| 1 | Attending of complaints from 0900 hrs to 1700 hrs by deployingelectrician along with helpersfor checking of existing electrical items including carrying out repairs such as tightening of loose electric connections, nuts, bolts, screws, repair/ replacement of switches, sockets, switch boards ceiling fans/exhaust fan, DB wiring etc as required to make the item functional and to ensure contiunous electric supply complete as specified and directed by Engr-in-Charge. Note:(a) Replacement of electric fitting shall be mesured andpaid for seperately under respective items.(b) Rate quoted deemed to be inclusive of T&P etc.(c) The safteyand insurance of persons/helper engaged in Execution shall be responsibility of contractor.(d) As the Nos of complaints shall be on required basis the financial effect to this is deemed to be included in the rate quoted.(e) In case of failure on the part of contractor for attending any complaint within 48 hours, a penalty shall be imposed @ Rs 100/- per complaint per day and recovered from his dues. |
| 2 | Taking down carefully aluminium / copper point wiring (light / fan / socket or power) while not disturbing existing conduit complete including fitting such as switches, ceiling roses, socket, light fittings, regulators etc complete and making good disturbed surfaces of walls and floors. |
| 3 | Taking down sub main wiring of two single core PVC cable PVC insulated4 / 6 sqmm including conduit or wooden batten and remove from the site of work and making good the disturbed surfaces of wall or floor etc. as directed by Engineer-in-Charge. |
| 4 | Taking down main switch / DB and making good the disturbed surface as directed by Engineer-In-Charge. |
| 5 | M&L for point wiring with PVC insulated, unsheathed cable single core multistranded copper conductor FRLS cable 1.5 sqmm size, 1100V grade, drawn into existing PVC rigid concealed conduit medium grade (ISI marked) including PVC unsheathed cable single core copper FRLS conductor 1.5 Sqmm as continuous earth wire and including pressed MS sheet sunken box 1.6 mm thick with 3 mm thick laminated bakelite sheet all as specified.a) One light / fan / call bell point controlled by one, one way switch. |
| 6 | b) Do all as per Ser item No -5 above but for 5 amps socket on independent board |
| 7 | c) Do all as per Ser item No- 5 above but for 5 amps socket on same board |
| 8 | Do all as per ser item No- 5 above but with 2.5 sq mm cable for 15 amps switch socket combination outlet on independent board complete all as specified and directed. |
| 9 | M&L for point wiring with PVC insulated, unsheathed cable single core multistranded copper conductor FRLS cable 1.5 sqmm size, 1100V grade, drawn into and including PVC rigid concealed conduit medium grade (ISI marked) including PVC unsheathed cable single core copper FRLS conductor 1.5 Sqmm as continuous earth wire and including pressed MS sheet sunken box 1.6 mm thick with 3 mm thick laminated bakelite sheet one light / fan / call bell point controlled by one, one way switch.all as specified.a) One light / fan / call bell point controlled by one, one way switch. |
| 10 | b) Do all as per Ser item No -9 above but for 5 amps socket on independent board |
| 11 | c) Do all as per Ser item No- 9 above but for 5 amps socket on same board |
| 12 | Do all as per ser item No- 9 above but with 2.5 sq mm cable for 15 amps switch socket combination outlet on independent board complete all as specified and directed. |
| 13 | M&L for point wiring with 1.5 sqmm, PVC insulated but sheathed, stranded copper conductor single core FRLS cable, IS-694 marked, drawn through and including non metallic rigid PVC concealed conduit medium grade 20mm dia (minimum) or higher size as specified and cutting chasing on wall complete with all PVC conduit accessories such as socket, elbow, junction box, bell mouth, reducer, bend and flexible conduit etc/ fittings ISI marked for modular fittings andbrass screws and cup washers including 1.5 sqmm stranded copper conductor PVC insulated FRLS cable green in colour as continuous earth conductor connected to common earth and earth dolly with all accessories complete all as specified and directed.Note : Cost of Metal boxes and modular accessories like cover plates will be paid seprately in respective items)(a)Fan point/ exhaust fan point / one light point / bell/ buzzer controlled by one switch/ bell push. |
| 14 | (b) One socket outet point 5 amps on the same board. |
| 15 | (c) One socket outet point 5 amps on the independent board. |
| 16 | All as Ser item 13.00 here in before but with 2.5 sq mm wire and earth wire (green colour) of 2.5 sq mm for 3 Pin 15 Amp modular type socket outlet. |
| 17 | Supply and fixing modular metal flush box 1/2 module complete all as specified and directed. |
| 18 | Supply and fixing modular metal flush box 3 module complete all as specified and directed. |
| 19 | Supply and fixing modular metal flush box 4 module complete all as specified and directed. |
| 20 | Supply and fixing modular metal flush box 6 module complete all as specified and directed. |
| 21 | Supply and fixing modular metal flush box 8 module complete all as specified and directed. |
| 22 | Supply and fixing modular metal flush box 12 module complete all as specified and directed. |
