| 1 | M&L for Excavation in trenches in soft/loose soil not exceeding 1.5 mtrwide and not exceeding 1.5 meter in depth for taking out and laying UG cable and getting out, excavated earth, forming bottomsurfaces to required level complete all as specified and directed. |
| 2 | Excavation in trenches not exceeding 1.5 m wide and beyond the first 1.5 m in depth for taking out pipe line etc for repairs / laying cables etc and getting out in soft / loose soil complete all as specified and as directed. |
| 3 | M&L for Returning,filling in, including spreading, leveling, watering and well raming in layers not exc 25 cm. |
| 4 | M&L for Removing excavated soil and depositing to the sides and returning filling in including spreading leveling watering and well ramming in layers n.exc 25cm thick in soft/loose soil after cable is laid complete all as specified. |
| 5 | Supply and fixing on wall/floor or ceiling HDPE pipe of size 80 mm for UG Cable protection with proper clamping arrangement all as specified and directed. |
| 6 | M&L for providing dry screened river sand as in sand cushioning to under groundcable including punning down of sand by layer complete all as specified and as directed. NOTE: Punned thickness shall be measured and paid. |
| 7 | Supply and lay unreinforced precast cable cover size 250X150X40 mm complete all as specified and as directed. |
| 8 | M&Lfor PCC 1:4:8 type D2 using40mm graded aggregatefor pole / struts foundation etc allasspecified and directed. |
| 9 | M&LforPCC 1:3:6 type C1 using 20mmgradedaggregateforcoping includingnecessaryform workandfair finishingofexposedsurface of concrete allasspecified and directed.NOTE : Volume of poles / strut/pipe s embedded in concrete shall be deducted for the purpose of payment. |
| 10 | Taking out old unserviceable underground cable of any size/ make/ type etc from excavated trenches/ on poles/ passing through pipes etc from different locations complete all as specified and as directed. |
| 11 | Supply, laying or passing through pipe HT, XLPE insulated, galvanised steel stripor wire armoured electric power cable (heavy duty) with stranded aluminium conductor 11000 Volts,earthed grade of size 185 Sqmm 3 core including connecting/testing after taking out from trenches/ pole unserviceable HT UG cable complete all as specified and directed. |
| 12 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150sq mm 3½ core |
| 13 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120sq mm 3½ core |
| 14 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3½ core |
| 15 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core |
| 16 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core |
| 17 | Dismantling and Taking down LT U/S panels incl all outgoing and incoming connections and making good the disturbed area from site all as specified and directed by Engineer-in-Charge. |
| 18 | Supply,install,test and commision LT panel board,outdoor type, factory made, powder coated , dust and vermin and weather proof, Cubicle type made out of 3 mm thick CRCA Sheet & MSangle iron section of 50X50X6 mm frame, front operated with locking arrangements. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands and provision for louvers and air vent gasket for natuaral flow of air .The panel board shall have suitable busbar chamber having sufficient space to pass through UG Cables and have compartments for each control gear and metering devices.Providing bus bar for phases and neutral and shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size \"F\" class insulators made on non hygroscopic, non combustile, track resistant, high strength FRP/SMC/DMC material at an interval of not more than 300 mm through out the length of the TPN bus bar all as specified and directed by the Engr-in-Charge. Note: (a) The quoted rate includes the cost of sutable foundation recommended by the manufacturer of panel board. INCOMERAlu. Busbar 600 A with support duly Heat shrinkable PVC Sleeved- 04 nosMake Hindalco400 A, 4P Changeover Switch -01400 A, 4P MCCB 35 KA- 01 Nos Digital Volt Meters 96mm x96 mm - 01 NosDigital Amp Meter 96mm x 96 mm -01 Nos CT 400/5A -03 NosR Y B phase indicating lamp LED type -01 Sets20A Neutral linkOUTGOING200 A, 4P MCCB 35 KA - 02 Nos 160 A, 4P MCCB 35 KA - 02 Nos MCB SPN 63 Amps \"C\" curve -05 NosPVC WIRING, Thimble,Ferrules etc- LS |
