| 1 | Taking down Ceiling fan /exhaust/wall mounted fans of any type and sizeand transportation to work shop, and examining the rotor, stator, bearings/bushes, winding etc subsequently Oiling, greasing assembling, testing andtransportingback to building/site from work shop, hanging/fixing and connecting the electrical connections, testing for noise free smooth running etc; as directed by Engineer -in-Charge.(NoteWork for repair/replacement of spareparts will be measured and paid separately under respective items. |
| 2 | Taking out defective/burnt out windings of ceiling fans of various makes fromsite under GE (North) AOR, of size 1200/1400 mm sweep , 220-240 volt, 50Hz and rewindingthe same with supper enamelled new copper wire of appropriate gauge including varnishing with good quality varnish\" baking up, reassembling the fan, testing includingall as directed by Engineer-in-Charge. |
| 3 | Description all as per item No 2 here-in-before but for exhaust/ wallfans of size 150to 450mm sweep |
| 4 | M & L for replacement of defective ball bearing for ceiling of any size any type (Bearing make/size SKF-6201/6202/ 6203/6204or equivalent ) |
| 5 | M & L for replacement of defective capacitor of size 2.5 mfd for any type of fans suitable for 250 V including making connection complete all as specified and directed. |
| 6 | Description all as per item No 5.00 here in before but for 0.75/1.7 mfd suitable for PVC /steel exaust fan |
| 7 | Description all as per item No 5.00 here in before but for 3.15 mfd |
| 8 | S&F in repair PVC insulated twin twisted copper conductor wire 1100 V grade of size 24/.20 (0.75 Sqmm) |
| 9 | M & L for paintingof ceiling fans along with blades of any make/model of size 1200 to 1400mm sweep.. |
| 10 | Description all as per item No 9 here-in-before but for exhaust fan of size 300- 450 mm sweep. |
| 11 | M & L in replacement of PVC canopy suitable for 1200 mm to 1400 mm sweep ceiling fan complete. |
| 12 | Supply and fixing \"S\" type hook made of 12 mm dia MS round bar/MS flat strip 40x4 mm ofall as specified and directed . |
| 13 | Supply and fixing Exhaust fans steel body,AC single phasee 230 volts of size 300 mm sweep with 4 blades and frame and louver complete all as specified and directed |
| 14 | Supply and fixing Air circulator toilet/bathroom fan PVC body,AC single phasee 230 volts of size 150 mm sweep with blades and frame and louver complete all as specified and directed |
| 15 | Supply and fixing Exhaust fans heavy duty steel body, industrial type wall mounted AC ingle phasee 230 volts of size 450 mm sweep with 4 blades, four arms, frame and louver complete all as specified and directed make cromton greaves. |
| 16 | Supply and fixing Wall mounted fan steel body,AC single phasee 230 volts of size 400 mm sweep with blades withcomplete accessories all as specified and directed |
| 17 | Supply and fixing Pedestal Fan floor mounted ,AC single phasee 230 volts of size 450 mm sweep with aerodynamically designedblades and with powerfull copper motor , air delivery 70CPM, RPM 1350, hight adjustabke tilt oscillation, free stand, plastic body, 3 blade, 60watt make bajaj model No 131021422 complete all as specified and directed |
| 18 | Supply and fixing Ceiling fan 1200mm sweep, AC single phasee 230 volts 52 Watts BEE star rated, 340RPMcopper windingwith complete accessories as manufacturesall as specified and directed |
| 19 | S&Fclamp for down rod of suitable size including gromet/reeltype rubber pad with bolts, nuts and washers and split pin suitable for housing ceiling fan. |
| 20 | Taking out old, broken and rusted louver shutter of any size exhaust fan from wall for necessary replacementcomplete all as specified and directed |
| 21 | Supply and fixing of louver shutter madeof GI sheet metal / pressedsteelsheet 1.2 mm thick for round base and 0.8 mm thick for flaps, comprising of mounting legs framesexhust fan up to 300/450 mm sweep etc copmlete. |
| 22 | Supply and fixing in replacement of ceiling fan blade set 1200 mm/1400mm sweep for ceiling fan of any make and model aero dyanamically balancedincluding screws for fixing with fan complete all as specified and directed. |
| 23 | Supply and fixing in replacement MS down rodheavy duty 15mm nominal dia 18\"long duly painted in matching colour complete all as specified. |
| 24 | Supply and fixing in replacement of rigid aluminium fan blade for exhaust of capacity 150/300/450 mm etc complete. |
| 25 | Disconnection of electric and water connection and taking down carefully storage type electric water heaters ( Geysers ) of capacity 25/35/50 Ltrs ( any Make/Modal ) from its existing position andInspection of Geysers for its seriviceabilty/ un servicieability. |
