| 1 | Taking down carefully copper/aluminium point wiring light ,fan, socket or power complete,such as switches, ceiling roses,pendents, regulators, sockets etc.removing materials to store for keeping in safe custody or for taking credit and making good disturbed surface of walls, floors etc.Complete all as specified and directed by Engineer-in-Charge. |
| 2 | Taking down MCB DB any type and any capacity all as specified and directed by Engineer-in-Charge. |
| 3 | Taking down Sub main wiring any type any size all as specified and directed by Engineer-in-Charge. |
| 4 | M&L for point wiring with 1.5sqmm PVC insulated 1100 volt grade IS -694 FRLSH multi stranded but unsheathed copper conductor cable drawing in existingsteel /PVC conduit and terminated in existing terminal box with 3 mm thick plastic laminated sheet cover for fixing of switches,sockets and fan regulator including continuous earth wire with copper cable FRLSH 1.5 sq mm similar description of main cable connected to main earth dully complete all as specified and directed by Engineer in Charge. |
| 5 | one light/ fan/Exhaust fan point controlled by one switch. |
| 6 | -do -as above but for 5 amp socket on same board |
| 7 | -do- as above but for 5 amp socket on independent board |
| 8 | All as per item No 4 above but with 2.5 Sq mm cable for Independent one 6 pin 5/15 Amps socket outlet In and including1.5 Sq mm PVC insulated copper conductor unsheathed 1100 v grade IS -694 FRLSH cable for continuous earth wire. |
| 9 | M&L for point wiring complete with 1.5 Sq mm PVC insulated but unsheathed multistranded copper conductor FRLSH cable 1100 volts grade IS-694 (Phase- Red/Blue/Yellow, Netural -Black and earth continuity conductor 1.50 sqmm Green) drawn through and including PVC casing caping not less than 20x12mm ISI marked ivory colour includingaccessories like bends, tees junction boxes, etc fixed on wall or ceiling etc including 1.5 Sq mm, single core,PVC insulated but unsheathed multi stranded copper conductor FRLSH cable 1100 Volts grade as earth continuity wire including sunken type pressed steel terminal boxes of suitable size with 3mm thick phenolic laminated white sheet cover/ Modular box suitablefor mounting swiches, sockets, fan regulators etc complete for : - |
| 10 | One light point/fan point controlled by one switch 5 amp one way |
| 11 | -do- as above but for 5 amp socket on same board |
| 12 | -do- as above but for 5 amp socket on independent board |
| 13 | All as per item No 5 above but with 2.5 Sq mm cable for Independent one 6 pin 5/15 Amps socket outlet In and including1.5 Sq mm PVC insulated copper conductor unsheathed 1100 v grade IS -694 FRLSH cable for continuous earth wire. |
| 14 | S&F in repair switch piano 5 amps flush type single pole one way |
| 15 | S&F in repai switch piano 16 amps flush type single pole one way |
| 16 | S&F in repair socket outlet flush type 5 pin 6 amps |
| 17 | S&F in repair socket outlet 2 in 1, 5 pin 16 amps flush type |
| 18 | S&F in repair modular switches 6 amps single pole one way |
| 19 | S&F in repair modularsocketes outlet6 amps 5 pin |
| 20 | S&F in repair modular switches 16 Asingle pole one way |
| 21 | S&F in repair modularsocket6-16 A 3 pin combined 2 module |
| 22 | S&F in repair modular Step fan Speed regulator 5 steps |
| 23 | Supply and fixing in repair Steped type elecrtonicfan regulator flash type on the existing phenolic laminated sheet etc suitable for 240 volt |
| 24 | M&L for ceiling rose surfaces bakelite 65 x 17mm white coloured 3 terminals ISI marked |
| 25 | Supply and draw submain wiring with two single core 6 sqmm FRLS PVC insulated copper cable 1100 vots grade multistrand, unseathed conductor drawn into PVC casing and caping and all necessary fittings including 6 sqmm multi strand FRLHS PVC insulated copper wire for earth continuty conductor connected to common earth dully complete including taking down old unserviceable sub main wiring of any size and making good disturbed surface complete all as specified and directed. |
| 26 | All as per Item No-17 above but two single core 4 Sqmm for phase & neutral and 01 single core 4 Sqmm for earth wire. |
| 27 | All as per Item No-17 above but two single core 2.5 Sqmm for phase & neutral and 01 single core 2.5 Sqmm for earth wire. |
| 28 | S&F in repair MCBs of\"C\" series having breaking capacity 10 KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs of Single pole 6 to 32 amp. |
| 29 | S&F in repair MCBs of\"C\" series having breaking capacity 10 KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs of SPN 40 to 63 amp. |
| 30 | S&F in repair MCBs of\"C\" series having breaking capacity 10 KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs of TPN 40 to 100 amp. |
| 31 | S&F in replacment of MCB distribution board, powder coated, CRCA steel sheet, degree of protection IP 43 - IK 09 with reversible double door, recess mounted, having insulated 100 amp tinned copper bus bar, neutral busbar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required with SPN, 240 volts, 4 ways. |
| 32 | S&F in replacement MCB distribution board, powder coated, CRCA steel sheet, degree of protection IP 43 - IK 09 with reversible double door, recess mounted, having insulated 100 amp tinned copper bus bar, neutral busbar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required with SPN, 240 volts, 8 ways. |
| 33 | S&F in replacement MCB distribution board, powder coated, CRCA steel sheet, degree of protection IP 43 - IK 09 with reversible double door, recess mounted, having insulated 100 amp tinned copper bus bar, neutral busbar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required with TPN, 440 volts, 4 ways. |
| 34 | S&F in repair LED fixture 8 watt 2 feet including connection operated at AC 240 Volt completeall as specified and directed by Engineer in Charge. |
| 35 | Supply and fixing in repair rechargable inverter 4 feet 20W tube light fitting battery powered polycarbonate housing connecting up withflexible copper conductor cable of suitable size from ceiling rose complete |
| 36 | M&L in repair for single pole and neutral metal clad enclosures with a two pin and earth plug and socket complete with one single MCB 20 amps ‘C’ curve type and electrical connection all as directed by EIC. |
| 37 | Supply and fixing in repair LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.as directed |
| 38 | Supply and fixing in repair LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection complete with GI bracket and fittings as directed |
| 39 | M&L for in repairs earthing complete with galvanised steel earth electrode 60cmx60cmx6mm buried directly in ground vertically to depth not less than 2.25m below normal ground level with top edge of the earth plate at a depth not less than1.5m below ground level connected to and including GI earth lead wire 4mm dia by meansof nuts, bolts, check nuts and washer etc, made of GI and connected to test point and earth dolly all as shown in electrical plate No. 3 SSR Part-I 2009 and specified or indicated including excavation and earthwork in any type of soil PCC (1:3:6) Type C1 in chamber, precast RCC 50 mm thick in cement concrete (1:2:4) type B1, reinforced with welded steel wire fabric or XPM (Weight not less than 4.00 Kg/Square metre) with PCC frame, funnel with wire mesh, 20mm bore medium grade GI watering pipe, lugs, 15mm bore medium grade GIprotection pipe, test point etc. complete all as specified and directed.Note: -(i) Item includes the cost of 7.5 metre GI pipe for protection of earth lead.(ii) Item includes the cost of 7.5 metre GI earth lead. |
| 40 | NOTE:- THE OLD UNSERVICEABLE ITEM SHALL BE DEPOSITED BY CONTRACTOR TO AGE EM STORE YARD BY HIS OWN ARRANGEMENT. |