| 19 | Supply,install,test and commision LT panel board, out door type, factory made, powder coated , dust and vermin and weather proof, Cubicle type made out of 3 mm thick CRCA Sheet & MSangle iron section of 50X50X6 mm frame, front operated with locking arrangements. The bottom of the outer shell contains a detachable plate having provision for LT meter with HRC fuse as direction by KSEB entry of armoured cable of adequate size with glands and provision for louvers and air vent gasket for natuaral flow of air .The panel board shall have suitable busbar chamber having sufficient space to pass through UG Cables and have compartments for each control gear and metering devices.Providing bus bar for phases and neutral and shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size \"F\" class insulators made on non hygroscopic, non combustile, track resistant, high strength FRP/SMC/DMC material at an interval of not more than 300 mm through out the length of the TPN bus bar all as specified and directed by the Engr-in-Charge. Note: (a) The quoted rate includes the cost provision for LT meter (refixing only with HRC fuse as direction by KSEB and suitable foundation recommended by the manufacturer of panel board.INCOMERAlu. Busbar 200 A with support duly Heat shrinkable PVC Sleeved- 04 nosMake Hindalco250 A, 4P MCCB 36 KA- 01 Nos Multi function meter - 01 NosCT 63/5A -03 NosR Y B phase indicating lamp LED type -01 Sets20A Neutral linkOUTGOING63 A, 4P MCCB 25 KA - 02 Nos MCB, 230 V, 32 A, TPN - 02 Nos MCB SPN 63 Amps \"C\" curve -05 NosPVC WIRING, Thimble,Ferrules etc- LS |
| 20 | Supply and install 120 watt New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protectionall as specified and as directed by Engr in Charge. |
| 21 | Supplyanderrect of Steel Tubular Swaged Pole complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP - 31, 9.0 Mtrs long all includingtwo coats of aluminium paint over a coat of red oxide and two coats of bituminous paint inside and outside of bottom portion up to 1.8 Mtr length all as specified and and directed. |
| 22 | Supply and fix Street light multi function timer switch , electric automatic, 220 V, AC, 16 Amps, 50 Hz ofsuitable rating with all accessories fixed in a suitable steel enclosure and necessary fixing arrangement to fix on panel board or fix on pole as per specification IEC 60730-1/IEC 60730-2-7 all as specified and directed by Engr-in-Charge. |
| 23 | M&L for repairs to LT/HT panel boards complete with necessary welding works to doors, replacement of unserviceable hinges and all drop bolt complete and painting with two coat of synthetic enamel paint of approved colorinternally and externally all as specified and as directed by Engineer-in-Charge |
| 24 | Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 1.1 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all specified and directed. |
| 25 | M&L in replacement of HT Cable end termination box suitable for 11000 Volts grade120 to 185 Sqmm 3 Core XLPE 11KV cable, indoor, hot shrinkable type withall accessories complete all as specified and directed. |
| 26 | S & F PVCweather proof, hinged door, junction box with 10A Aluminium bus bar, 240V, Neutral link and 1No MCB SP of 6 Amps, necessary fixing arrangement such as clamps, nut, bolts, etc including dismantling old unservieable junction box allasspecified and directed. Make : Sintex/L&T or equivalent. |
| 27 | Material and Labour for cutting the existing bituminous road / PCC Hard Standing upto 75cm in depth, 60cm in width and getting out excavated materials making good the damaged portion after laying of pipes by returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick and PCC 1:2:4 type B1 using 20mm graded stone aggregate all as specified and directed. |
| 28 | Supplying and laying in replacement of GI pipe, 40mm dia, Light grade for cable protection at pole/road crossing etc including necessary road cutting and making good with PCC 1:2:4, Type B-1, using 20mm graded stone aggregate, 100mm thick or fixing on wall / poles of any type, secured with clamps complete all as specified and as directed by the Engineer - in - Charge. |
| 29 | Supplying and laying in replacement of GI pipe, 80mm dia, Light grade for cable protection at pole/road crossing etc including necessary road cutting and making good with PCC 1:2:4, Type B-1, using 20mm graded stone aggregate, 100mm thick or fixing on wall / poles of any type, secured with clamps complete all as specified and as directed by the Engineer - in - Charge. |
