| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | Wiring for Light /Power Plug with 2 x 4 sq.mm FRLS PVC Insulated Copper Conductor single core cable in surface/Recessed medium class PVC Conduit along with 1 No. 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop earthing as required. |
| 4 | Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required. |
| 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 7 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 8 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 9 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 10 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 11 | Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required |
| 12 | Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 15/16amps modular socket outlet and 15/16 amps modular switch,connection,painting etc. as required. |
| 13 | Supplying and fixing 32A DP Switch with indicator on surface/ recess complete with connections, testing and commissioning etc. as required. |
| 14 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 15 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 16 | 12 way , Double door |
| 17 | 8 way , Double door |
| 18 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 19 | 12 way (4 + 36), Double door |
| 20 | 8way (4 +24), Double door |
| 21 | Supplying and Fixing of Following Ratings of D.P MCB 240 Volts \"C\" Series in the Existing MCB D.B complete with connections,Testing and Commissioning Etc. as Required. |
| 22 | 63 A D.P MCB 10 Ka \"C\" Curve |
| 23 | 40A D.P MCB 10 Ka \"C\" Curve |
| 24 | 32 A D.P MCB 10 Ka \"C\" Curve |
| 25 | 16 A D.P MCB 10 Ka \"C\" Curve |
| 26 | Supplying and fixing following rating, Four pole, 415 V, 10 Ka M.C.B in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 27 | 40 A F.P MCB 10 Ka \"C\" Curve |
| 28 | 63 A F.P MCB 10 Ka \"C\" Curve |
| 29 | Supplying and fixing 5 amps. to 32 amps.rating240 volts \"C\" series, miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 30 | Single Pole |
| 31 | Supply and Fixing Single Pole Blanking Plate in the Existing MCB DB complete as Required. |
| 32 | Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value. Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. Earth pit chamber (300mm x 300mm) with CI cover for the above. |
| 33 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nutbolt & spring washer spaced at 50mm) |
| 34 | Supply installation testing and commissioning ofCeiling Fan 3 Star Rated with Voltage Range 90 V to 300 V,Min. Air Delivery 212 CMM,Service Value 5.3 Cu.m/min/watt,Aluminium Blades ,including wiring the down rods of standard length(Upto 45 cm)with 1.5 sq.mm FR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. |
| 35 | Supply installation testing and commissioning of IP20 led downlighter 12 W +/- 1 WLEDRecess downlighter round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved Inhouse NABL lab/ government of India authorised lab. |
| 36 | Supply installation testing and commissioning of IP65 led Street Light 90 W +/- 5 Wcomplete with M.S/G.I Pipe(Duly Bracket embedded along with Parapet/Wall including complete connections as required .The P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80. The LED with Useful life of 50000 Hrs at L70. The Input voltage range shall be 150V to 265V. The Fixture should have In-built Surge Protection of 2.5kV Certification:- LM79 & LM80 test report should be from govt approved Inhouse NABL lab/ government of India authorised lab . |
| 37 | Supply & Fixing of 36W ,2x2 LED reccesse typeLuminaire suitable for operating Voltage range of 150V-270V with inbuilt surge protection of 2KV and Color temprature 5700K ANSI BIN . Minimum system lumens 4320and systemefficacy >120 Lm/watt (Supported by in house NABL approved report ofLM79 provided by OEM and duly signed by company manager not below rank of RM) . Luminaire should be suitable for armstrong /grid ceiling mounting with help of 4 Nos clips for suspension. Body made up of CRCA powder coatedwith Diffused Optics. Luminaire size should not be less than 595x595x60mm and power factor >=0.95, CRI>=80, THD<10%, Max systemwattage should be 36 Watt, IP-20 ingress protection. NABL certification and BIS (both luminaire and driver) requried to be provided at the time ofsample approval. |
| 38 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 39 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 40 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 41 | SITC of Dry Type Co2 Type Fire Extinguisher 4.5 Kg |
| 42 | SITC of ABC Type Fire Extinguisher IS 15683 4.0 KgHaving Deep drawn and CO2MIG welded can construction ,Epoxy polyester powder external coating,Epoxy powder internal coating,Body Thickness 1.6 mm(Cease fire) |
| 43 | Supplying,Installation,Testing and Commissioning of Cubical Type Main Distribution Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking ,Synchronising etc. as required as per the Following Description.(IP:42)INCOMERAdj. TMR Based MCCB 400 Amps FP Icu=Ics=100%Breaking Capacity 36 KA with Extendable ROH (01 Nos)Digital Metering Devices,comprising Voltmeter,Ammeter,Selector Switch,Indicating Lamps,C.T Set,Bus Bar( 400 Amps ) and MCB Strip of suitable size as Required.OUTGOINGSF.P M.CCB 250 A 50 KA \" C\" Curve(02 Nos)F.P M.CC .B 160 A 36 KA\" C\" Curve(02 Nos)D.P M.C.B 32 A 10 KA\" C\" Curve(04 Nos)Load Bearing Members to be made out of 2.0 mm CRCA Sheet.Partitions to be made out of 1.6 mm CRCA SheetBy pass changeover 200 A = 1 NoGland Plates to be 3.0 mm Thick.The Complete Panel Shall be Made out of 2.0mm CRCA sheet including Frame/Partitions/Doors etc. |
| 44 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 45 | 200 mm dia (OD-200 mm & ID-175 mm nominal) |
| 46 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in groundin Existing DWC Pipe including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 47 | 3.5 C X 300 Sq.mm A2XFY |
| 48 | Supply and Making end Termination with Brass Compression Gland and Aluminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required (Comet) |
| 49 | 3½ X 300 sq. mm (70mm) |
| 50 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 51 | Telephone socket outlet |
| 52 | Computer Socket RJ45 Modular type |
| 53 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 54 | 1 or 2 Module (75mmX75mm) |
| 55 | Supplying and Fixing of Following sizes of PVC Conduit along with Accessories in surface/Recess including painting in case of surface conduit,cutting the wall and making good the same in case of recessed conduit as required. |
| 56 | 20 mm PVC Conduit |
| 57 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 58 | 2 Pair |
| 59 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 60 | 1 run of cable |
| 61 | Supply&Erectionoflockable12 Urackwith5Astripand twofanfordistribution,mountingofpatchpanels,hubs, switches etc,, complete as per specification and as desired by EIC. |
| 62 | Supply, Installation, Testing & Commissioning of 5MP IP Network TDN Low-Light IR Fixed Lens Dome Camera, 1/2.8\" CMOS or better, 5MP (2592 x 1944) @ 25fps or better, triple stream at various resolution & Frame Rates, Min. Illumination required 0.007 lux (color), 0 Lux IR On, 2 IR LEDs, Smart IR with upto 50m IR distance, Auto ICR (Infrared Cut Filter) 120dB True WDR, S/N Ratio 50db, Shutter Speed 1/8 - 1/30,000; Adavance Video Compression technology such as H.265, H.264 & MJPEG , Fixed Lens 2.8mm, Field of View FoV H:90°, V:62°, BLC, HLC, WDR, 3DNR, White Balance - Auto/Manual, Minimum Edge Intelligence Video Analytics : Video Motion Detection, Tampering, Loitering, Intrusion,& People Counting, 4 Privacy Mask, 8 Region Of Intreset, Defog, HTTPS, IP Filter, TLS1.2, AES-128/256, SSH/Telnet closed, Stream Encryption, 2-Way Audio Full Duplex Line IN/Out, 256GB SD card support, Alarm: 1In/1out,PoE (802.3 af) and 12V DC, Max 5W, IP 66/67 & IK10 with Die Cast Aluminium Housing, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S/G/TCompliant, UL/CSA, CE, FCC, EN, RoHS & NDAA Section 889 compliant. |
| 63 | Supplying and Laying of 20 Mtr HDMI Optical Fiber Cable AOC 2.0, 4K with Bandwidth 18Gbps |
| 64 | Supplying and Fixing of S.D Card 256 G.B in the Existing Camera |
| 65 | Supply&ErectionofCAT6,24port Jackpanel for terminationofCAT6cable,Testing&certificationofthe network with Omni/Penta Scanner of each Cable. |
| 66 | Supply & Erection of Cat-6, 1Mtr Patch Cordscomplete as per specification and as desired by EIC. |
| 67 | Supply & Erection of Cat-6, 3 Mtr Patch Cordscomplete as per specification and as desired by EIC. |
| 68 | Supply, installation, testing and commissioning of Junction Boxes/DB-20 Pairs with Original Krone module and Back Mount Frame and have Lock -n- key, complete in all respect as per specification and desired by EIC |
| 69 | Supply, Installation, Testing and Commissioningof 10/100/1000 Mbps Unmanaged Switches with Provision of 24 10/100/1000 Mbps ports as per specification and as desired by the Engineer Incharge. |
| 70 | Supply,Installation,Testing and Commissioning of Media Converter. |
| 71 | Supply & Erection ofTermination Box complete as per specification and as desired by EIC. |
| 72 | Supplying,Installation,Testing and Commissioning of 55 Inches Ultra HD 4K LED Display Monitor with 3840 x 2160 pixels (Min.) |
| 73 | Supply , Installation , Testing and commissioning of 24 Channel NVR (Network Vedio Recorder) Embadded Linux based for recording upto 24CH @ D1 with 02 nos. SATA HDDs minimum 20TB storage or more (recording requirement all cameras recording at D1, 25fps for 30 days), H.265 HEVC/H.264/MJPEG codec decoding, Front Control Pannel with LEDs Indication, 2 nos. USB, ONVIF S, Time Sync with NTP, Encrypted Streaming & Control, 2-Way Audio Line & Out, PTZ Operation Pan, Tilt, Zoom, Support, Pre & Post Alarm Recording Support, Recording/Evidance Clip Export to USB, 16 Channel Syncronous Playback, Playback control i.e Play, Pause, Stop, Fast Forward, Backward, Timeline & Zoom; Snapshot, Web Client, Central Monitoring Softawre, iPhone; iPad; Android based Mobile clients, 01HDMI & 01VGA Output, 02 On Board HDDS each up to 10TB, Alarm Input (1 nos.), Alarm Output (01 nos.), NDAA Section 889 Compliant, Operating Temperature –10°C to 55°C, Certification : Certifications: ONVIF compliant, UL/CSA, CE, FCC, EN, NDAA & RoHS compliant.including fixing accessories and cable termination with required connectors/Jack, complete in all respect as per instruction of engineer in-charge. |
| 74 | SITC of 10TB 7200 rpm SATA 6 Gb/s 3.5\" Internal Enterprise Hard Drive |
| 75 | Fire Detection |
| 76 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 77 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 78 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 79 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
| 80 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 81 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required |
| 82 | 2 x 1.5 sq. mm |
| 83 | Supplying of Steel tabular poles as per 410 SP 55 with base plate of size 300x300 x 6 mm , FAT before installation work is necessary along with test certificates and Purchase GST invoice. |
| 84 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 4 mm nominal size) foundation including excavation and refilling etc. as required. |
| 85 | Above 10.00 metre and upto 12.00 metre |
| 86 | Supply and laying of ACSR Dog conductor 0.1 with jumpering and termination works. |
| 87 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre)V shape cross arm for two 11 KV over head line conductors complete with 50 mm X 6mm M.S. flat iron clamps,bolts and nuts including drilling holes for insulator pins, bolts, F-top,nuts and washers etc (as per drawing) and painting with primer and finish paint as required. |
| 88 | Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required. |
| 89 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt,spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 90 | Spike type Earthing rods, 2.5m long |
| 91 | 11 kv PG clamps |
| 92 | Supply and painting of each Pole 1 coat red oxide paint and 2 coats of aluminium paint (@ 1 ltr/pole red oxide paint and 1 ltr/pole aluminium paint) |
| 93 | Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. asrequired. |
| 94 | Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required. |
| 95 | Excavation for foundation in soft soil including dressing of sides and cum ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as direted, within a lead of 50 metres.(12x9x1.5ft) |
| 96 | Providing and laying in position cement concrete 1 :2:4 (1 cement : 2 cum coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of dtSset etc including form work etc as required. (9x9x9ft X2 No) |
