| 1 | Supply, Installation, Testing & Commissioning of \"silent type\" new Diesel Generator set of reputed make/ manufaturer having prime power rating of 20 KVA, 415 volt, 0.8 lagging power factor suitable for 50 HZ, 3 phase system (conforming to the norms of CPCB IV+ upto latest amendmend) comprising of 4 Stroke Liquid cooled Diesel Engine, electric start turbocharged developing of min. 25 BHP at 1500 RPM, capable of taking 10 % over loading for one hour after 12 hours of continous operation coupled with self excited and self regulated, Brush less, Synchronous alternator with H class insulation in SPDP enclosure rated at 20 KVA, 415 V at 1500 RPM, 3 phase 50 HZ, A.C supply with 0.8 lagging power factor, both the engine and alternator shall be mounted on a common MS base frame in Accoustic & wheather proof enclosure on suitable C.C foundation as per manufacturer drawing & design complete with Automatic mains failure control Panel (AMF) with suitable rating MCCBs including auto/ manual by-pass, battery charger, Micro-processor based Genset controllers with display for voltages & Currents, Frequency, Genset KVA, KW, KWh, KVAr, Power Factor, Lube oil pressure, Engine Temperature, RPM, Run Hours, Number of starts, Fuel Level, Auto / Manual Stop, Emergency Stop, Battery charge condition, advanced Digital AVR for improving voltage regulation & response time, Electronic Governor, Fuel tank, Residential type silencer, AVM pads fitted on base frame, First fill of lube oil, 12V DC starting system comprising of starter motors & 1 No. 12V battery including transportation, loading and unloading of the DG set. The entire set must be warranted least of 24 months / 5000 Hrs from the date of Commissioning whichever is earlier. The agency will have to fill full tank & provide permanently multi-core control cables as required with allied accessories including laying of the same before commissioning of the DG set and also including supplyingandfixingexhaustgaspipingof suitabledia.weldedblackMS,BClasspipe conformingtoIS:3589cuttorequiredlengths andinstalledwithnecessarybends,supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/Rockwool, 50mmthickwiremesh&aluminumcladding etc., The DG set should be of reputed brand and must be approved by the Engineer-in Charge and installed as per CPWD specifications. |
| 2 | Supply of XLPE Power cable of size 4x25 sq.mm of 1.1 KV grade armoured Al. Cable Compulsary ISI made Confirming to IS : 7098/ Pat -I / 88 with amendment no Iof reputed make as required. |
| 3 | Earthing with G.I earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.. |
| 4 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 5 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 6 | Providing PVC slieve on the 25 mm X 5 mm G.I. strip for neutral connection |
| 7 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.(a)Upto 35 sq. mm |
| 8 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.(a)Upto 35 sq. mm |
| 9 | Laying and fixing of one No. PVC insulated & PVC sheathed/XLPE al conductor cable of 1.1KV gradeof following size on the wall surface as reqd. |
| 10 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of size Upto 35 sq. mm in the existing RCC/ HUME/ METAL / HDPE pipe as required.(a)Upto 35 sq. mm |
| 11 | Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required. |
| 12 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulatedand PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required(a) 4x 25 sq mm(28 mm) |
| 13 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-Charge) of total coated thickness 0.50mm (base metal of minimum 0.45mm thickness withtotal coatin thickness of 0.05mm) with zinc coating 120 grams per sqm as per IS:277, in 20MPa steel grade ,5-7 microns epoxy primer on both side of the sheet and polyster top coat, 15-18 microns. Sheet should have protective guard film of 25micronsminimum to avoid scratches during transportation ans should be supplied in single length upto 12metre or as desired by Engineer -in- Charge. The sheet shall be fixed using self drilling/ self tapping screws of sixe 5.5x 55mm) with EPDM seal, complete upto any pitch in horizontal/vertical or curved surfaces excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required |
| 14 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 15 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture. |
| 16 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil |
| 17 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering- All work upto pllinth level:1:2:4 (1 cement 2 coarsesand (zone III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 18 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering- All work upto pllinth level:1:1.5:3 (1 cement : 1.5 coarse sand (zone-III derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources |