Quotation For Different Items Work For Museum Area At Pandit Deen Dayal Museum At Lucknow , Low Side Refrigerant Piping Supply, Installation , Testing And Commissioning Of Interconnectingrefrigerant Copperpipe Work Suitable For R-410A Refrigerant With (19Mm / 13Mm Thick) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Ofindoor & Outdoor Units As Per Specifications, All Piping Inside The Room.All Pipingshall Be Properly Supported With Ms,Gi Studs / Clamps / Hangers. All Piping Shall Be Pressure Tested For 1.5 Times The Working Pressure. The Refregerant Pipes Running In Vertical Shaft Shall Be Supported On Ms Angle And Wooden Saddle At Every 1200 Mm Distance And The Pipes Which Are Running Horizontally Above The False Ceiling Should Be Supported On Ms Angle/Slotted Angle At Every 1200 Mm Distance. (Make :- Mandev, Mexflow) 41.1 Mm , Low Side Refrigerant Piping Supply, Installation , Testing And Commissioning Of Interconnectingrefrigerant Copperpipe Work Suitable For R-410A Refrigerant With (19Mm / 13Mm Thick) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Ofindoor & Outdoor Units As Per Specifications, All Piping Inside The Room.All Pipingshall Be Properly Supported With Ms,Gi Studs / Clamps / Hangers. All Piping Shall Be Pressure Tested For 1.5 Times The Working Pressure. The Refregerant Pipes Running In Vertical Shaft Shall Be Supported On Ms Angle And Wooden Saddle At Every 1200 Mm Distance And The Pipes Which Are Running Horizontally Above The False Ceiling Should Be Supported On Ms Angle/Slotted Angle At Every 1200 Mm Distance. (Make :- Mandev, Mexflow) 34.9 Mm , Low Side Refrigerant Piping Supply, Installation , Testing And Commissioning Of Interconnectingrefrigerant Copperpipe Work Suitable For R-410A Refrigerant With (19Mm / 13Mm Thick) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Ofindoor & Outdoor Units As Per Specifications, All Piping Inside The Room.All Pipingshall Be Properly Supported With Ms,Gi Studs / Clamps / Hangers. All Piping Shall Be Pressure Tested For 1.5 Times The Working Pressure. The Refregerant Pipes Running In Vertical Shaft Shall Be Supported On Ms Angle And Wooden Saddle At Every 1200 Mm Distance And The Pipes Which Are Running Horizontally Above The False Ceiling Should Be Supported On Ms Angle/Slotted Angle At Every 1200 Mm Distance. (Make :- Mandev, Mexflow) 28.6Mm , Low Side Refrigerant Piping Supply, Installation , Testing And Commissioning Of Interconnectingrefrigerant Copperpipe Work Suitable For R-410A Refrigerant With (19Mm / 13Mm Thick) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Ofindoor & Outdoor Units As Per Specifications, All Piping Inside The Room.All Pipingshall Be Properly Supported With Ms,Gi Studs / Clamps / Hangers. All Piping Shall Be Pressure Tested For 1.5 Times The Working Pressure. The Refregerant Pipes Running In Vertical Shaft Shall Be Supported On Ms Angle And Wooden Saddle At Every 1200 Mm Distance And The Pipes Which Are Running Horizontally Above The False Ceiling Should Be Supported On Ms Angle/Slotted Angle At Every 1200 Mm Distance. (Make :- Mandev, Mexflow) 22.2 Mm , Low Side Refrigerant Piping Supply, Installation , Testing And Commissioning Of Interconnectingrefrigerant Copperpipe Work Suitable For R-410A Refrigerant With (19Mm / 13Mm Thick) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Ofindoor & Outdoor Units As Per Specifications, All Piping Inside The Room.All Pipingshall Be Properly Supported With Ms,Gi Studs / Clamps / Hangers. All Piping Shall Be Pressure Tested For 1.5 Times The Working Pressure. The Refregerant Pipes Running In Vertical Shaft Shall Be Supported On Ms Angle And Wooden Saddle At Every 1200 Mm Distance And The Pipes Which Are Running Horizontally Above The False Ceiling Should Be Supported On Ms Angle/Slotted Angle At Every 1200 Mm Distance. (Make :- Mandev, Mexflow) 19.1 Mm , Low Side Refrigerant Piping Supply, Installation , Testing And Commissioning Of Interconnectingrefrigerant Copperpipe Work Suitable For R-410A Refrigerant With (19Mm / 13Mm Thick) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Ofindoor & Outdoor Units As Per Specifications, All Piping Inside The Room.All Pipingshall Be Properly Supported With Ms,Gi Studs / Clamps / Hangers. All Piping Shall Be Pressure Tested For 1.5 Times The Working Pressure. The Refregerant Pipes Running In Vertical Shaft Shall Be Supported On Ms Angle And Wooden Saddle At Every 1200 Mm Distance And The Pipes Which Are Running Horizontally Above The False Ceiling Should Be Supported On Ms Angle/Slotted Angle At Every 1200 Mm Distance. (Make :- Mandev, Mexflow) 15.9 Mm , Low Side Refrigerant Piping Supply, Installation , Testing And Commissioning Of Interconnectingrefrigerant