Tender For Automation Of Water Supply At Meerut; 1 PART-IDesign, Develop, Integrate and Commission SCADA System along with various analysing equipment for water supply System as indicated in the layout diagram enclosed and as per details attached at Table. The SCADA system shallcomprise of following:- 2 (a) Master Control station with personal coumputer with latest processor and monitor of suitable size.(b) UPS with half an hour backup(c) Laser Printer(d) Server(e) Data Gateway(f) SCADA software which can be operated, programmed and modified by agencies other than developer(g) PLC/Microprocessor Controllers with indoor/outdoor applications for water sensing display, pump oprations with RTU/without RTU or Microprocessor controller and microprocessor transmitter.(h) Suitable communication system including payment of bills to telecom service provider.(j) Motorised butterfly valves(k) Pressure transmitters(l) Ultrasonic sensors/ Radio frequency sensors(m) Flow meters and switches(n) Air Release solendoid valves(o) Smart motor protection(p) Online residual Cholorine analyser(q) Level Censor(r) Interconnection motorise valves 3 Notes : (i) Design of Communication System shallbe done by the bidder. Cloud based server/ data storage/ communication shall not be used and only local server based system shall be designed.(ii) The cost of each item shall also be attached to arrive at pricing in case of some addition/reduction at site.(iii) Operating system, system software and programming shall not be interllectual property of any agency.(iv) The memory in the hard disk shall be suitable for six months data. The backup storage device/devices shall be provided for archiving of data more than six months old.(v) In case of addition of installations, the system shall be capable of integrating the same.(vi) The responsibility of the agency is restricted to intimate mechanical and electrical failures such as failure of pumps, leakages etc. Such repairs shall be carried out by MES.(vii)Operation and maintenance charges tobe seperately.(viii) The SCADA system should have provision of both manual and automatic operation of installations.(ix)Third party inspection of whole scheme and SCADA system for ensuring satisfactory and smooth functioning of SCADA system shall be carried out by Central Govt approved agency / firm before issuing the completion certificate to the contractor. 4 Note for Maintenance and operations for 10 Years :-(a)Operate SCADA system during Defect Liability Period for two years after completion of work without manning ( Contractor to provide month wise breakdown details of data / information) all as specified and as directed by Engineer-in- charge.(b) Operation and comprehensive mainenance of SCADA systemsincluding cost of spares for 08 years postdefect liability period,operation including payment of bills by telecom service provider (Contractor to provide month-wise breakdown details of data / information). all as specified and as directed by Engineer-in- charge. 5 NOTE :- COMPONENT OF PAYMENT FOR ITEM NO -1.(a) Sucessfully installation and operation of SCADA on completion of work :- 71.44 % of quoted rate of item No -1, Paymentto be regulated as per clause No 4 (a)of Particular Specification of (Water Supply SCADA) (b)1st year under defect liability period after completion :- 1.44 % of quoted rate of item No -1. 6 (c)2nd year under defect liability period after completion :- 1.44 % of quoted rate of item No -1. (d)1st year after defect liability period after completion :- 2.85 % of quoted rate of item No -1. (e)2nd year after defect liability period after completion :- 2.85 % of quoted rate of item No -1. 7 (f)3rd year after defect liability period after completion :- 2.85 % of quoted rate of item No -1. (g)4th year after defect liability period after completion :- 2.85 % of quoted rate of item No -1.(g)5th year after defect liability period after completion :- 3.57 % of quoted rate of item No -1. 8 (f)6th year after defect liability period after completion :- 3.57 % of quoted rate of item No -1. (g)7th year after defect liability period after completion :- 3.57 % of quoted rate of item No -1.(g)8th year after defect liability period after completion :- 3.57 % of quoted rate of item No -1. 9 PART-IISupplying , installation , testing and commissioningsubmersible pump, electric driven 415V, TP of suitable capacitysuitable for 250mm dia bore well (Casing pipe size 300mm) capacity 1200 LPM at 70 Mtr head . 10 Supplying , installation , testing and commissioning submersible pump, electric driven 415V, TP of suitable capacity suitable for 250mm dia bore well (Casing pipe size 350mm) capacity 800 LPM at 70 Mtr head . 11 Supplying , installation , testing and commissioning submersible pump, electric driven 415V, TP of suitable capacity suitable for 250mm dia bore well (Casing pipe size 350mm) capacity 1500 LPM at 70 Mtr head. 12 Supplying , installation , testing and commissioning submersible pump, electric driven 415V, TP of suitable capacity suitable for 250mm dia bore well (Casing pipe size 350mm) capacity 2000 LPM at 70 Mtr head. 13 Supply and fixing Soft Starter, 3 Phase, 415 Volt, 50Hzof suitable for item No 2 of BOQwith contactor of suitable rating , fuse with base duly ON, OFF, Trip indicating light, push button, digital Amp meter with CT complete with fixing including suitable size of copper cable with lugs all as directed at site. 14 Supply and fixing Soft Starter, 3 Phase, 415 Volt, 50Hzof suitable for item No 3 of BOQwith contactor of suitable rating , fuse with base duly ON, OFF, Trip indicating light, push button, digital Amp meter with CT complete with fixing including suitable size of copper cable with lugs all as directed at site. 15 Supply and fixing Soft Starter, 3 Phase, 415 Volt, 50Hzof suitable for item No 4 of BOQwith contactor of suitable rating , fuse with base duly ON, OFF, Trip indicating light, push button, digital Amp meter with CT complete with fixing including suitable size of copper cable with lugs all as directed at site. 16 Supply and fixing Soft Starter, 3 Phase, 415 Volt, 50Hzof suitable for item No 5 of BOQwith contactor of suitable rating , fuse with base duly ON, OFF, Trip indicating light, push button, digital Amp meter with CT complete with fixing including suitable size of copper cable with lugs all as directed at site. 17 Taking out of old unsv sluice / NRV valve of any capacity 18 S&F Non Return Valveflanged end of class 1.6 PN 150mm (6) dia, complete as directed by Engr-in-Charge. 19 S&F Non return Valve flanged of class 1.6 PN 100mm (4) dia, complete as directed by Engr-in-Charge. Note : The rate quoted againstitem No- 11 & 12 shall be inclusive of jointing and jointing materials e.g rubber, mild steel nuts, bolts and washer etc complete. 20 Taking out of old Unsv column pipe of size 150 / 100mm dia bore 21 Supply and lowering in borewell, MS ERW IS-4270(2001) Column pipe150 mm bore 4.8 mm thick in 3 mtr length both end MS flanged 10 mm thick with cut for passing the submersible cable including suitable size of nuts, bolts, washers and rubber gasket complete all as specified and directed by Engineer-in-Charge. 22 Supply and lowering in borewell, MS ERW IS-4270(2001) Column pipe100 mm bore 4.8 mm thick in 3 mtr length both end MS flanged 10 mm thick with cut for passing the submersible cable including suitable size of nuts, bolts, washers and rubber gasket complete all as specified and directed by Engineer-in-Charge. 23 Material and labour for submersible flat copper cable 3 core 35 Sqmm multi stranded 1100 Volt grade with electric connectionincluding suitable size of copper thimble, nuts, bolts, washerscomplete all as specified and directed by Engineer-in-Charge. 24 Material and labour for submersible flat copper cable 3 core 16 Sqmm multi stranded 1100 Volt grade with electric connectionincluding suitable size of copper thimble, nuts, bolts, washerscomplete all as specified and directed by Engineer-in-Charge. 25 Supply and fixing Heavy duty chemical Dosing system plunger type suitable to inject solution upto 25 LPH working pressure 10 Kg/Cm2 comprising dosing pump coupled with three phase electric motor of capacity 0.5 HP, 1440 RPM assembly with agitator in one motor, agitator with SS sweep blade duly FRP coated of FRP tank 150 Ltrs capacity.complete unit mounted on heavy duty MS fabricated frame complete with painting with anticorrosive paint connecting all item, chemical grade PVC NRV, any pipe, valve alongwith control panel of dosing pump of powder coated MS fabricated box consisting of led indicator, digital volt meter Amp meter, single phase preventor, High voltage low voltage protection. Note:-(i) Complete unit shall be mounted heavy duty MS fabricated frame complete with painting with anticorrosive paint alongwith DOL motor starter for dosing pump, including inlet/ outlet check valve with installation.(ii) Provide original test certificate from manufacturer with ISO 9001-2015 authorised certificates.(iii) Foundation work and pipe line work, gate valve, starter, drilling and welding on main pipe line work etc are inclusive in the quoted rate. 26 S & F in repairs SPN DB, IP Pritection, double door, 240 Volt, 4 way with 200 amp rated bus bar complete all as specified and directed 27 S & F in repairs TPN Isolator, 415 Volt,complete all as specified and directed 28 M&L Sub main wiring with 4.0 sqmm (Nominal area) FRLS with four runs of single core PVC insulated stranded unsheathed copper conductor cable upto and including 1100 V grade drawn through in PVC conduit fixed to wall/ ceilling etc incl one runs 4.0 sqmm (nominal area) single core, FRLS PVC insulated stranded unsheathed copper conductor as earth wire and duly connected to common earth point etc. complete all as specifed and as directed.Note: four runs of 4 sqmm single core cable, one run of 4.0 sqmm earth continuity wire and one run of PVC conduit shall be measured as one meter. 29 Excavation in trenches in soft/lose soil n.exc. 1.5M wide & n exc 1.5M deep for laying of GI/CI pipe line & getting out including forming bottom surface all as specified and directed. 30 Returning, filling in, trenches including spreading, levelling, watering and well ramming in layer n.exc. 250 mm in any type of soil after the pipe laid & tested complete all as specified and directed. 31 Removing excavated surplus soil to a distance n.exc. 50mtr and depositing where directed at a level n.exc. 1.5 m above the starting point all as specified and directed 32 Taking out old CI pipe of 100 mm dia including all fitting with spigot and socket ends and lead jointed complete all as specified and directed 33 Taking out old CI pipe of 150 mm dia including all fitting with spigot and socket ends and lead jointed complete all as specified and directed 34 Taking out old CI pipe of 200 mm dia including all fitting with spigot and socket ends and lead jointed complete all as specified and directed 35 Supply and laying DI pipes of size 100 mm dia with spigot and socket ends centifugally cast (spun) class K9 in any length, externally coated with metallic zink coating finished with bituminous paint complete all as specified and directed 36 Supply and laying DI pipes of size 150 mm dia with spigot and socket ends centifugally cast (spun) class K9 in any length, externally coated with metallic zink coating finished with bituminous paint complete all as specified and directed 37 Supply and laying DI pipes of size 200 mm dia with spigot and socket ends centifugally cast (spun) class K9 in any length, externally coated with metallic zink coating finished with bituminous paint complete all as specified and directed 38 S & F sluice valve PN-1, 150 mm dia with stainless steelspindle conforming to IS-14846-2000 doubles flange and including jointing material like suitable size of nuts, bolts, washer and rubber gasket complete all as specified and directed. 39 S & F sluice valve PN-1, 100 mm dia with stainless steelspindle conforming to IS-14846-2000 doubles flange and including jointing material like suitable size of nuts, bolts, washer and rubber gasket complete all as specified and directed. 40 S & F sluice valve PN-1, 200 mm dia with stainless steelspindle conforming to IS-14846-2000 doubles flange and including jointing material like suitable size of nuts, bolts, washer and rubber gasket complete all as specified and directed. 41 M & L DI/CISpecials class B as per ISsuch as bends,tappers,any type branches cross all sockets and spigot collar caps and plug up to 150mm bore all as specified and as directed 42 M&L for construction of brick masonary valve pit of size 1.00x1.00x 1.00mm incl necessary excavation and earth work and disposal of surplus soil upto 50m, BB work in CM 1:6, 10mm plastering internally in cement mortor 1:4, PCC 1:2:4 100mm thick at bottom and at top of wall as copling of valve pit, MS sheet 3mm thick cover double door fixed in angle iron frame 35mmX35mmX5mm and 40mmX40mmX5mm at bottom for accomadating cover duly embaded in PCC coping with 25X3mm FI lugs 300mm long, one on each side, 12mm dia MS handle made to shape, locking arrangement with 1 No.Lock with two keys NAVTAL/Godrej/Harrison 50mm incl two coats of Synthetic enamel paint over a coat of red oxide zinc chrome primer on steel surface complete all as specified and shown on drawing. 43 Note : Tenderers may note that amount of credit Rs 06,74,350.00 will be deducted from the total amount arrived, at the time of Acceptance of contract.