| 30 | Earthing complete with galvanised steel earth plate electrode of size (600 x 600 x 6.3) mm thick buried directly into ground vertically to depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, surrounded on all sides by alternate layers of 150 mm thick charcoal and common salt,connected to ed iron strip 25 x 4mm by means of lugs, bolts, nuts, washer, check nuts of galvanised iron or steel all as shown in Electrical plate No. 3, wire protected by dia 15 mm bore light grade GI Pipe laid in floor and fixed to wall with proper size of clamps and watering pipe of bore 20 mm dia GI light grade including wire mesh funnel, PCC, earth chamber pit with PCC 1:2:4 type B-1 using 20 mm grade stone aggreate including form work cement mortar including CI Pit cover with frame necessary excavation and earth work in any type of soil including testing on completion for desired result all as specified. |
| 31 | M & L for point wiring with PVC insulated unsheathed multistranded copper conductor cable 1100 volt grade, FRLS of size 4 Sqmm drawn in and including PVC caping and casing surface wiring including modular metal flush box of suitable size with inner and outer white plastic plate (same make of switch and socket) including continues 4 Sqmm copper conductor (multistranded) PVC insulated and unsheathed cable earth wire to common earth and connected to earth dolly complete all as specified conforming to IS-694 for the following:- (a ) One 3 pin socket outlet 16 Amps on Independent board |
| 32 | Supply and fixing of Modular Switch socket combination 16 A, 6 pin, 3 module complete all as specified and directed |
| 33 | Supply and fixing MCB SP 6-32 amp rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) of single pole in the MCB DB complete with connection testing and commissioning complete all specified and directed. |
| 34 | Supply and fixing MCB SPN 40 amp rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) of single pole in the MCB DB complete with connection testing and commissioning complete all specified and directed. |
| 35 | Supply and fixing sheet metal enclosure distribution board (DB), when MCB to be used, dust and vermin proof, single pole andneutral (SPN) 4 way with 200 Amps rated copper bus bar double door protection, neutral bar, earth bar, single pole and neutral 240 volts, MCBs used as incommer Double door, flush to wall complete all as specified and directed. |
| 36 | Material and labour for submain wiring using two run of sinlge core PVC insulated cable (FRLS) 6 Sqmm copper conductor multi stranded and 6 Sqmm copper conductor insulated cable (FRLS) using as earth wire drawn through and including PVC rigid conduit of size not less than 25mm dia with accessories (concealed) complete all as specified and directed |
| 37 | Supply and install 2 TR Capacity ,BEE 5 star ratedhi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality (Inverter type) including provision of suitable bracket fixing arrangement, required copper pipe and insulation as per site requirement, all as specified and directed by the Engineer-in-Charge. |
| 38 | Supply and install 1.5 TR Capacity ,BEE 5 star ratedhi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality (Inverter type) including provision of suitable bracket fixing arrangement, required copper pipe and insulation as per site requirement, all as specified and directed by the Engineer-in-Charge. |
| 39 | Supply and fix Voltage stabilizer 5KVA for automatic operation, single phase naturally air cooled indoor type& designed for input variation between 170 Vto 250 V with output voltage stabilized at 230 Vwith accuracy of ± 2.5%model No VG 500 of Make V Guard/ equivalent approved by the Engineer-in-charge. |
| 40 | Supply & laying of 3- Layer PP-R Polypropylene random copolymer) pipes of 25 mm bore SDR 7.4 & SDR 11 UV stabilised antimicrobial welded having thermal stability forhot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings fixed complete all as specified and directed by Engr-in-charge. |
| 41 | Supply & laying of 3- Layer PP-R Polypropylene random copolymer) pipes of 50 mm bore SDR 7.4 & SDR 11 UV stabilised antimicrobial welded having thermal stability forhot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings fixed complete all as specified and directed by Engr-in-charge. |
