| 1 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core all as specified and directed by Engineer-in-Charge. |
| 2 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core all as specified and directed by Engineer-in-Charge. |
| 3 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core all as specified and directed by Engineer-in-Charge. |
| 4 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core all as specified and directed by Engineer-in-Charge. |
| 5 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core all as specified and directed by Engineer-in-Charge. |
| 6 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core all as specified and directed by Engineer-in-Charge. |
| 7 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core all as specified and directed by Engineer-in-Charge. |
| 8 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 mtrin depthfor laying of cables, erection of poles, struts/stays, leveling of yard etc not exceeding 10 M² on plan and not exceeding 1.5 mtr in depth and getting out in soft/loose soil. |
| 9 | Material and labour for sand cushioning to underground cable screened tibba sand including watering and consolidation complete all as specified and as directed. Note :- Only punned thickness shall be measured for payment purpose. |
| 10 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type I, flat, size 250 mm x 150mm x 40mm complete laid over the cable perpendicular to the cable for protection complete all as specified and as directed. |
| 11 | Returning, filling in, including spreading, leveling watering and well ramming in layers n.exc 25 cm in soil. |
| 12 | Removing of excavated soilnot exc. 50 M from startingpoints all as directed by EIC. |
| 13 | M&L for Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 32 x 6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in Electrical Plate No 3 of MES Sch. part I and testing on completion including necessary excavation and earthwork, expansive soil, adequate common salt, charcoal dust and funnel, PCC(1:3:6) type C-1 pit with precast RCC(1:1.5:3) type A-I cover, 40mm thick reinforced with 6 mm dia MS bars 3 Nos both ways with lifting hooks made out of 6mm dia MS bars, watering arrangement with funnel, wire mesh, with 20mm dia GI medium grade watering pipe earthing lead from earth plate to equipment earth point complete all as specified. |
| 14 | Dismantling of unserviceableACSR conductor of any type and size from existing poles at various location all as directed by Engr - in - charge at site. |
| 15 | Dismantling of cross arms (Clamp, nut bolts ),care fully fromsite complete all as specified and directed byEngr-in-charge. |
| 16 | Dismantling ofinsulators any type any size from existing poles all as directed. |
| 17 | Taking out serviceable LT cable of any type and size for re-use and relaying in ground/along wall at site as directed . Note : Earth work, sand & PCC covers/stone slab shall be measured and paid separately. |
| 18 | Supply and fix security light junction boxes of dimension 240×130×110mm, with shockproof, rustproof, termite resistant, weather proof, cable entry from bottom , pole mounting arrangement along with 3 phase 4 wire almunium busbar with insulators and MCB SP-0.5 amps ratingwith provision of MCB, Cable Glands, lugs incl three core copper cable with pvc conduit from junction box to existing LED fitting. |
| 19 | Supply and fix copper cable 1100 volts gradePVC insulated and PVC sheathed wheather proof multistranded of size 3 Core x 1.5 sqmm complete all as specified and directed by EIC. |
| 20 | M & L for rigid non-metallic PVC conduit exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows. Reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipehooks, MS clamps for fixing with pole etc of size 20 mm dia complete all as directed by EIC. |
| 21 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, aluminium conductor cable of size 25 sqmm complete as specified and as directed by EIC. |
| 22 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, aluminium conductor cable of size 50 to 95 sqmm complete as specified and as directed by EIC. |
| 23 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, aluminium conductor cable of size 120 to 150 sqmm complete as specified and as directed by EIC. |
| 24 | Supply and fix cable jointing kit for 1.1 KV grade cable for End joint outdoor type complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, aluminium conductor cable of size 150 sqmm complete as specified and as directed by EIC. |
| 25 | All as item no 24 above but size of cable 120 sqmm 3.5 core |
| 26 | All as item no 24 above but size of cable 95 sqmm 3.5 core |
| 27 | All as item no 24 above but size of cable 70 sqmm 3.5 core |
| 28 | All as item no 24 above but size of cable 50 sqmm 3.5 core |
| 29 | Supply and fix cable path indicators made out of thick roughly hammer dressed stone slab size (30cm x 75cm x 7.5cm ) with applying two coats of paint, marking of voltage and size of cable, route including necessary earth work required complete all as specified and directed by Engr-in-charge. |
| 30 | Excavation in trenches not exceeding 1.5 m wide and exceeding 1.5 min depthfor, erection of poles and not exceeding 3 m in depth and getting out in hard rock complete all as directed by EIC.Note:- Hard rock meet during the excavation shall become property of contractor and recovery @ Rs 800/cum shall be made from the contractors from his RAR. |
| 31 | Supply and fix Prestressed concrete poles of 9 meter long having 102 mm x 172 mm at top and 102 mm x 279 mm at bottom class 10 complete all as specified and directed by Engr-in-Charge. |
| 32 | Material and labour Cement concrete (1:2:4) type B -1 using 20 mm graded stone aggregatefor pedestal of poles/copping including necessary frame work ,fair finishing to exposed surfaces using extra cement complete form, all as directed by EIC. |
| 33 | Material and labour for Cement concrete (1:3:6) type C -2 using 40 mm graded stone aggregate for foundation of pole /struts/stayassembly etc complete all as directed by EIC. |
| 34 | Supply and fix bracket for fixing street light fitting made out of GI pipe medium grade 32 mm 1.5 M long along with necessary accessories with two coat of aluminium painted MS clamps,nuts, bolts, and washers etc complete as directed. |
| 35 | Supply and fix of smart LED Street light with PDC housing, IP66 and IR sense based auto ON/OFFof capacity 60 Watts complete. |
| 36 | Motorized Auguring/drilling in road at 60 cm depth of dia suitable for laying of 40/50/80mm dia GI tubing pipe complete all as directed. |
| 37 | M&L for GI tubing light grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall and under road crossing including clamps, nuts bolts etc all as specified and directed of following sizes:- |
| 38 | (a) 40mm dia |
| 39 | (b) 50mm dia |
| 40 | (c) 80mm dia |
| 41 | Supply and fix street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer. The digital timer switch along with suitable power contactors, MCBs in incoming and outgoing side, copper short links in contactors, PVC insulators for incoming and outgoing circuit for support, copper cable of 16 Sqmm for incoming and outgoing 40 amps MCBs and02 Nos support terminals to support the timer box on pole and wall, including suitable lugs and cable glands, enclosure made of rust proof, electric shock proof, termite proof andjunction box conforming to IP 65. suitable for three phase . |
| 42 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 400 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 43 | (A) IN COMING |
| 44 | (a) MCCB 4 Pole 415 Volts 35 KA 250 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 45 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 46 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No. |
| 47 | (B) OUT GOING |
| 48 | (a) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -02 No |
| 49 | (b) MCCB 4 Pole 415 Volts 35 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 50 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 400 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 51 | (A) IN COMING |
| 52 | (a) MCCB 4 Pole 415 Volts 35 KA 250 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 53 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 54 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No. |
| 55 | (B) OUT GOING |
| 56 | (a) (a) MCB TPN 415 Volts 63 Amp rating-02 Nos |
| 57 | (b) MCCB 4 Pole 415 Volts 35 KA 200 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 58 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 300 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 59 | (A) IN COMING |
| 60 | (a) MCCB 4 Pole 415 Volts 35 KA 200 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 61 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 62 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No L&T/Siemens. |
| 63 | (B) OUT GOING |
| 64 | (a) (a) MCB TPN 415 Volts 63 Amp rating-02 Nos |
| 65 | (b) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magneticadjustable release type(Icu=Ics=100%) -01 No |
| 66 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 150 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 67 | (A) IN COMING |
| 68 | (a) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 69 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 70 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No L&T/Siemens. |
| 71 | (B) OUT GOING |
| 72 | (a) (a) MCB TPN 415 Volts 40 Amp rating-03 Nos |
| 73 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 400 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 74 | (A) IN COMING |
| 75 | (a) MCCB 4 Pole 415 Volts 35 KA 250 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 76 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 77 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No. |
| 78 | (B) OUT GOING |
| 79 | (a) (a) MCB TPN 415 Volts 40 Amp rating-03 Nos |
| 80 | (b) MCCB 4 Pole 415 Volts 35 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 81 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 250 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 82 | (A) IN COMING |
| 83 | (a) MCCB 4 Pole 415 Volts 25 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 84 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 85 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No |
| 86 | (B) OUT GOING |
| 87 | (a) MCB TPN 415 Volts 40 Amp rating-03 Nos |
| 88 | (b) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magneticadjustable release type(Icu=Ics=100%) -01 No |
| 89 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 400 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 90 | (A) IN COMING |
| 91 | (a) MCCB 4 Pole 415 Volts 35 KA 250 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 92 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 93 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No. |
| 94 | (B) OUT GOING |
| 95 | (a) (a) MCB TPN 415 Volts 40 Amp rating-04 Nos |
| 96 | (b) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -02 No |
| 97 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 250 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 98 | (A) IN COMING |
| 99 | (a) MCCB 4 Pole 415 Volts 35 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 100 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 101 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No |
| 102 | (B) OUT GOING |
| 103 | (a) MCB TPN 415 Volts 63 Amp rating-04 Nos |
| 104 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 500 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 105 | (A) IN COMING |
| 106 | (a) MCCB 4 Pole 415 Volts 35 KA 320 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 107 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 108 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No. |
| 109 | (B) OUT GOING |
| 110 | (a) (a) MCB TPN 415 Volts 40 Amp rating-06 Nos |
| 111 | (b) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 112 | (b) MCCB 4 Pole 415 Volts 35 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 113 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 160 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 114 | (A) IN COMING |
| 115 | (a) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 116 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 117 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No |
| 118 | (B) OUT GOING |
| 119 | (a) MCB TPN 415 Volts 40 Amp rating-04 Nos |
| 120 | Supply,install,testing and commissioning of LT Panel board, outdoor type, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply systemhaving bus bars chamber with copper bus bars of rating 250 amps duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheettotally enclosed dust, vermin and rust prooffront operated, front and rear opening with locking arrangement fixed with MSangle iron frame of size 40X40X5 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable sizeincllugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- |
| 121 | (A) IN COMING |
| 122 | (a) MCCB 4 Pole 415 Volts 35 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 123 | (b) RYB indicating lamp LED type suitable for panel mounting(Set of three) - 01 No. |
| 124 | (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No |
| 125 | (B) OUT GOING |
| 126 | (a) MCB TPN 415 Volts 40 Amp rating-06 Nos |