| 1 | Attending of complaints from 0800 hrs to 1800 hrs by deployingelectrician along with helpersfor checking of existing electrical items including carrying out repairs such as tightining of lose electric connections, nuts, bolts, screws, repair/replacement of switches, sockets, switch boards, tube rod, light fittings, Distribution Board,MCBs etc as required to make the item functional and to ensure contiunous electric supply complete as specified and directed. Note:(a) Replacement of electric fitting shall measured andpaid seperately under respective items (b) Rate quoted deemed to be inclusive of T&P etc. (c) The safteyand insurance of persons/helper engaged in Execution shall be responsibility of contractor. (d) As the Nos of complaints shall be on required basis the financial effect to this is deemed to be included in the rate quoted. |
| 2 | M&L for point wiring in repair with PVC insulated, unsheathed cable single core multistranded copper conductor FRLS cable 1.5 sqmm size, 1100V grade, drawn into and including PVC rigid concealed conduit medium grade (ISI marked) including PVC unsheathed cable single core copper FRLS conductor 1.5 Sqmm as continuous earth wire and including pressed MS sheet sunken box 1.6 mm thick with 3 mm thick laminated bakelite sheet all as specified. |
| 3 | a) One light / fan / call bell point controlled by one, one way switch. |
| 4 | b) Do all as per Ser item No -1 above but for 5 amps socket on independent board |
| 5 | c) Do all as per Ser item No- 1 above but for 5 amps socket on same board |
| 6 | Do all as per ser item No- 1 above but with 2.5 sq mm cable for 15 amps switch socket combination outlet on independent board complete all as specified and directed. |
| 7 | Supply & fixing in repair switch piano flush type single pole one way 5 Amps all as specified. |
| 8 | All as item 4 here-in-beforebut single pole 5 Amps two way all asspecified. |
| 9 | Supply & fixing in repair bell push single pole 5 Amps all as specified. |
| 10 | Supply & fixing in repair switch piano flush type single pole 15 Amps complete all as specified and directed. |
| 11 | Supply & fixing in repair socket outlet5 Amp flush type all as specified. |
| 12 | All as per item 8 here-in-before but 6 pin 5/15 Amps multi type complete all as specified and directed. |
| 13 | Supply & fixing in repair ceiling roses surfaces bakelite two three terminals 65 x 50 mm all as specified. |
| 14 | Supply & fixingin repair lamp holder PVC, insulated body with back plate suitable for batten fittings all as specified. |
| 15 | Supply & fixing in repair light fittingsdecorative LED lunminare for wall mounting multi colour ABS housing with ploycrabonate rings thermo set plastic lamp holder CITY 1 fitting for lampDécor along with 05 watt retrofit LED Spiral lamp complete all as specified and as directed. |
| 16 | Supply & fixing in repair regulator electronic switch type 5 steps suitable for 1200/1400 mm sweep 230 volts.complete all as specified and directed. |
| 17 | Supply & fixing in repair regulator electronic socket type 5 steps suitable for 1200/1400 mm sweep 230 volts . complete all as specified and directed. |
| 18 | Supply & fixing in repair bell electric (dingdong) 230 volt, SP. complete all as specified and directed. |
| 19 | Supply & Fixing in repair MCBsingle pole , 240 volts, 6 to 32 Amps in the existing DBs. make HPL of osafe ,legrand , 10 Kb curve confirming to osafe series of HPL /ACTI 9 SERIES OF schneider/ hager./L&T/ SIEMANScomplete all as specified and directed |
| 20 | -ditto- as per item no 17 but32 Amps SPN . complete all as specified and directed. |
| 21 | Supply & Fixing in repairDIistributionboard8 way complete with copper bush barfor netural and earth bar complete as specifiedmake ..... osafe series of HPL /ACTI 9 SERIES OF schneider/ hager./L&T/ SIEMANScomplete all as specified and directedin repair MCB DB SPN with 200 amps rated Bus Bar suitable for MCBs 8 way . complete all as specified and directed. |