| 26 | M&L for opening, dismantling, brushing and cleaning ofelectric water heaters ( Geysers ) of capacity 25/35/50 Ltrs, removingall the sludge , scaling and bleaching from the tank and examining of any leakage of water and tightening of nuts, boltsincluding reassembling and refixing its own location complete including following:-(a) Check and connect earth continuity to electric water heater. (b)Cheking and adjusting of pressure realease valve(c) Check and Maitenance, setting of thermostate valve.(d) Visual examination of fusible plug.Notes:-(i)Spare parts/components of Geysers, shall be measured and paid separately.(ii)Transport cost for carry out Geysers from site of work to workshop & vice versa shall be deemed to be included in unit rate. (iii (iii) Minimum two technician ( One Electrician and One Plumber) and one helper with all types of tools and plants/veh etc. should report to E&M yard at 08.30 hrs in all working days.(iv) Repair works will be carried out at workshop E&M yard.(v) Repair works of geyser shouldcompleted and re-fixed the same with in 24 hrs after receipt of complaint slip. (vi) Electrician with helper along with T&P and Ladder will be provided by the contractorfor repairing & servicing for day to day complaints in PB Enlcve, Ashok Vihar, Old Medical Complex, CHNC and complete OTM Accn/Md Accn under this AOR. |
| 27 | Supply and fixing in replacement Geyser Heating elementall typeelect geyser available at site i.e (Clenta, bajaj, recold, crompton, havells etc)of capacity 2KW complete |
| 28 | Supply and fix electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc |
| 29 | Supply and fix electric instant water heater, ABS outer with SS inner tank and heating element upto 3 KW capacity 3 litre, suitable 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc |
| 30 | Supply and fixing in replacement thermostat all type of elect geyser available at site i.e (Clenta,bajaj,recold,crompton, havells)240 Volts AC temperature adjustable suitable for 25 to 50 Ltr electric water heater and making electrical connection all as specified and directed. |
| 31 | Supply & fixing Neon lamp (Red & Green) round / square in shape suitable for 25 / 35 / 50 liters capacity geysers making electrical connection at its original position including taking down old lights complete all as specified and directed. |
| 32 | Supply and fixing in replacement Base cover plate steel for mounting ofindicator lamp in existing shape and size suitable for 25 to 50 ltr capacity of electric water geyser. |
| 33 | Supply and fixing in replacement Stainless steel SS Braided flexible Hot &coldwater connection Hoses pipes tubes suitable forfor working temp of not less than 90 degree Centigrage of side, Size 18/24 incc long. |
| 34 | Supply and fixing in replacement inner shell ( inner tank) made out of stainless steel sheet 20 guage suitable for 25 Ltr electric water heater in existing shape and size complete all as specified and directed. |
| 35 | All as per serial item no 34here in before but 50 Ltr Electric water heater. |
| 36 | Supply and fixing in replacement unsv outer body covercomplete with Top and bottom cover, inspection plate of 25 Ltr electric water heater duly painted with super enamelled paint two coat over a red oxide steel primer complete. |
| 37 | All as per serial item no 36 here in before butfor 50 Ltr electric water heater. |
| 38 | Taking down existing glass wool and supply and fix new superior quality glass wool in geysers any capacity i.e 25/50 Ltr electric water heater all as specified and directed. |
| 39 | Supply and fixing in replacement inner base assy Chromium plated brass complete any shape and size with inlet, out let , thermostate slot, drain plugand clamp or bolts for fixing heating element as existing shape and size complete suitable for 25/50 Ltr electric water heater. |
| 40 | Taking down existing unsv copper flexible cable and supply and fixnew3 core copper flexible PVC insulated multistranded cable of size 4 Sqmm. |
| 41 | Supply and fixing in replacement 15 Amp plug top 3 pin including making electrical connection with existing cable complete |
| 42 | Supply and fixing in replacement base assy gasket in 25/35/50 ltr capacity electric water heater in any shape and size all as specified and directed. |
| 43 | Supply and fix in replacement safety valve suitable for 25 Ltrs t /50Ltrs capacity Gysers all as specified and directed. |
| 44 | Supply and fix in replacementfastner bolt as per site requirmement where is required all as per specified and as directed by Engr-in- charge. |
| 45 | Taking out defective/burnt outPVC Exhaust fan Motor of size150mm to 300mm (Bajaj, Crompton, Havells) and supply and fixing new PVC Exhaust fan coppermotor of existing makes/sape/size in OffrsJCOs/ORsMarried /OTM Accnunder GE (North). 230 volt, 50Hz single phase AC supply all as directed. |
| 46 | Supply and fixing in replacement of PVC rigid Exhaust fan plastic blade for 150-300mm including locking nut complete all as specified.As per sample/ existing. |
| 47 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting and making good disturbed surfaces of walls, floors etc complete. |
| 48 | Taking down carefully by unscrewing from boards / outlet boxes fittings and fixture such as,LED bulk head fitting, LED tube light fitting,switches, sockets, ceiling rose, regulators, bell, DBs/MCBs etc complete. |
| 49 | M&L for point wiring (light/Fan/bell point) with 1.5 Sq. mm PVC Insulated unsheathed FRLS multistranded copper conductor, medium grade ISI markedinto and including PVC concealed conduit 25mm dia medium grade with all accessories from terminal box to junction of ceiling and wall and rest of circuit conductor wire drwan in to and including suraface PVC rigid non metalic conduit for forlight/fanpoint controlled by one switch with and also including 1.5 sqmm continious earth wire connected to common earth dolly completed. |
| 50 | All as per item No. 49 here in before but point wiring One 3 pin socket outlet 5 amps on the same board with other switches, with cables 1.5 sq complete. |
| 51 | All as per item No. 49 here in before butpoint wiring One 3 pin socket outlet 5 amps independent board with other switches, with cables 1.5 sq complete. |
| 52 | All as per item No. 49 here in before but wire size 2.5 Sqmm to controlled the 3 pin 5 / 15 Amps socket outlet on independent board and providing earth continuity wire using PVC insulated, FRLS 1100 volts grade un sheathed single core stranded copper conductor cable of size 2.5 Sqmm complete all as specified and as directed. |
| 53 | S&Fin repair Switch Piano flush type single pole 5 Amps One way. |
| 54 | S&Fin repair Switch socket combination 2 in1 3pin 5/15 Amp o flush type single pole. |
| 55 | S&Fin repair Switch socket combination piano type 5 pin 5 Amps flush type complete. |
| 56 | S&Fin repair Ceiling rose,3 terminal, PVC / polycarbonet, isolated body complete. |
| 57 | S&Fin repair Electric bell (Ding dong) AC 230/250 volts grade single pole ISI marked, complete. |
| 58 | S&Fin repair switch pianoflush type for bell Push 5 Amps, complete. |
| 59 | S&Fin repair Electronic type fan regulator Stepped type, 240Volt flush type suitable for 1200/1400mm sweep ceiling fan complete. |
| 60 | S&Fin repair Socket outlet Two in one, 3/5 Pin piano type 5 Amp flush type complete. |
| 61 | S&Fin repair Switch Piano type single pole 16/20 Amps One way, complete. |
| 62 | S&Fin repair Socket outlet Two in one, 3/5 Pin piano type 16/20 Amp flush type complete. |
| 63 | Taking down fan, ceiling fan cable end, dismantling blades and kept in safe custody for refixing on same location all as specified and directed by engineer in charge. |
| 64 | Hanging /fixing only ceiling fan and connecting up including provision of cable from ceiling rose or connector to fan obtained from item No 63 here in before. |
| 65 | Supply and fixing LED light fitting mirror type with high out put diffuser 1 feet, 5 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete. |
| 66 | Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete. |
| 67 | S&FSupply and fixing LED lights fitting 1x 20W, 220V,AC decorative box type with driver, holder includingLED tube light connecting up with three core flexiblecopper conductor cable of suitable size from ceiling rose complete. |
| 68 | S & F LED light fitting 1x9W/1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size.complete. |
| 69 | Supply and fixing LED luminaire 600 mm x 600 mm,35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete. |
| 70 | S&F in repair decorative wall light fixture made up of polycarbonate, suitable for 9W LEDcomplete with LEDall as specified and as directed by engineer-in -charge |
| 71 | Sub main wiring with two run single core 4 sqmm FRLS copper conductor cable PVC insulated, unsheathed, 1100V grade including 25mm dia PVC concealed conduit casing & caping medium grade ISI marked with all accessories such as Tees, elbows, junctgion boxes etc, as required fixed on wall alongwith one run of 4 sqmm single core PVC FRLS insulated unsheathed copper conductor cable as continious earth wire and connecting to existing main switch board/distribution board complete including taking down unserviceable submain of any type/size and testing on completion etc fixed in replacement, complete all as specified and directed by engineer-in-charge.Note : Two run of 4 sqmm and one run 4 sqmm cable and one run of PVC conduit shall be measured as one RM |
| 72 | Sub main wiring with two run single core 4 sqmm FRLS copper conductor cable PVC insulated, unsheathed, 1100V grade including 25mm dia PVCcasing & caping medium grade ISI marked with all accessories such as Tees, elbows, junctgion boxes etc, as required fixed on wall alongwith one run of 4 sqmm single core PVC FRLS insulated unsheathed copper conductor cable as continious earth wire and connecting to existing main switch board/distribution board complete including taking down unserviceable submain of any type/size and testing on completion etc fixed in replacement, complete all as specified and directed by engineer-in-charge.Note : Two run of 4 sqmm and one run 4 sqmm cable and one run of PVC conduit shall be measured as one RM |