| 42 | Supply and fixing PP-R gate valves(brass insert) for 50 mm dia pipe as per requirement of the site all as specified and directed . |
| 43 | Supply and fixing PP-R ball valves(brass insert) for 25 mm dia pipe as per requirement of the site all as specified and directed . |
| 44 | Supply and erect rotational moulded polye thylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I of capacity 2000 Litre. |
| 45 | Supply and erect rotational moulded polye thylene water storage tanks triple layer (cylindrical vertical with closed top) of capacity 10000 Litre hoisted and fixed in position complete all as specified and directed . |
| 46 | Supplying and fixing, levelling, testing, and commissioning of Monoblock Pump single phase 230 volts of capacity 01/ HP with superior quality super enameled copper winding and necessary fitting complete all as specified and directed. |
| 47 | Supply, Fixing and commissoning ofDOL motor starter in sheet metal enclosure typesuitable for single phase electric motor of capacity upto 2HP, 1 phase 230V with relay range 6-12 Amps, complete all as specified and directed by Engineer-In-Charge. |
| 48 | M&L for PCC 1:2:4 type B-1 using 20mm graded crushed stone aggregate suitable foundation including form work for rotational moulded polye thylene water storage tank capacity 10000 Ltrscomplete all as specified and as directed by Engineer-In-Charge. |
| 49 | Supply,installation,testing and commissioning single phase energy meter with the following specifications: Microprocessor based single phase tamper proof electronic static pre paid cum postpaid energy meter rating 240 Volts, 50 HZ of range 10-60 Amps, complying to IS16444 :2015 (reaffrimed 2020)and conforming to IS 13779 with LED display and parameters like Voltage, Current, Frequency, Power, Power factor, KWH/KVA, default /in built dual source, inbuilt long range (LORAWAN) Communication suitable for outdoor LoRa data accumulator and also compatible for Prepaid and Postpaid online energy monitoring billing system with disconnection /reconnection through remote software / data export to ERP complete with 5 Years warranty, complete all as specified and as directed. Make :Elmeasure Model: PE5121 or equivalent in Secure, L&T,Schneider,HPL etc.Note: (a) The contractor would be responsible for removing the existing meter, noting down the reading and depositing it with the MES AGE E/M store complete all as specified & directed.(b) The Energy Meter to be capable of running in both prepaid and postpaid mode.(c) The meters to carry 5 year warranty |
| 50 | Supply,installation,testingand commissioningThree phase energy meter with the following specifications: Microprocessor based three phase tamper proof electronic static pre paid cum postpaid energy meter rating 415 Volts, 50 HZ of range 10-60 Amps, complying to IS16444 :2015 (reaffrimed 2020) and conforming to IS 3779 with LED display and parameters like Voltage, Current, Frequency, Power, Power factor, KWH/KVA, default /in built dual source, inbuilt long range (LORAWAN) Communication suitable for outdoor LoRa data accumulator and also compatible for Prepaid and Postpaid online energy monitoring billing system with disconnection /reconnection through remote software / data export to ERP complete with 5 Years warranty, complete all as specified and as directed. Make :Elmeasure Model: PE5121 or equivalent in Secure, L&T,Schneider,HPL etc.Note: (a) The contractor would be responsible for removing the existing meter, noting down the reading and depositing it with the MES AGE E/M store complete all as specified & directed.(b) The Energy Meter to be capable of running in both prepaid and postpaid mode.(c) The meters to carry 5 year warranty. |