| 22 | Supply & fixingin repair MCCB 3 pole of capacity 63 Amps with breaking capacity 16KA including all electrical connections and fixing arrangment all as specified and directed by Engineer -in-Charge. |
| 23 | S&F Factory made sheet metal enclosures double door type made out of CRCA 1.2 mm thick M.S. sheet, powder coated, partly embedded in wall, IP-43 protection, VTPN DB with 200 Amps rated bus bar, 4 way, 415 volts, vertical type, dust and vermin proof, suitable for incorporation of MCCBs/ MCBs, factory made, including thermal based release adjustable type 4 pole 63 Amps, 50 Hz, 415 Volts with rupturing capacity 16 KA and making good distrubbed surfaces with matching colour, complete all as specified. |
| 24 | S/F in repair MCB TPN 100 Amps415 volts complete all as specified and directed. |
| 25 | M & L for taking down existing T/L fitting 36/40 watt and change the connection suitable for LED Tube Rod including replacement of existing tube Rod with LED tube rod 18 watts & refixing the same all as directed . |
| 26 | S & F in repair surface mounted LED Batten with LED tube rod 2 Feet 10W internal surge protection device of 4 KV with voltage band 140-280V and making electrical connection to ceiling rose all as directed. |
| 27 | S&F new generation energy saving 50 Watt LED flood light, powder coated PDC aluminum body with toughened glass visor.Efficacy>100 Lm/w. Available 5700K IP66. complete all as specified and directed. |
| 28 | LED Tube light Fitting 20 watt use and throw type complete all as specified and directed. |
| 29 | Supply & Fixing LED Bulb 7 Watts. complete all as specified and directed. |
| 30 | Supply & Fixing LED Bulb 12 Watts. complete all as specified and directed. |
| 31 | Supply and fixing of new generation, post top, energy saving spun aluminium landscape luminaries with high power 25W suitable for Pole dia36mm complete all as specified and directed. |
| 32 | M & L for sub main wiring with 1100 volt grade two single core FRLS Wire PVC insulated and unsheathed cable with stranded copper conductor 6 sqmm drawn into and including electrical grade PVC conduit not less than 25 mm dia with IS 9537 (Part-III) 1983 mark, or relevant ISI mark with all accessories fixed concealed including chase cutting in brick/ stone masonry for fixing conduit and making good the disturb surfaces of wall as per existing including 6 sqmm multi - stranded copper conductor as earth wire in green colour complete all as specified and directed. Including taking down old unserviceable sub main wiring. complete all as specified and directed.Note : Tworuns of 6 sqmm PVC FRLS multi stranded copper cable wire and One run of 6 sqmm PVC FRLS multi stranded copper cable earth wire and One run (01 meter) PVC conduit of suitable size ISI mark will be measured and one unit length. |
| 33 | All as per ser item No. 29 above but for sub main wiring with 2 run of 4 sqmm & 1 run of 4 sqmm as earth wire |
| 34 | supply and fixing XLPE insulated, armoured heavy duty electric cable withaluminium conductor, 1100 volts grade, cross-sectional area insulated armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq. mm 3.5 core complete all as specified and directed. |
| 35 | Supply and fixing modular metal flush box 1/2 modular complete all as specified and directed. |
| 36 | Supply and fixing modular metal flush box 3 modular complete all as specified and directed. |
| 37 | Supply and fixing modular metal flush box4 modular complete all as specified and directed. |
| 38 | Supply and fixing modular metal flush box6 modular complete all as specified and directed. |
| 39 | Supply and fixing modular metal flush box12 modular complete all as specified and directed. |
| 40 | Supply and fixing modular white cover plate with frame ,1/2 modulecomplete all as specified and directed. |
| 41 | Supply and fixing modular white cover plate with frame ,3 modulecomplete all as specified and directed. |
| 42 | Supply and fixing modular white cover plate with frame ,4 modulecomplete all as specified and directed. |
| 43 | Supply and fixing modular white cover plate with frame ,6 modulecomplete all as specified and directed. |
