| 1 | Sub head - Chimney partSupply, Installation, Testing and Commissioning of customized SS ExhaustHood fabricated in SS304,20 SWGsheet, welded body construction having following size with baffle filters complete with installation etc. as required.(a) 60 inch x 24 inch x 22 inch |
| 2 | (b) 39 inch x 30 inch x 12 inch |
| 3 | Supply, Installation, Testing and Commissioning of the Backward Curved Direct Driven Centrifugal Blower,having air volume capacity 4000 CFM with minimum 60 mm static pressure i/c with 3 HP, 3 Phase, 415 V, 1440 RPM Direct Drive AC Motor ( ABB/Crompton Make) with suitable size GI cabinet box ( Heat insulation type), Bird Screen Netting inlet and Fire proof Canvas Cloth Connection at outlet including making foundation with Cement, Sand, Iron Rods, Hiring Chain pulley/Labours for Fan Cabinet Installation at required place etc. complete as required. |
| 4 | Supply, Installation, Testing and Commissioning of Axial flow Fan of 600 mm dia having air volume capacity 6000 CFM with minimum 15 mm static pressure with high affiance acro-foil section 11 blade directly driven by 1 HP, 1440 RPM. 3 Phase, 415 V, AC Motor ( ABB/Crompton Make) with suitable size GI cabinet box ( Heat insulation type), Bird Screen Netting inlet and Fire proof Canvas Cloth Connection at outlet including making foundation with Cement, Sand, Iron Rods, hiring Chain pulley/Labours for Fan Cabinet Installation at required place etc. complete as required. |
| 5 | Sub head - Ducting partSupplying, Installation, Balancing and Commissioning of factory fabricated GI Sheets 22 SWG metal rectangular/round ducting duly painted with an approved shade and complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, fresh air grills, hangers, supports etc as per approved drawings and specification complete as required. |
| 6 | Supply,installation, testing and commissioning of 3 phase 415 V DOL Starter of L&T Model no. 3 Pol MK1 etc. as required. |
| 7 | Gas Pipe line part Supply and fixing of 1+1=2 no\"s cylinder manifold with all fitting such as 1” heavy MS pipe ,adopter’ nrv, cpt, clamp , socket etc complete as required. |
| 8 | Supply and fixing of ½” LPG pipe line with ½” heavy MS pipe, clamp, socket, union set ,elbow, paint, Labour etc complete as required. |
| 9 | Supply and fixing of Burner Point with NCV ,hose etc complete as required. |
| 10 | Supply and fixing of 1st stage regulator station 20psi with fitting etc complete as required. |
| 11 | Sub head : MCB DB & WiringSupplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 12 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc as required.i) 40 Amp |
| 13 | ii) 63 Amp |
| 14 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.(a) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 15 | (b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 16 | (c ) 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |