| 1 | Taking out old unsvLT under ground cable of any size and description from trenches / floor / road / wall / pipe / pole of any size and description incl joint complete all as directed by Engr-in-Charge. |
| 2 | S&F in replacement of XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional area 6.0 sq mm 4.0 core, laid in trenches/ducts /encased in GI pipe /fixed to pole complete all as specified and directed by Engineer-in-Charge. |
| 3 | All as per item No. 2.00 here-in-above, but cross sectional area 10 sq mm 4.0 core. |
| 4 | All as per item No. 2.00 here-in-above, but cross sectional area 16 sq mm 4.0 core. |
| 5 | All as per item No. 2.00 here-in-above, but cross sectional area 25 sq mm 3.50 core. |
| 6 | All as per item No. 2.00 here-in-above, but cross sectional area 35 sq mm 3.50 core. |
| 7 | All as per item No. 2.00 here-in-above, but cross sectional area 50 sq mm 3.50 core. |
| 8 | All as per item No. 2.00 here-in-above, but cross sectional area 75 sq mm 3.50 core. |
| 9 | All as per item No. 2.00 here-in-above, but cross sectional area 95 sq mm 3.50 core. |
| 10 | All as per item No. 2.00 here-in-above, but cross sectional area 120 sq mm 3.50 core. |
| 11 | Supplying and laying in Material and Labour for GI tubing light grade in repairs incl. accessories for protection of cables on poles / under road crossingof sizes 80 mm bore, complete all as specified and directed. |
| 12 | All as per item No. 12.00 here-in-above, but sizes 50 mm bore |
| 13 | All as per item No. 12.00 here-in-above, but sizes 40 mm bore |
| 14 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 min depthfor laying of cables, erection of poles, struts/stays, leveling of yard etc not exceeding 10 M² on plan and not exceeding 1.5 m in depth and getting out in soft/loose soil, complete all as specified and directed. |
| 15 | Excavation in trenches not exceeding 1.5 m wide and exceeding 1.5 min depth upto 3.0 m for erection of poles, struts/stays, leveling of yard etc not exceeding 10 M² on plan and getting out in hard/dense soil, complete all as specified and directed. |
| 16 | M&L for dry clean tibba sand as in sand cushioning to underground cable including punning down ofsand layer, complete all as specified and as directed. Note :- Punnedthickness shall only be measured and paid. |
| 17 | Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1, flat size 250 mm x 150 mm x 40 mmand abutting each other with gap between adjacent precast concrete cable cover not exceeding 10 mm over underground cables for protection, complete all as specified and as directed. |
| 18 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick in soils complete all as specified and directed. |
| 19 | Removal of excavated material soil to a distancenot exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed. |
| 20 | M&L for Auguring/ Driling /Boring of holes under road, pavement, hard standing by trenchless technology by mannual /machine, including fixing of HDPE pipe of 100 mmbore dia, complete all as specified and directed. |
| 21 | Re-routing/relaying of existing LT cable PVC/XLPE insulated aluminium conductor armoured with glavanised steel wire complete of any size and core from any position i.eground /wall/poles/ culvertsetc complete with protection cover, sand, pipe complete all as specified and directed by Engineer-in-charge.Note:- (i) Old cable as obtained shall be re-used. (ii) Old serviceable protection cover, protection pipe and sand obtained under this item shall be reused if found serviceable.(iii) Earth work and any other new items shall be measured and paid separately under relavent items. |
| 22 | Material and labour for replacement of old unserviceable indicator lamp any type with LED based indicating lamps of RYB colour incl disconnecting and connecting of the same all as directed at site. |
| 23 | Material and labour for fabrication of copper busbar iE26:E29 hot in any size and shape all as directed and including RYB insulation mounted on epoxy cast/polymer glass insulators all as directed by Engr-in-charge. |
| 24 | Supply, fixing and replacement of MCCB 400 Amps 4 pole 36 KA 415 Volts 3 Phase 4 wire, microprocesssor release type MTX1.0 (Icu=Ics=100%), Uimp=8kV including accessories like spreaders, nut bolts, lugs etc suitablesetting complete all as directed by Engineer-in-Charge. |
| 25 | All as peritem No. 25.00 here-in-above, but MCCB 250 Amps 4 pole 36 KA, thermal magnetic adjustable release type. |
| 26 | All as peritem No. 25.00 here-in-above, but MCCB 160 Amps 4 pole 36 KA, thermal magnetic adjustable release type. |
| 27 | All as peritem No. 25.00 here-in-above, but MCCB 160 Amps 3 pole 36 KA, thermal magnetic adjustable release type. |
| 28 | All as peritem No. 25.00 here-in-above, but MCCB 250 Amps 3 pole 36 KA, thermal magnetic adjustable release type. |
