluminium of 2.59 mm dia and 1 strand of steel of 2.59 mm dia on HT/LT poles, bringing the sag within limit fixing on Insulator/Cross arms by means of necessary binding with 16 SWG aluminium binding wire and providing alkathin pipe of approved quality for jumpers, reconnecting the service connections after removing the carbon material including taking down old UNSV, ACSR conductor of any size & type from LT poles at any height position and place complete all as specified and directed. |
| 41 | M&L for work confirming to Fe-410-O or Fe-310-O as in cross arms, support, bracings, stiffeners, clamps channels fabricated from structural steel including nuts, bolts and washers welding, bending cold or hot drilling holes for bolts in any shape or size all as directed including two coats of aluminium paint over a coating of red oxide primer including taking out old UNSV cross arms complete all as specified and directed. |
| 42 | Supply and fix in replacement of steel tubular swaged poles type 410 SP-31 (9 meter long), Including taking out old UNSV, RCC/Steel Pole complete all as specified and directed. |
| 43 | S&F pin type porcelain vitreous insulator 100 mm height and 65 mm dia for 1100 Volts grade including galvanised mild steel spindle, one nut and two washers & Including taking out old UNSV insulators complete all as specified. |
| 44 | S&F shackletype insulator porcelain vitreous white,brown and green of size 75 mm heaight and 90 mm dia incl galvanised MS straps 31x3 mm size ,washers,insulator bolt 12 mm dia and nut for working pressure 1100 Volts grade & Including taking out old UNSV insulators complete all as specified. |
| 45 | Material & Labour for stay asembly comprising of stay bow (4000 x 14mm), stay rod 215 cm long and 16 mm dia with nuts, stay plate 300 x 300 x 6 mm thick and 2 nos of thimble complete as shown in electric plate no 1 of SSR part-1 connected to loop type insulator, including dismantling old UNSV stay assembly complete.NOTE :- Earth work excavation, concrete and loop type insulator & Stay wire shall be measured and paid separetely under relevent items of Sch \"A\". |
| 46 | S&F LT loop type insulators, vitreous, porcelain brown, white or green insulators for working pressure of 1100 volts grade of Small size with over all dimensions 65 x 90 mm including dismantling of existing LT loop type insulator from LT poles of any height place and position complete all as specified and directed. |
| 47 | S&F galvanised stay wire stranded of size 7/4 mm including necessary binding, strengthening complete all as specified and directed. |
| 48 | M&L PCC 1:4:8 type D2 (using 40mm graded crushed trap stone aggregate) for foundation of poles/stays complete all as specified and directed. |
| 49 | M&L PCC 1:3:6 type C1 (using 20mm graded crushed trap stone aggregate) for coping of HT/LT poles, including necessary form work and finishing exposed surface of concrete even and smooth without using extra cement complete all as specified and directed. |
| 50 | M&L PCC 1:2:4 type B-2 (using 40 mm graded crushed stone aggregate) for making good the road cutting complete all as specified and directed. |
| 51 | M&L danger notice plate of 1.6 mm thick Mild Steel sheet vitreous enamelled white with letters figure and conventional skull & bones in signal red colour & fixed with MS clamps, bolt,nuts of approved size for LT 20 x 15 cm size including dismantling the old unserviceable one complete all as specified and directed. |
| 52 | M&L preparing old painted surfaces of steel tubular poles sewaged pole of any description and length not exc 7.5 above ground level erected in vertical position in LT OH line including cross arms of angle iron/ channel section clamps brackets etc with one coat of aluminium paint 6.0 mtr from top of the pole onward & remaining with black & Yellow paint strip in 30 cm width alternatively upto ground level& numbering the pole with white paint on black paint base 20 cm dia circular/square shape complete all as specified and directed. |
| 53 | Supplying, laying, testing or passing through pipe and commissioning of XLPE insulated screened PVC bedded galvanised steel strip or wire armured electric power cable(Heavy duty ) with aluminium conductor 1100 volts grade, including taking out old UNSV, UG cable of cross sectional area 120 Sqmm 3.5 Core complete all as specified. |
| 54 | Description all as per item No. 53 above but of size 95 Sqmm 3.5 core complete. |
| 55 | Description all as per item No. 53 above but of size 70 Sqmm 3.5 core complete. |
| 56 | Description all as per item No. 53 above but of size 50 Sqmm 3.5 core complete. |
| 57 | Description all as per item No. 53 above but of size 35 Sqmm 3.5 core complete. |
| 58 | Description all as per item No. 53 above but of size 25 Sqmm 4 core complete. |
| 59 | Description all as per item No. 53 above but of size 16 Sqmm 4 core complete. |
| 60 | Description all as per item No. 53 above but of size 10 Sqmm 4 core complete. |
| 61 | S&F tube \"medium\" grade galvanised Pipe of 40 mm dia with all fittingfor cable protection, laid in trenches, fixed to wall and floor by MS shaddle & fixed with pole, 02 position by MS clamp made of 40x5 mm MS flat, complete all as specified and directed. |
