CONSTRUCTION OF 220/132 KV, 1X160 MVA GSS at SUMERPUR (Distt.- PALI) (UPGRADATION) INCLUDING SUPPLY OF ALL EQUIPMENTS/MATERIALS, ERECTION (INCLUDING CIVIL WORKS), TESTING AND COMMISSIONING- 1 MAIN MATERIAL/ ITEMS 2 Circuit Breakers 3 220 kV Circuit Breakers 4 220kV circuit breakers (3 Ph.) Along with support Structure 5 2500 A, 50 kA 6 132 kV Circuit Breakers 7 132 kV circuit breakers (3 Ph.) Along with support Structure 8 1250 A, 40 kA 9 33 kV Circuit Breakers 10 33 kV circuit breakers (3 Ph.) Along with support Structure 11 1600 A, 31.5 kA 12 Instrument Transformers 13 Capacitor Voltage Transformer 14 Single-Phase, 220 kV, 4400 pf CVT 15 Single Phase 132 kV , 4400 pf CVT 16 33 kV Potential Transformer 17 33/√3 kV /110-110√3 18 Current Transformer (1-Phase) 19 220 kV CT 20 1000/1 A, 5C 21 132 kV CT 22 1000/1 A, 3C 23 500/1 A, 3C 24 33 kV CT 25 1000/1 A, 4C 26 500/1A, 2C 27 C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II) 28 New Substation 29 Control Panel for 220 kV Transformer (220 kV Side) Type: SAS-THCB 30 Relay Panel for 220 kV Transformer (for both HV & MV) Type: SAS-THRB 31 Control Panel for 220 kV Feeder Type: SAS-FCB 32 Relay Panelfor 220 kV Feeder Type: SAS-FRB 33 Control Panel for 220 kV Bus Coupler Type: SAS-BCCB 34 Relay Panel for 220 kV Bus Coupler Type: SAS-BCRB 35 220 kV Busbar Protection Relay Panel Type: SAS-BBRB 36 Control Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLCB 37 Relay Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLRB 38 Control and Relay Panel for 1x 50/31.5/25 MVA, 132/33 kV Power Transformer Type SAS-TCRA 39 Control Panel for 132 kV Feeder Type SAS-FCA 40 Relay Panel for 132 kV Feeder Type SAS-FRA 41 Control and Relay Panel for 132 kV Bus-Coupler Type SAS-BCRA 42 Control and Protection Panel for 33 kVFeeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD 43 Station HMI [Industrial grade Computer with 21TFT monitor as per specification requirements] 44 Station HMI (Hot Standby)[Industrial grade Computer with 21TFT monitor as per specification requirements] 45 HMI View Node[Industrial grad Computer with 21TFT monitor as per specification requirements] 46 A3 Size B&W Laser Printer 47 Substation Automation System Network Panel Type SAS-NW 48 Modems (both sending and Receiving End) for communication to RCC & Sub SLDC for PLCC] 49 Data Concentrator Unit (DCU) at Substation for RAS mounted in suitable enclosure & fully wired 50 Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification. 51 Substation Auxiliary Monitoring Panel Type SAS-SAMP 52 Other Items: 53 Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements. 54 Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards. 55 Surge Arresters 56 220 kV LA 57 132 kV LA 58 33 kV LA 59 Substation LT Transformer 60 33/ 0.433 kV, 250 kVA LT transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil 61 Batteries & Battery Charger 62 Batteries (Sizing shall be as per requirement of technical specification) 63 220 V [Min. 600 AH] 64 48 V [Min. 600 AH] 65 Battery Charger System 66 220 V Float and Boost 67 50 V Float and Boost 68 Lighting System 69 Outdoor Lighting & other Works 70 Lighting Fixture Type FL-1 71 Lighting Fixture Type FL-2 72 Outdoor Receptacle 73 Type-RP 74 Type-RO 75 Substation Premises Lighting 76 Lighting poles 77 Type-L1 78 Type-D1 79 Street Lighting Type-SL-L1 for mounting on poles 80 Street Lighting Type-SL-D1 for mounting on Poles 81 Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast and Other Loaction as designated complete with all controgears and accessories, items etc. 82 Lighting PanelType ACP-2 as per technical specification 83 Lighting PanelType ACP-3 as per technical specification 84 Indoor Lighting & Other Works 85 Electrification 86 Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room,Hall and administrative office building as per the requirements of the specifications 87 Illumiation 88 Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories andmounting arrangements) 89 Indoor Lignting Panels 90 Lighting Panel (Indoor)Type ACP-1 as per technical specification 91 Lighting Panel (Indoor)Type DCP as per technical specification 92 Wall mounted fans Approx. 400 mm sweep 93 Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator 94 Exhaust Fans 95 Fire Fighting System 96 Nitrogen Injection Fire Protection System for Auto Transformer (160 MVA ) complete in all respects. 97 DCP Type 98 i) 5 Kg. 99 ii) 10 Kg. 100 Carbon di oxide type – 6 Liters. 101 Foam Type- 9 Liters 102 Sand type 103 i) GI Buckets 9 liters capacity 104 ii) Steel Stands for four buckets 105 Air Conditioning System 106 Air Conditioning for the Rooms specified in the specifications 107 1.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building] 108 Power Cables(XLPE) 109 1Cx630 sq.mm 110 3.5Cx300 sq.mm 111 Power Cable(PVC) 112 1Cx150 sq.mm 113 3.5Cx70 sq.mm 114 3.5Cx35 sq.mm 115 4Cx16 sq.mm 116 4C x 6 Sq. mm 117 2C x 6 Sq. mm 118 Control Cable (PVC) 119 4 CX4 Sq. mm 120 3Cx2.5 sq.mm 121 5Cx2.5 sq.mm 122 7Cx2.5 sq.mm 123 10Cx2.5 sq.mm 124 14Cx2.5 sq.mm 125 19Cx2.5 sq.mm 126 Substation Structures 127 Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]: 128 Non-Standard type Pipe Support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe Support structure as per specification requirements] 129 Isolators 130 220 kV (3-Phase) (Horizontal DOUBLE BREAK) 131 1600A, 50KA, isolator with one E/S 132 Post insulators for above Isolator 133 1600A, 50KA, isolator without E/S 134 Post insulators for above Isolator 135 1600A, 50KA, isolator without E/S (TANDEM Type) 136 Post insulators for above Isolator 137 132 kV (3-Phase) (Horizontal DOUBLE BREAK) 138 1250A, isolator with one E/S 139 Post insulators for above Isolator 140 1250Aisolator without E/S 141 Post insulators for above Isolator 142 33 kV (3-Phase) (Horizontal DOUBLE BREAK) 143 1250A, isolator without E/S 144 Post insulators for above Isolator 145 800 Aisolator without E/S 146 Post insulators for above Isolator 147 800Aisolator withE/S 148 Post insulators for above Isolator 149 Switchyard Erection 150 Busbar & Interconnections 151 New Substation/ Switchyard 152 220 kV Switchyard Works: 153 Main-I Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/PorcelainLong Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays] 154 Main-II Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Pocelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays] 155 Aux Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string(DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays] 156 220 kV Overhead Jack Bus (for DMT Layout) on Twin ACSR Zebra(Bus-Coupler Bay)/ Single ACSR Zebra (Transformer/ Line on ACSR Zebra) with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, clamps, connectors, spacers etc. as per Substation Layout arrangementand specification requirements[ for 1 Bay] 157 Twin ACSR Zebra 158 Single ACSR Zebra 159 Equipment Interconnections to Main Bus, Overhead Bus including Single ACSR Zebra (for Line), Twin ACSR Zebra (forTransformer bay & B/C Bay), bus-bar materials, clamps,connectors, spacers, corona shields, including equipment connectors, Junction box including of all accessories etc. for the following: 160 220 kV DMT-type layout 161 Line bay 162 Transformer bay 163 Bus-Coupler 164 Bus CVT Interconnections to Main Buses including Single ACSR Zebra, clamps,connectors, junction box including of all accessories etc. 165 132 kV Switchyard Works: 166 Main Bus: 132 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulator, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays] 167 Aux Bus: 132 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays] 168 132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay),Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangementand specification requirements[ for 1 Bay] 169 Twin ACSR Zebra 170 Single ACSR Zebra 171 Single Panther 172 Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV TransformerBay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps,connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following: 173 132 kV Main & Aux-type layout 174 Line bay 175 Transformer bay 176 Bus-Coupler 177 Bus CVT Interconnections to Main Bus including Single ACSR Zebra, clamps,connectors, junction box including of all accessories etc. 178 33 kV Switchyard Works: 179 Aux Bus: 33 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]] 180 33 kV Overhead Jack Bus for Transformer Incomer (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangementand specification requirements[ for 1 Bay] 181 Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps,connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following: 182 33 kV Main & Aux-type layout 183 Line bay 184 Transformer bay 185 Bus-Coupler 186 LT Transformer connection with ACSR Panther conductor, 33 kV DO Fuse Set alongwith required Clamp/connectors 187 Bus PT Interconnections to Main Bus including Single ACSR Panther , clamps,connectors, junction box including of all accessories etc. 188 Bus Post Insulators (BPI) 189 220 kV 190 132 kV 191 33 kV 192 Earthing & Lightning Protection System 193 Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area 194 40 mm Dia MS Rod 195 40mm Dia, 3.2 M Long MS Rod Earth Electrodes Directly Driven. 196 40mm Dia, 8 M Long MS Rod Earth Electrodes Directly Driven. 197 40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works 198 75X12 mm GS Flat 199 50X6 mm GS Flat 200 Earth Enhancing Compound for treated pits as above and other requirement as per specification 201 Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 75x12 mm GS Flat and 50x6 mm GS flat 202 Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats 203 Earth Wire for Shielding Protection of Switchyard 204 7/3.15 Galvenized Steel Wire 205 Earthwire tension clamps with D Shackle assembly 206 PG calmp to suit 7/3.15 mm GS earth wire 207 Cleat clamp on structure to suit 7/3.15 mm GS earth wire/ 75 X 12 mm GS Flat 208 Pad clamp on structure to suit 7/3.15 mm earth wire and 75 x 12 GS flat 209 Lug to suit 7/3.15 mm earth wire 210 Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire 211 Bay Marshalling KIOSK 212 200 way (Stud Type Connectors) 213 AC Distribution Boxes (Outdoor Type) 214 Outdoor AC Distbibution Box (Double Front type) 215 Outdoor AC Distbibution Box (Single Front type) 216 Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building] 217 Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washersetc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works] 218 LT Switchgear 219 LT AC Main Panel 220 LT AC Distribution Board 221 Main Lighting Distribution Board 222 Emergency Lighting Distribution Board 223 220VDCDB 224 48V DCDB 225 PLCC EQUIPMENTS 226 220 kV Wave trap (2000A, 0.5 mH, 40 kA) 227 132 kV wave trap (1250A, 0.5 mH, 40 kA) 228 VFT equipment (Modem) suitable for transmission of Data through PLCC links based on frequency shift keying modulation techniques programmable for both baud rate from 50 Baud to 2400 Baud and center frequency through switches or jumpers (A.F. Shift Channel) 229 SSB four Channel Carrier Set (40 W) suitable for transmitting Data and super imposed channels along with Remote subscriber facility and emergency calling set. 230 A.F. Protection coupler microprocessor based suitable for Four commands. 231 Coupling Devices for Phase to Phase coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level. 232 Coupling Devices for Phase to Ground coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level. 233 HF Armoured Coaxial cable having 75 Ohms unbalanced impendance. 