| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 2 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 3 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 4 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 5 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 6 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ sub main wiring/ cable as required. |
| 7 | Supplying and fixing 6 way double door, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 8 | Supplying and fixing of following rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 9 | Single pole |
| 10 | Single Pole & neutral |
| 11 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 12 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories includingsafety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 13 | Supply of XLPE Power cable of size 2x10 sq.mm of 1.1 KV grade armoured Al. Cable Compulsary ISI made Confirming to IS : 7098/ Pat -I / 88 with amendment no Iof reputed make as required. |
| 14 | Laying of one No. PVC insulated & PVC sheathed/XLPE POWER CABLE of 1.1 kv grade armoured Al. cablecompulsory ISI mark confirming to IS:7098/ PART –I / 88 with amendment no.1 as required direct in ground i/c excavation, sand cushioning, protective covering and refilling the trench etc. as reqd (upto 35 sq mm) |
| 15 | CABLE SIZE 2 X 10 SQ.MM |
| 16 | Laying of one number additional PVC insulated and PVC sheathed / XLPE XLPE POWER CABLE of 1.1 kv grade armoured Al. cablecompulsory ISI mark confirming to IS:7098/ PART –I / 88 with amendment no.1 in the existing RCC/ HUME/ METAL pipe as required (upto 35 sq mm). |
| 17 | CABLE SIZE 2 X 10 SQ.MM |
| 18 | Laying of one number additional PVC insulated and PVC sheathed / XLPE XLPE POWER CABLE of 1.1 kv grade armoured Al. cablecompulsory ISI mark confirming to IS:7098/ PART –I / 88 with amendment no.1 (clamped with 1mm thick saddle) on the wall surface as reqd (upto 35 sq mm) |
| 19 | CABLE SIZE 2 X 10 SQ.MM |
| 20 | Supply of 45 Watt LED Street light made up with pressure die cast aluminium housing with weather proof conditions suitable for all weathers, toughened clear glass, high power LEDs with secondary optics, SPD 5 KV/10KV and IP 66 protection. The luminaire should have the efficacy greater than or equal to 100 lumens per Watt of make of reputed brand as required |
| 21 | Supplying and fixing of 32 mm dia X 1.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required |
| 22 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulatedand PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as requireda) 2x10 sq mm cable (19 mm) |
| 23 | S/I/T/C of highly robust industrial luminaire suitable for 1xT8 tube and single20/22 Watt LED glass T8 tube with in build driver and efficacy of 100 lm/W and Installation, testing and commissioning of pre-wired,LED fitting,complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc.as required |
| 24 | Supply of 300 mm sweep Medium Duty Exhaust fan of 1400 RPM, Metallic Grey alongwith all accessories as required. |
| 25 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required |
| 26 | Jointing copper/G.I. tape (with another copper/G.I tape, base of the finial or any other metallic object) by riveting/ nut bolting/ sweating and soldering etc as required |
| 27 | Providing and fixing G.I. tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For Horizontal Run) |
| 28 | Providing and fixing G.I. tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For vertical Run) |
| 29 | Providing and fixing testing joint, made of 20 mm x 3 mm thick G.I. strip, 125 mm long, with 4 nos of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |