tender for Electrification Work Of Circles In Municipal Corporation Bhilwara. - 1 Supply, Installation, Testing and Commissioning of Spike Light with 10 Degree Beam Deflection and 3000 K CCT. 2 6 Watt 3 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fittedin existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A &above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer AnnexureA attached with this BSR 4 Double pole MCB(With B/C curve tripping Characteristics) 5 6 A to 32 A rating 6 Providing & Fixing of IK07 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA.driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min>=4KV internal and 10KV external but inside driver compartment, ystem life of 50000 Burning hourswith 70% of Initial Lumens aintained, CRI>70 and CCT 5700K ±355K. Manufactures Word rk/NameEngraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shallbe IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LEDfixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shallbe submitted. All as per pre approved by gineer in charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR . 7 High Power LED Flood Light Minimum lumen output 3700 lm 8 High Power LED Flood Light Minimum lumen output 6200 lm 9 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathedArrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P -I of 1.1 KV with H4- Grade electrolytic aluminium conductorconfirming to IS 8130 of purity >99.6 %, round / flat strip armouringof cables, Inner / outer sheath confirming to IS:5831 in existing RCC/ Hume / Stoneware / PVC pipe/ open duct/cable trench / Cabletray(with cable tie) including testing etc. as required of followingsize. OEM must have its own in house NABL accrediatedLaboratory for testing procedure as per IS:10810.For additionaltechnical parameters of product / work refer Annexure A attachedwith this BSR 10 4.0 Sq. mm 11 4.0 Sq.mm 4 core 12 Providing & Fixing of IK10 IP65 protected 600 mm height LEDBollard Luminarie with base plate made of powder coated die castalluminium housing with UV stabalized PC diffuser. The Systemlevel Luminous efficacy ≥ 90 Lumen/W. SMD LEDs is to be used,System CRI>70, CCT: 3000/4000/6500 K. The integral electronicdriver must be potted & has a unique BIS R number must be potted& has a unique BIS R number constant current and Internal/externalsurge protection device of min. 4KV(L-N) and efficiency > 85%,PF>0.9, THD<20% and input Voltage range of 90-270V AC at 50Hz.System life of 30000 Burning hours with 70% of Initial Lumensmaintained Light output in Cool white or Warm White Colour as perengineers choice. driver current <750mA. Fixture must be incompliance with BIS Standards and Trade mark Certificate completein all respect.OEM Must have its own in house NABL lab setup forall testing facilities for LED fixtures. (LM79/LM80) Certificate/report with liable warranty of product/accessories from OEM shall besubmitted. All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer AnnexureA attached with this BSR . 13 Minimum lumen output 800 lm Bollard 14 Providing & Fixing of IK10 IP65 / IP66 protected LED Up - Down Luminarie Wall / Surface mounting made of powder coated die cast alluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy ≥ 90 Lumen/W. COB LEDs is to be used,System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant currentand Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained Light output in Cool white or Warm White Colour as per engineers choice. driver current <750mA. Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure A attached with 15 Minimum lumen output 800 lm Up-Down Luminary 16 Supplying and drawing FR PVC insulated & unsheathed flexiblecopper conductor as per PWD specification for electrical Works withISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wireshould be made from 99.90 % purity copper, class 5 stranding inacc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for lesschances of oxidization, insulation PVC type A/C/D , flame retardantas per IS 10810-53, better amperage rating as per IS:3961 part 5, inexisting surface or recessed PVC/ MS conduit/casing cappingmaking connections with Copper Lugs of suitable size,Ferrules,testing etc. as required. OEM Must have its own in houseNABL lab setup for all testing facilities for wires. For additionaltechnical parameters of product / work refer Annexure A attachedwith this BSR 17 2 x 2.5 sq.mm 18 Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. B class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387with perforated holes of 12 mm dia ,including all accessories like nut,bolts, reducer, nipple, wire meshed funnel, and Heavy duty weatherproof poly-propylene earth pit chamber with lockable Jam free lidsuitable for safe working load 5000 Kg or more of size Top Dia. 225to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm.and embodying the pipe complete with alternate layers salt andcoke/ charcoal, testing of earth resistance for value of 5 ohms orless as required & must record by engineer in-charge during sitevisit and ensure to enter in measurment book.All as per preapproved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure A attached withthis BSR . 19 Supply & Laying following size earth wire in horizontal or vertical runin ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95% thimble etc. asrequired. All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer AnnexureA attached with this BSR . 20 10 SWG G.I. ( Hot Dipped ) Wire 21 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed UnarmouredCopper cable confirming to IS:1554 P-I / IS :7098 P - I of1.1 KV with electrolytic grade Copper made of copper rodsconfirming to IS 613-1964, of purity >99.7 %, Inner / outer sheathconfirming to IS:5831 in existing RCC / Hume / Stoneware / PVCpipe/ open duct/cable trench / Cable tray (with cable tie) includingtesting etc. as required of following size. OEM must have its own inhouse NABL accrediated Laboratory for testing procedure as perIS:10810 For additional technical parameters of product / work referAnnexure A attached with this BSR 22 1.5 Sq. mm 23 2 Core 24 Providing & Fixing of IP - 65 protected impact resistantpolycarbonate / Polysterene enclosures with knock out for cableentry/out including fixing with nut, bolt, fatner etc as requiredcomplete in all respect of following sizes.All as per pre approved byEngineer in-charge. For additional technical parameters of products/work , refer Annexure A attached with this BSR . 25 250 x 200 x 115 mm 26 P / L of Double wall corrugated HDPE pipe confirming to IS : 16205P-24, Stiffness Class 750 N, Externally corrugated and havingsmooth surface inside with HDPE Coupler, Elbow, Tee at requiredDepth below the ground for laying cable of following Nominal Outerdia. MFR Test report from NABL accrediated is to besubmitted.(Excavation of Earth & Back filling with compaction is tobe Paid Extra)All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer AnnexureA attached with this BSR . 27 75 mm 28 Add Extra for Laying of one number PVC insulated and PVCsheathed / XLPE power cable of 1.1 KV grade direct in groundincluding excavation of trench of size 75 cm (Depth) x 35 cm(Width), with procedure as per following points:- (a) Make a riversand bed of height 125 mm along the trench, (b) Lay the cable inthe middle of the trench, (c) Provide river sand bed of height 125mm on top of the cable, (d) Lay the protective Common burnt clayF.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mmthickness and 225 mm wide just above the sand bed verticallyacross the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill theexcavated soil leaving 300 mm from the Ground level, (f)Lay theCable warning tape and again back-fill the remaining portion of thetrench upto the ground level and compacting the earth 29 Add Extra in Item no.60.5 if Excavation done in Hard Rock / CC road/ TAR Road and making Good the same 30 S&F following sizes (dia.) of ISI marked virgin material MMS (IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988)accessories as required in recess including cutting the wall,covering conduit and making good the same as required. Foradditional technical parameters of product / work refer Annexure Aattached with this BSR 31 25 mm