| 29 | M&L for end outdoor/indoor jointing kit suitable for 25 to 50 sqmm3.5/4 coreXLPE/ PVC Cable 1100 volts grade, heat shrinkable type for indoor/ outdoor applications complete including preparing ends of cable, complete all as specified and directed. |
| 30 | M&L for end outdoor/indoor jointing kit suitable for 70 to 95 sqmm3.5 core XLPE/ PVC Cable 1100 volts grade, heat shrinkable type for indoor/ outdoor applications complete including preparing ends of cable, complete all as specified and directed. |
| 31 | M&L for end outdoor/indoor jointing kit suitable for150 to 185 sqmm3.5 coreXLPE/ PVC Cable 1100 volts grade, heat shrinkable type for indoor/ outdoor applications complete including preparing ends of cable, complete all as specified and directed. |
| 32 | Material and labour Cement concrete (1:2:4) type B -1 using 20 mm graded stone aggregatefor pedestal of poles/copping including necessary frame work ,fair finishing to exposed surfaces using extra cement complete form, all as directed by EIC. |
| 33 | Material and labour for Cement concrete (1:3:6) type C -2 using 40 mm graded stone aggregate for foundation of pole /struts/stayassembly etc complete all as directed by EIC. |
| 34 | Material and labourin replacement forprestressed cement concrete poles 9 M long of size 102 mm x 172 mm at top and 102 mm x 279 mm at bottom class-10, conforming to relavent latest IS including dismantling and refixing of cross arm, security light fittings, brackets or any other existing fittings etc connecting, testing including dismantling and removal of broken pole and coping complete all as specified and directed at site.NOTE:- (i) Earthwork, PCC will be measured and paid separately under relevant item.(ii)Removal of dismantled items from site are included in rate quoted by the contractor. |
| 35 | Dismantling and Supply, erection and fixing in true vertical position steel tubler swaged pole 09 mtr long type (410-SP-31) conforming to IS -2713 (part 1 and 2) - 1980 complete with cast iron base plate, pole cap, MS bolts, nuts and screws, welded and reduced section and lonitudinal weld seam throughout entire length of pole including material and labour for 2 coats of black bituminous paint throughout internally and externally upto planting depth and remaining exterior position of pole with two coats of aluminium paint over a coat of red oxide primer complete allas specified and directed. |
| 36 | Dismantling ofinsulators any type any size from existing poles, complete all as specified and directed. |
| 37 | Supply and fix pin type porcelain insulator, vitreous whitebrown or green including onegalvanised mild steel spindle two GI washer and GI Nuts 100 mm height 65 mm dia for 1100 volts grade, complete all as specified and directed. |
| 38 | All as peritem No. 38.00 here-in-above, but, 50mm height, 65mm dia for 550 volts grade |
| 39 | Supply and fix shackle Type, porcelain, vitreous, white, brown or green insulator 1100 volt grade 75 mm in height and 90 mm dia including galvanised mild steel straps of size 31 x 3 mm, insulator bolt of 12 mm dia, washers and nut complete all as specified and as directed. |
| 40 | M & L for disconecting and re-connecting of burnt LT XLPE cable from panel to OH conductor on pole/ panel/equipment including removing of faulty part of cable, preparation of cable for connection, suitable Al lugs, nut bolts, glands, GI pipe etc and as directed on site by EIC. Note: (i) The cost of earth work for taking out LT cable loop and refiling will deemed to be included in above quoted rate. (ii) GI pipe and Al Lugs to be measured under separate Sch \"A\" item mentioned. |
| 41 | S&F in replacement of Aluminium lugs of 16 Sqmmall as specified and directed by Engineer-in Charge. |
| 42 | S&F in replacement of Aluminium lugs of 25 Sqmmall as specified and directed by Engineer-in Charge. |
| 43 | S&F in replacement of Aluminium lugs of 35 Sqmmall as specified and directed by Engineer-in Charge. |
| 44 | S&F in replacement of Aluminium lugs of 50 Sqmmall as specified and directed by Engineer-in Charge. |
| 45 | S&F in replacement of Aluminium lugs of 70 Sqmmall as specified and directed by Engineer-in Charge |
| 46 | S&F in replacement of Aluminium lugs of 95 Sqmm all as specified and directed by Engineer-in Charge. |
| 47 | S&F in replacement of Aluminium lugs of 120 Sqmmall as specified and directed by Engineer-in Charge. |
| 48 | Labour only for Re-stringing, restraining ACSR conductor laid over, OH LT line on steel/PCC poles after removing the binding from insulators, lowering the ACSR conductor or broken OH line due to any reason, jointing the broken conductor, Re-winding the ACSR with insulators including providing binding wire, jumpering & connecting the existing service cables after re-stretching/Re-straining to OH line & removing unavoidable sag in the lines, complete all as specified and directed by Engr-in-charge Note :1. Proper shut down will be taken by the authorised rep only. 2. The necessary man power, tool & plant, ledder and JCB/ Veh required for is deemed to incl in the rate quoted for the job. |
| 49 | Supply, fixing, stringing, testing and commissioning in replacement of ACSR insulated rabbit conductor of size 6+1/.35 mm binding with insulators including binding material and connection of all service connections/existing cables complete all as specified and as directed. Note :- (i) Rate of dismantling of old u/s conductor is deemed to be included in quoted rate. |
| 50 | Material and labour in replacement for steel structure, cross arms, bracing supports, clamps, back plates of any type, section incl. nuts, bolts, washers, welding, fabrication/bending cold or hot in any size and shape required at site complete applying of two coats of aluminumpaints over a coat of red oxide primer incl dismantling complete all as directed by Engr-in-charge. |
| 51 | Cutting and trimming of trees and branches to clear the over head line in the arc of LT over head line feeders and removal of the trimmed branches of trees complete all as specified and directed.Notes :1. Any ACSR conductor damaged during the cuttings of trees / branches shall be repaired and jointed / fixed by the contractor, to the entire satisfaction of Engr-in-Charge, without any extra cost and nothing extra shall be admissible from the department on this account what-so-ever. 2. The cutting / trimming of tree branches shall be done to atleast 2.00 metre radius of OH line. 3. The unit of measurement is \"SPAN\" i.e. distance covered between two poles. 4. Proper shut down will be taken by the authorised rep only. 5. The necessary man power, tool & plant, cutting tools and JCB required for cutting/pruning of branchesis deemed to incl in the rate quoted for the job. |
| 52 | M&L for danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red color and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 30x25cm size complete all as specified and as directed. |
| 53 | All as peritem No. 53.00 here-in-above, but for HT, 25x20cm size |
| 54 | Material and Labour for preparation of old painted surface and ZEBRA painting of PCC/steelpoles 9/11 m long alongwith roadupto 1.5 m height from pedestal, with two coats of enamel synthetic paints in 30 cm height incl painting of pole coping with white paint all as directed by EIC. |
| 55 | M&L for painting in steel tubular pole/rail pole upto 9 mtr long applying two coats of enamel synthetic silver paints over including M&L surface coat of red oxide incl painting of pole coping with white paint and zebra painting upto 1.5 mtr from pole coping all as directed by Engr-in-Charge. |
| 56 | Material and Labour for preparation of old painted surface for steel structure, cross arms bracing supports ,clamps, back plates of any type, section incl. nuts, bolts, washers, pipes mounted on PCC/steel poles 9/11m long alongwith road with two coats of enamel synthetic paints all as specified and directed by Engr-in-Charge |
| 57 | Material and labour for writing pole number ofminimum size 10 cm height with black paint over base of yellow paint on PCC/steel poles of LT supply complete all as directed by EIC. |
| 58 | M&L in replacement for stay assembly completewith 230x230x 6 mm thick plate and 16 mm dia stay rod all asshownin electplate No-1 of SSR-part -1including stay wire of size 7/4mm dia and suitable loop insulator of appropriate size all as spcified and directed byEngr in charge. Note : Rate quoted is deemed to be included excavation in any type of soil, PCC for stay and dismantling of old stay assy. |
| 59 | M&L for straight through joint kit suitable for 10 to 16 sqmm 3.5/4 core XLPE/PVC cable 1100 volts grade,heat shrinkable type complete including preparing of cable all as directed by Engr-in-Charge |
| 60 | M&L for straight through joint kit suitable for 25 to 50 sqmm 3.5 core XLPE/PVC cable 1100 volts grade,heat shrinkable type complete including preparing of cable all as directed by Engr-in-Charge |
| 61 | M&L for straight through joint kit suitable for 70 to 95 sqmm 3.5 core XLPE/PVC cable 1100 volts grade,heat shrinkable type complete including preparing of cable all as directed by Engr-in-Charge |
| 62 | M&L for straight through joint kit suitable for 120 to 185 sqmm 3.5 core XLPE/PVC cable 1100 volts grade,heat shrinkable type complete including preparing of cable all as directed by Engr-in-Charge |
| 63 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 10 sqmm 2 core nominal cross section in service connections, complete all as specified and directed by Engr-in-charge. |
| 64 | All as per item No. 64.00 here-in-above, but 16 aqmm 2 core |
| 65 | M&L for earthing complete with galvanised steel earth plate electrode 60 cm × 60 cm × 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point complete all as specified and directed by engineer-i-charge including testing on completion. |
| 66 | Ditto as per item no 66 but using galvanised iron strip 25×4mm as earthing lead. |
| 67 | Ditto as per item no 66but using galvanised iron strip 32×6mm as earthing lead |