234 Microprocessor based 32/16 line Electronic Private Automatic Exchange (EPAX) with PLCC interphasing facility 235 Telephone Sets (Push Button Type) 236 5 Pair jelly filled armoured telephone cable having copper conductor of Dia. 0.5 mm 237 5 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm 238 TESTING & MEASURING INSTRUMENTS, TOOLS & TACKLES AND MISCELLANEOUS ITEMS 239 (A) TESTING EQUIPMENT/ INSTRUMENTS [This shall consist of all the standard accessories, cables, software etc. required for satisfactory operation of equipment meeting functional requirements] 240 Insulation Tester (5000 Volts, Digital) 241 SF6 Leakage Detector 242 Digital Multimeter 243 Digital Clamp Meter 244 PLCC Maintenance/Testing Equipments: 245 200Hz to 620KHz selective level meter including impedance return loss measuring attachments compatible with level generator (at sl.ii below) 246 Level generator with a range at 50Hz to 620kHz including facility for synchronization with SLM 247 8 digit time interval & frequency counter with the frequency range of 10 Hz to 10MHz & timer range of 1 microsec to 1 sec in decade steps. 248 Dual range 15 MHz oscilloscope with a display screen 8x10 sq.cm and the input impedance of 1 M ohm/25 pF with a deflection coefficient of 5Mv/div to 20 V/div. 249 4-1/2 digit LCD Multimeter with input impedance of 10Mohm & with a range of 0.1 mV to 1000 V DC, 0.1mV to 600v AC, 0-10 AMP AC,(40hz to 10KHz) & 0-20 Mohm With builtin power –supply. 250 Print testing Kit for PLCC terminal, protection coupler, EPAX , As per specifications appended at Annexure- V2-P3-S19-2, Volume-II, Part 3, Section-XIX 251 (B) Maintenance Tools& Tackles 252 Oil Sampling Bottle (1 Liter Capacity) 253 Vaccum Cleaner 254 Telescopic ladder aluminium 6 meter height 255 Ring spanner set 256 Tube spanner set 257 Pipe wrench 24 inch 258 Pipe wrench 18 inch 259 Hydraulic crimping tools up to 630 sq.mm 260 Threading die set for pipe threading 261 Welding machine (arc welding) 10kVA 262 Heavy duty drilling machine 263 Bench Vice 264 Insulated cuttingplier 12 inch 265 Insulated cuttingplier8 inch 266 Screw driver 18 inch 267 Screw driver 12 inch 268 Hammer 8 lbs 269 Hammer 2 lbs 270 Chain pulley block 5 ton 271 Pipe derrick 272 Allen Keys 273 Box Spanners 274 (C )Office and Miscellaneous Equipments/ Items 275 Insulation Rubber mat (1mX2mX 12 mm) 276 Isulation Rubber Gloves (15 kV Tested) 277 Furniturefor Control Room Building: 278 SCADA Room Furniture (Control Desk for specified consoles and Revolving Chair) matching with the overall interiors as per specification 279 Executive Desk bulit in wood and steel with lockable drawings on both side (6 feetX2 ½ feetx 2 ½ feet) 280 Junior executive table with three drawings on right side One Cup board left side with prelaminated decolam top 20mm thick over painted M.S. Frame ( 4 ½ feet x 2 ½ feetx 2 ½ feet). 281 Library Shelf with Glass Door (min 4 Shelf) 282 Steel tubular “S” type with continuous and one feet dia 14guage pipe, cane seat backing, teak wood with quality cane. 283 Archival Storage 4 Drive Type 284 Lateral Filing Cabinets 285 3 Drawer Unit 286 4 Drawer Unit 287 Steel Almirah of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system. 288 Steel Almirah (with Glass doors) of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system. 289 Minor Almirah of size 4 ½ feet x30 inch x 17 inch with three shelves making four compartments in 22 guage or better with two waylocking system. 290 Steel rack of size 5 feet x 3 feet x 16 inches with six shelves making five compartments (22 guage). 291 Steel file trays of size 16 inches x11 inches x 3 inches of guage 14 SWG. 292 Steel stools of size 15 inch x15 inch x 18 inch square pipe 16 guage 293 Steel waste paper baskets of size 12 inch (H) and Approx. 10 inch Dia Round. 294 Key board (wooden) with Glass door 295 First Aid Box 296 Shock Treatment Chart [Laminated with Frame] 297 Safety Instruction Boards [ Laminated with Frame] 298 (D) Drinking Water Arrangement 299 Water Cooler (Storage type, Storage Capacity 40 Ltr, Cooling Capcity 20 Ltr./hr) 300 RO/ Water Purifier 301 Refrigirator (380 Lt.) 302 Substation Name Board [1 No. Glow Type & 1 No. Painted Type] [Size and Color etc. be got approved from owner] 303 Danger Plate [Size and Color etc. be got approved from owner] 304 Add: Any other supply item, if any, bidder may require completing the substation as per specification requirements.