| 51 | Supplying, Fixing, Commissioning and testing of configuration of cloud Hosted multi user web based software with following modules:(a) Meter Data Management ModuleThe meter data management module would be responsible for collecting the data from the data concentrator and make the data available to the billing system. The system would support offline meter data entry. The meter data management system would capture and provide the following data:(i) 30 min instantaneous data from all the meters for seven parameters – Cumulative Energy, Cumulative Apparent Energy (as applicable), Power, Current, Voltage, Power Factor and Frequency(ii) Monthly billing survey data for cumulative energy and max demand(b)Billing Module :The billing module would collect the data from the meter data management module, calculate the energy consumption, calculate billing determinant and make energy data / billing data available to admin and end users. The billing module would include functionalities for tariff setup, bill format setup, bill adjustment, occupation billing and vacation billing. It would allow postpaid and prepaid functionality as required.(c) Occupation and Vacation Module :The system would support occupation / vacation based on the unit catagories. The system would support automatic data capture on occupation and vacation events.(d) Customer Module :The system would include a customer portal for the resident /occupant to log in and view their own energy / billing data.(e) Energy Accounting Module :The system would include features of energy accounting. The system would be able to account for total energy block wise, facility wise and would also allow calculations of unaccounted energy in case total energy meter is also available.(f) Communication Module :The system would provide communication of energy data and bills via print, email and sms methods. (g) Meter Master Data :The system would support meter master data repository. The system would support meter replacement process.(h) Excel Export :The system would support export of metering and billing data in excel format. Make: Elmeasure or equivalent of Secure, L&T, HPL etc. |
| 52 | Supply, installation, testing and commissioning of Outdoor LoRa accumulator for long range communication up to 1KM suitable for communicating with Prepaid come postpaid meter with LoRa communication protocol and the data transfer to the existing Elnet V5 Software complete all as specified and as directed by Engr-in-Charge. The cost of pole /fixing /mounting arrangement on which the accumulator to be installed and SMPS power supply with Power backup for Minimum up to 2 Hours is deemed to be included in the unit quoted ratescomplete all as specified and as directed by Engr-in-Charge Make:- ELMEASURE or equivalent of Secure, L&T,HPL etc. |
| 53 | Supply,installation,testingand commissioning of Cloud based Network Server, MQTT based intelligent network server for bridging between gateway and end application. Eliminate duplicate packets, schedule acknowledgement, and adapts data rates along with 1 Hour UPS back up. Make:- ELMEASURE or equivalent of Secure, L&T,HPL etc. |
| 54 | Hosting GPRS (4G) charges for two Gateways for four years warranty from the date of completion (Including 2 years waranty and 2 years Maintinance after warranty) Make:-Airtel/Jio/Vodafone |
| 55 | Earthing complete with Galvanized steel earth plate electrode of size 600mmX600mm, 6.00 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below the normal ground level with top edge of the plate not less than 1.5m below normal GL and connected to galvanized iron strip of size 32 x 6 mm size by means of bolts, nuts, check nuts and washers of galvanized ironsteel all as shown in Electrical Plate No.5 connecting to earthing test point, including necessary earth work in any type of soil, PCC earth chamber made in PCC 1:3:6 type C1 (using 20mm graded aggregate), common salt, charcoal, CI funnel, earth pit cover in RCC 1:2:4 type B1(using 20mm graded aggregates), with 8mm CTD bars @ 100mm c/c in both ways, including necessary form work complete including necessry test on completionall as specified and as directed. ( LT panels-2 nos x 2=4 nos,Note : The unit rate shall also include for excavation, earth work in hard/dense soil PCC (1:3:6) type C1 , RCC cover slab, GI funnel with 15 mm dia watering pipe, wire mesh, 40mm dia light grade GI protection pipe for earth lead etc., complete. |
| 56 | Taking down carefully single/ three phase energy meter of any type and make from exinsting position without disturbing other connection and deposit the same to AGE E/M store yard complete all as specified and directed. |
| 57 | Material and labour for Portable water supply connection at Radar Station Alleppey pipeline work. |
| 58 | Schedule of Credit (Minus) Rs.25100.00NOTE: Bidder shall insert credit amount of Rs. 25100.00 as ratein Green field under Col-13. |