| 97 | Centering and shuttering including strutting , propping etc and removal of foam for foundation footing bases of column etc for mass concrete. 2(14+14 ft) x7 ft) |
| 98 | Excavating earth rubbish by mechanical transport upto a lead of 5 km and disposal of rubbish |
| 99 | 12mm cement plaster of mix 1:6 sides of concrete foundation for transformer 49x5x2sft |
| 100 | Dismantling of existing 250 KVA DTs and shifting to plaatform by way of Hydra/Crane etc . With Installation works |
| 101 | GI Ch iron 75x40x6mm x 10ft |
| 102 | 33 kV link set Heavy duty complete with all accessories ISI standard Heavy duty 600 Amp |
| 103 | 11kV lightening arrester setHeavy duty complete with all accessories ISI standard Station type |
| 104 | 11kV drop out set Heavy duty complete with all accessories ISI standard |
| 105 | Muky claps /J hook , galvanized nuts and bolts as requiredfor all items included . Complete job for entire work |
| 106 | S/l of Guy with turn buckler and Guy insulator etc, 8 SWg twisted GI wire laid in cement concrete . Complete job in all respects. |
| 107 | S/L ofCable 3.5 core 240 Sq mm Al armouredwith termination works etc |
| 108 | S/L ofCable 3.5 core 185 Sq mm Al armouredwith termination works etc |
| 109 | Supply and laying of folowing size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground 75mm below level including excavation and refilling thetrench but excluding sand cushioning and protective covering etc, complete as required. |
| 110 | 120 mm dianominal) |
| 111 | Fabrication, supply, installation, testing & commissioning of outdoor type compartmentalized feeder pillar having front area not less than 0.60 Sqmtr (900 mm x 750 mm) and depth 45 Cm (NS)made out of 2mm thick CRCA sheet with tappered roof having separate cable and bus bar alley, 1 door arrangement i/c locking arrangement, having 400 Amp four polealuminium bus bar of full length with base frame made out of50mmx50mmx6mm (thick)angle iron having 80cm legs for erection in ground with construction of cement concretesuitable foundationsizecomplete with connections and interconnections with copper conductor PVC insulated cables/ insulated aluminium busbar strips of appropriate size and terminal blocks (on outgoing) including supplying & fixing following switchgears & accessories there in, powder coating, labelling, earthing etc. complete as required. Providing and fixing following accessories in existing cubical panel board i/c making connection etc. as reqd. For 250 KVA Sub stationwith 1000 A Bus Bar Al 4 Strip.Details as underPanel Powder Coated 2.0mm MCCB400 A 4P 36kA , 1 No.handle extender typeDigital V,A,F, PF Meter Class 1.0 L&T 2 No.CT 600/5 AE 2 SetSpreader Terminals For DU MCCB 1 Set , , Panel Accessories like nut bolts, locks, etc |
| 112 | Fabrication, supply, installation, testing & commissioning of outdoor type compartmentalized feeder pillar having front area not less than 0.60 Sqmtr (900 mm x 750 mm) and depth 45 Cm (NS)made out of 2mm thick CRCA sheet with tappered roof having separate cable and bus bar alley, 1 door arrangement i/c locking arrangement, having 400 Amp four polealuminium bus bar of full length with base frame made out of50mmx50mmx6mm (thick)angle iron having 80cm legs for erection in ground with construction of cement concretesuitable foundationsizecomplete with connections and interconnections with copper conductor PVC insulated cables/ insulated aluminium busbar strips of appropriate size and terminal blocks (on outgoing) including supplying & fixing following switchgears & accessories there in, powder coating, labelling, earthing etc. complete as required. Providing and fixing following accessories in existing cubical panel board i/c making connection etc. as reqd. For 250 KVA Sub stationwith 1000 A Bus Bar Al 4 Strip.Details as underPanel Powder Coated 2.0mm MCCB630 A 4P 36kA , 1 No.handle extender typeDigital V,A,F, PF Meter Class 1.0 L&T 2 No.CT 600/5 AE 2 SetSpreader Terminals For DU MCCB 1 Set , , Panel Accessories like nut bolts, locks, etc |
| 113 | Note:-The rates quoted are inclusive of all carriages of materials (Mechanical/Manual) from source to site workand all extra charges including dewatering if any during the execution of work till complete in all respects. |