| 44 | Supply and fixing modular white cover plate with frame 12 modulecomplete all as specified and directed. |
| 45 | Supply and fixing modular Dummy platecomplete all as specified and directed. |
| 46 | S & F in repair 34Watt 2 x 2 LED PLUTO NEO Ceiling light fitting utra moderndesigned, LED luminaire which provides soft-light and glare free symmetrical illumination suitable for armstrong/Grid Celing,including Bracket nuts, bolts washer as required for fixing. Cat Part No PLUTONEO2X2PLR34WLED840S . |
| 47 | Supply & fixingModular switch single pole one way 6 Amps all as specified. |
| 48 | Supply & fixingModular switch single pole 6 Amps two way all asspecified. |
| 49 | Supply & fixingModular bell push single pole 6 Amps all as specified. |
| 50 | Supply & fixing Modular switch single pole 16 Amps. complete all as specified and directed. |
| 51 | Supply & fixingModular multi socket 3 pin and 2 pin 6 Amp flush button type all as specified. |
| 52 | Supply & fixingModular socket outlet 6 pin 6/16 Amps multi type with shutter. |
| 53 | Supply & fixingModular regulator electronic 5 steps suitable for 1200/1400 mm sweep 230 volts |
| 54 | Supply & fixingModular regulator electronic socket type 5 steps suitable for 1200/1400 mm sweep 230 volts |
| 55 | M & L for earthing complete with galvanised earth plate electrode 600 X 600 X 6 mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.5 m below normal ground level, connected to galvanised earth lead wire 4 mm dia by means of nuts, bolts, check nuts & washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2009, Part – I (Specifications) and connected to main switch board / main DB’s / earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust & common salt all around the earth plate minimum 150 mm in all directions with & including watering pipe 20 mm dia GI medium grade, GI funnel made out of 0.63 mm thick GI sheet, wire gauge, 50 mm thick RCC cover in PCC 1:2:4, type B-1, duly reinforced with 6 mm dia mild steel round bars @ 150 mm both ways center to center with suitable lifting handle to cover, earth pit of PCC 1:3:6 type C-1, GI protection pipe light grade 15 mm bore up to 7.5 m length from earth electrode & engraving of earth marking on nearby building with CM 1:4 plate size 200 X 150 X 15 mm & painting of earth result etc. including testing on complete all as specified and directed. |
| 56 | Supply and fix in replacement of security light fitting LED 35 Watt withdusk and down sensor aluminum pressure dia cast housing with touched glass cover IP-66 protectionIncludingsuitable size GI Bracketand accessories complete mounted including connection with 3 core PVC insulated overall sheathed flexible cable with muyltistranded copper conductor of size not less than 1.0 sq mm from celing rose to fitting terminal including taking down old CFL security light fittingall as specified and as directed. |
| 57 | Supply/replacement of Microwave Sensor enabled Integral LED 4 ft luminaire with extruded housing and Opal diffuser ith ABS end caps. The luminaire should have a color consistency SDCM < 5, CRI > 80 and CCT of 6500K. The luminaire shall be compliant with IP20 classification. Luminaire shall be designed to emit at least 2000 nominal lumens at a system efficacy of at least 100 lumen/watt with a maximum system wattage of 20 Watts. Fixture should cover upto 5 mtr sensor radius coverage area with 120 degree angle after 17 to 30 seconds & 30% light output in case of non-occupancy.The electronic driver used shall have a power factor >0.9 and THD <10% and suitable for an operating voltage range of 140-270V AC. Manufacturer shall have in house lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Havells Cat no LUMILINESMART20WLED865PCWH equivalent in Signify/Wipro |
| 58 | supply and fixing PVC insulated armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sq. mm 4 core complete all as specified and directed. |
| 59 | supply and fixing PVC insulated armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sq. mm 4 core complete all as specified and directed. |