| 73 | Sub main wiring with two run single core 6 sqmm FRLS copper conductor cable PVC insulated, unsheathed, 1100V grade including 25mm dia PVC concealed conduit casing & caping medium grade ISI marked with all accessories such as Tees, elbows, junctgion boxes etc, as required fixed on wall alongwith one run of 6 sqmm single core PVC FRLS insulated unsheathed copper conductor cable as continious earth wire and connecting to existing main switch board/distribution board complete including taking down unserviceable submain of any type/size and testing on completion etc fixed in replacement, complete all as specified and directed by engineer-in-charge.Note : Two run of 6 sqmm and one run 6 sqmm cable and one run of PVC conduit shall be measured as one RM |
| 74 | Sub main wiring with two run single core 6 sqmm FRLS copper conductor cable PVC insulated, unsheathed, 1100V grade including 25mm dia PVC casing & caping medium grade ISI marked with all accessories such as Tees, elbows, junctgion boxes etc, as required fixed on wall alongwith one run of 6 sqmm single core PVC FRLS insulated unsheathed copper conductor cable as continious earth wire and connecting to existing main switch board/distribution board complete including taking down unserviceable submain of any type/size and testing on completion etc fixed in replacement, complete all as specified and directed by engineer-in-charge.Note : Two run of 6 sqmm and one run 6 sqmm cable and one run of PVC conduit shall be measured as one RM |
| 75 | S & Fsheetmetal VTPN MCB DBs bouble door 04way (8 + 12) with metaldoor415voltsgrade IP 43 Protection Grade fixed flush to wall complete including connections should be provide with necessary reducer lugs complete all. |
| 76 | S&FMCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 16 KA |
| 77 | S & F8 way single pole and neutral sheet steel powder coated Distribution board for MCBs fitted with 200A busbar , Neutral link ,Earth Bar and Din rail suitable for use on 240 V, 50 Hz supply double door |
| 78 | S&F in replacement 4 waysingle pole and neutral sheet steel powder coated distribution board for MCBs fitted with 200A bus bar neutral link Earth bar and din rail suitable for use on 240V, 50Hz supply double door SPN DB system complete. |
| 79 | S&F in replacement 12 waysingle pole and neutral sheet steel powder coated distribution board for MCBs fitted with bus bar neutral link Earth bar and din rail suitable for use on 240V, 50Hz supply double door SPN DB system complete. |
| 80 | S&F in replacement Triple pole and neutral sheet steel powder coated distribution board for MCBs fitted with 200A bus bar neutral link Earth bar and din rail suitable for use on 415V, 50Hz supply double door TPN DB system 4 Way all as specified and directed by engineer in charge. |
| 81 | S & F in repair isolator TPN100 Amps415 Volts 16 ka . |
| 82 | S & Fin repairMCCB 4 pole100 Amps415 Volts 16 ka |
| 83 | S&F in repair SPN MCB 40 to 63 Amp 10kA |
| 84 | S&F in repairMCB SP 6-32 Amps. |
| 85 | S&Fin repair MCB SP 40 Amps. |
| 86 | Supply and fixing LED street light fitting 25/35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp, GI bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66. |
| 87 | Supply andfix in repair LED light fitting 1x16 watts flame proof ,CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protectionwith die cast aluminum housing with heat resistant toughened glass with LED tube light fixtures driver,holders, connector etc. Complete. |
| 88 | Suplly and fix in repair energy saving LED garden light fitting,decorative,bollard typeofcapacity 9/11 watt with opal diffuser & aluminium reflector complete with all accessaries and fixing arrengement on PCC block of size 45mm X 45 mm alogwith suitable size of black GI pipe for mounting of as per fixing nuts,bolts and PVC insulated aluminium conductor,stranded type of size 4.0 sqmm,2 -core. |
| 89 | S&Fin repair for MCB TPN 63 Amp, 415 Volts 10kA. |
| 90 | S&F in repair Metal clad Plug socket single pole enclosure with two pin earth plug and socket with one single 20 Amp , 240 volts MCB complete all as specified and directed by engineer incharge. |
| 91 | S&F in repair on load change over switch 4 pole, 415V in sheet metal enclosure 4 pole of capacity 100 Amps all as specified and as directed by EIC |
| 92 | Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specifiedand directed by EIC. |
| 93 | S&F in repair rigid non - metalic PVC casing caping of 25/12mm inclusive of all elbow, tees,etc complete all as per the direction of Engr-in-Charge. |