Copperpipe Work Suitable For R-410A Refrigerant With (19Mm / 13Mm Thick) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Ofindoor & Outdoor Units As Per Specifications, All Piping Inside The Room.All Pipingshall Be Properly Supported With Ms,Gi Studs / Clamps / Hangers. All Piping Shall Be Pressure Tested For 1.5 Times The Working Pressure. The Refregerant Pipes Running In Vertical Shaft Shall Be Supported On Ms Angle And Wooden Saddle At Every 1200 Mm Distance And The Pipes Which Are Running Horizontally Above The False Ceiling Should Be Supported On Ms Angle/Slotted Angle At Every 1200 Mm Distance. (Make :- Mandev, Mexflow) 12.7 Mm , Low Side Refrigerant Piping Supply, Installation , Testing And Commissioning Of Interconnectingrefrigerant Copperpipe Work Suitable For R-410A Refrigerant With (19Mm / 13Mm Thick) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Ofindoor & Outdoor Units As Per Specifications, All Piping Inside The Room.All Pipingshall Be Properly Supported With Ms,Gi Studs / Clamps / Hangers. All Piping Shall Be Pressure Tested For 1.5 Times The Working Pressure. The Refregerant Pipes Running In Vertical Shaft Shall Be Supported On Ms Angle And Wooden Saddle At Every 1200 Mm Distance And The Pipes Which Are Running Horizontally Above The False Ceiling Should Be Supported On Ms Angle/Slotted Angle At Every 1200 Mm Distance. (Make :- Mandev, Mexflow) 9.5 Mm , Low Side Refrigerant Piping Supply, Installation , Testing And Commissioning Of Interconnectingrefrigerant Copperpipe Work Suitable For R-410A Refrigerant With (19Mm / 13Mm Thick) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Ofindoor & Outdoor Units As Per Specifications, All Piping Inside The Room.All Pipingshall Be Properly Supported With Ms,Gi Studs / Clamps / Hangers. All Piping Shall Be Pressure Tested For 1.5 Times The Working Pressure. The Refregerant Pipes Running In Vertical Shaft Shall Be Supported On Ms Angle And Wooden Saddle At Every 1200 Mm Distance And The Pipes Which Are Running Horizontally Above The False Ceiling Should Be Supported On Ms Angle/Slotted Angle At Every 1200 Mm Distance. (Make :- Mandev, Mexflow) 6.4 Mm , Refrigerant Piping Y-Joints Or Headers As Required To Connect The Above Outdoor Units And Indoor Units. (Make :- Daikin, Bluestar, Mitsubhishi) Supply Of Y-Joint Indoor Unit , Refrigerant Piping Y-Joints Or Headers As Required To Connect The Above Outdoor Units And Indoor Units. (Make :- Daikin, Bluestar, Mitsubhishi) Supply Of Y-Joint Outdoor Unit , Low Side Control Wiring Supply, Installation, Testing And Commissioning Of 2C X 1.5Sqmm Control Cum Transmission Wiring/Power/Control Cabling With Pvc Insulated, Pvc Sheathed, Multicore Copper Conductor Control Cable In Suitable Conduits Between Indoor And Outdoor Units And Its Remote Controllers. (Make :- Anchor, Havels, Rr) , Drain Piping Supply, Installation , Testing And Commissioningof Hard Pvc Drain Piping Of Complete With U Trap Fittings And Elbows From The Indoor Unit Point To The Nearest Drain Point Complete With Fittings, Supports, Valve And 6 Mm Thick Closed Nitrile Rubber Foam Insualtion As Per Specifications & Drawings. (Make :- Prince, Supreme, Astral) 50 Mm , Drain Piping Supply, Installation , Testing And Commissioningof Hard Pvc Drain Piping Of Complete With U Trap Fittings And Elbows From The Indoor Unit Point To The Nearest Drain Point Complete With Fittings, Supports, Valve And 6 Mm Thick Closed Nitrile Rubber Foam Insualtion As Per Specifications & Drawings. (Make :- Prince, Supreme, Astral) 40 Mm , Drain Piping Supply, Installation , Testing And Commissioningof Hard Pvc Drain Piping Of Complete With U Trap Fittings And Elbows From The Indoor Unit Point To The Nearest Drain Point Complete With Fittings, Supports, Valve And 6 Mm Thick Closed Nitrile Rubber Foam Insualtion As Per Specifications & Drawings. (Make :- Prince, Supreme, Astral) 32 Mm , Drain Piping Supply, Installation , Testing And Commissioningof Hard Pvc Drain Piping Of Complete With U Trap Fittings And Elbows From The Indoor Unit Point To The Nearest Drain Point Complete With Fittings, Supports, Valve And 6 Mm Thick Closed Nitrile Rubber Foam Insualtion As Per Specifications & Drawings. (Make :- Prince, Supreme, Astral) 32 Mm , Supply, Installation, Testing And Commissioning Of Flexible Canvass Cloth Connection At Oulet Of Each Ducted Indoor Unit With Zipper To Facilitate Temperature Measurement , Supply, Installation, Testing And Commissioning Of Flexible Canvass Cloth Connection At Oulet Of Each Ducted Indoor Unit With Zipper To Facilitate Temperature Measurement , Dome Work 12Mm Thick Polycarbonate Sheet Including Aluminium Fitting Top & Bottam, Rubber Sheet Etc. Complete