| 62 | Description all as per item No. 61 above but of size 50 mm dia. |
| 63 | Taking out old unsv indoor and outdoor feeder pillar box, junction box including dismantling PCC foundation, all elctrical and earthing connections complete all as specified and directed. |
| 64 | Supply, Installation and commissioning and testing of CPRI approved LT panel cubical type suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system,with canopy sloped top projected, floor mounted outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 2.8 mm thick CRCA sheet, internal cover and partition made out of 3.15 mm thick CRCA sheet with angle iton 50mm x 50mm x 6mm covered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 60 CM above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washers etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-Charge :-(a) MCCB 400 Amps, 25KA 4 pole-1 No (As Incomer) (b) MCCB 200A, 25KA 4 pole-1 No (c) MCCB 160A, 16KA 4 pole-2 No(d) Spare Pocket for Fixing MCCB (e) Aluminium busbar 200 Amps TPN- 04 Nos (02 set as incoming & outgoing) (f) Digital voltmeter 0-500 Volts with selecter switch - 01 Nos (g) Digital Amp Meter 0-500 Amp with selector switch & CT 01 No (h) Indicator lamp LED type (R, Y, B) complete with bakelite fuse fitting - 01 Set (j)Cable entry gland and two no earthing terminal |
| 65 | Supply, Installation and commissioning and testing of CPRI approved LT panel cubical type suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system,with canopy sloped top projected, floor mounted outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 2.8 mm thick CRCA sheet, internal cover and partition made out of 3.15 mm thick CRCA sheet with angle iton 50mm x 50mm x 6mm covered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 60 CM above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washers etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-Charge :-(a) MCCB 250 Amps, 25KA 4 pole-1 No (As Incomer) (b) MCCB100A, 16KA 4 pole-2 No (c) MCCB 125 A, 16KA 4 pole-2 No (d) Spare Pocket for Fixing MCCB (f) Aluminium busbar 200 Amps TPN- 04 Nos (02 set as incoming & outgoing)(e) Digital voltmeter 0-500 Volts with selecter switch - 01 Nos (f) Digital Amp Meter 0-500 Amp with selector switch & CT 01 No (g) Indicator lamp LED type (R, Y, B) complete with bakelite fuse fitting - 01 Set (h) Cable entry gland and two no earthing terminal |
| 66 | Supply & Fixing in replacement MCCB 4 pole 63 amps 50Hz 415 volts with reputing cap 16 KAcomplete all as specified and directed. |
| 67 | Supply & Fixing in replacement MCCB 4 pole 100 amps 50Hz 415 volts with reputing cap 16 KAcomplete all as specified and directed. |
| 68 | Supply & Fixing in replacement MCCB 4 pole 125 amps 50Hz 415 volts adjustable type with reputing cap 16 KA complete all as specified and directed. |
| 69 | Supply & Fixing in replacement MCCB 4 pole 160 amps 50Hz 415 volts adjustable type with reputing cap 25KA complete all as specified and directed. |
| 70 | Supply & Fixing in replacement MCCB 4 pole 200 amps 50Hz 415 volts adjustable type with reputing cap 25KA complete all as specified and directed. |
| 71 | Supply & Fixing in replacement MCCB 4 pole 250 amps 50Hz 415 volts adjustable type with reputing cap 36KAcomplete all as specified and directed. |
| 72 | Supply & Fixing in replacement MCCB 4 pole 400 amps 50Hz 415 volts adjustable type with reputing cap 36KA complete all as specified and directed. |
| 73 | Supply & fixing in replacement Aluminium thimbles for LT panels in cable and connecting upto with GI nut bolts and washers suitable for 25 Sqmm to 50 Sqmm cable size complete all as specified and directed. |
| 74 | Supply & fixing in replacement Aluminium thimbles for LT panels in cable and connecting upto with GI nut bolts and washers suitable for 70 Sqmm to 95 Sqmm cable size complete all as specified and directed. |
| 75 | Supply & fixing in replacement Aluminium thimbles for LT panels in cable and connecting upto with GI nut bolts and washers suitable for 120 Sqmm to 150 Sqmm cable size complete all as specified and directed. |
| 76 | M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) vertically, with top edge of plate not less than 1.5 metre below normal ground level connected to galvanised earth lead Strip 32x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 of MES Schedule Part-I connecting to earthing test. Testing on completion with and including necessary excavation and earth work in any type soil, earth lead connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded BT stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, internal surface of concrete shall be given 10mm thick plaster in CM 1:4, pre cast RCC (1:2:4)type B-1 (using 20mm graded BTstone aggregate) 40 mm thick cover, reinforced with 8mm dia deformed or TMT bars 3 Nos both way with 12 mm dia round bar handle, GI medium grade watering pipe 20 mm dia with funnel and wire mesh and 40 mm dia GI medium grade earth lead protection pipe upto 7.5 mtr length complete all as specified and directed. |