| 23 | Supply and fixing modular white cover plate with frame, 1 module complete all as specified and directed. |
| 24 | Supply and fixing modular white cover plate with frame, 2 module complete all as specified and directed. |
| 25 | Supply and fixing modular white cover plate with frame, 3 module complete all as specified and directed. |
| 26 | Supply and fixing modular white cover plate with frame, 4 module complete all as specified and directed. |
| 27 | Supply and fixing modular white cover plate with frame, 6 module complete all as specified and directed. |
| 28 | Supply and fixing modular white cover plate with frame, 8 module complete all as specified and directed. |
| 29 | Supply and fixing modular white cover plate with frame,12 module complete all as specified and directed. |
| 30 | Supply and fixing modular Dummy plate complete all as specified and directed. |
| 31 | Supply and fix in repair Modular switch 6 Amps single pole one way as per existing make & model/ as per sample. |
| 32 | Supply and fix in repair Modular switch 16 Amps single pole one way as per existing make & model/ as per sample. |
| 33 | Supply and fix in repair Modular bell bush 5 Amps as per existing make & model/ as per sample. |
| 34 | Supply and fix Modular multi socket 3 pin and 2 pin 6 Amps round and flat as per existing make & model/ as per sample. |
| 35 | Supply and fix in repairModular socket 6A /16 A Twin socket heavy duty as per existing make & model/ as per sample. |
| 36 | Supply & fixingswitch piano flushtype single pole one way 5 Amps all as specified. |
| 37 | All as per item 36 here-in-beforebut single pole 5 Amps two way all asspecified. |
| 38 | Supply & fixingswitch piano flush type single pole 15 Amps. |
| 39 | Supply & fixingsocket outlet5 Amp flush button type all as specified. |
| 40 | All as per item 39 here-in-before but 6 pin 5/15 Amps multi type. |
| 41 | Supply & fixingswitch piano single pole bell push all as specified. |
| 42 | Supply & fixing ceiling roses surfaces bakelite two three terminals 65 x 50 mm all as specified. |
| 43 | Supply & fixing lamp holder PVC, insulated body with back plate suitable for batten fittings including LED lamp 9W all as specified. |
| 44 | Supply & fixing bell electric (dingdong) 230 volt, SP |
| 45 | Supply and fix in repair modular fan regulator step type 240 V, 120 W, 2 modules all as as per existing make & model/ as per sample. |
| 46 | Supply and fix ceiling fan regulator Electronic rotary Step typesingle phase A/C 230 volts all complete as specified and directed. |
| 47 | Supply and Fixed single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of cap 20A complete all as specified and directed. |
| 48 | Supply and fix Bed side Reading light with all electrical connection as required all as specified and directed. Make: Havells LED READELUX Bed straight 4W Cir. White/Black Product Code: LHEXCIPBPN1K004 or equivalent as approved by Engineer-in-charge. |
| 49 | Supply & fixing decorative wall light fixture made up of polycarbonate/glass all as specified and directed. Make : Havells Floretine WL 1LS B22 SS Item Code -LHFOAJE1TZ1I060 or equivalent as approved by Engineer-in-charge. |
| 50 | Supply and fix of Recess LED 2x2 PIR based luminaire , White/Warm white with CRCA housing suitable with fully diffused diffuser for general lighting in office areas. The luminaire should have a color consistency SDCM < 5, CRI > 80 and CCT of both 5700K. The luminaire shall be compliant with IP20 and IK02 classification. Luminaire shall be designed to emit at least 4250 nominal lumens and an outstanding System efficacy of atleast 115 lumen/watt and maximum system wattage of 36 Watts. In up position sensor will work with detection range of 3m & in down position sensor will work with detection range of 6m. Time delay options should be 5s, 30s, 1min, 5min, 8min.The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 and THD <10% with 3 KV internal surge protection and suitable for an operating voltage range of 140-270V AC. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters complete all as specified and directed . Havells Cat no VENUSNEOHE2X2R36WLED857PIRSENSOR equivalent in Signify/Wipro. |
| 51 | S & F surface mounted LED Battern with LED tube rod 2 Feet 10W internal surge protection device of 4 KV with voltage band 140-280V and making electrical connection to ceiling rose all as directed. |
| 52 | Supply and fix of Microwave Sensor enabled Integral LED 4 ft luminaire with extruded housing and Opal diffuser ith ABS end caps. The luminaire should have a color consistency SDCM < 5, CRI > 80 and CCT of 6500K. The luminaire shall be compliant with IP20 classification. Luminaire shall be designed to emit at least 2000 nominal lumens at a system efficacy of at least 100 lumen/watt with a maximum system wattage of 20 Watts. Fixture should cover upto 5 mtr sensor radius coverage area with 120 degree angle after 17 to 30 seconds & 30% light output in case of non-occupancy.The electronic driver used shall have a power factor >0.9 and THD <10% and suitable for an operating voltage range of 140-270V AC. Manufacturer shall have in house lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameterscomplete all as specified and directed. Havells Cat no LUMILINESMART20WLED865PCWH equivalent in Signify/Wipro |
| 53 | S& F in replacement LED tube set (fitting) 20 Wuse and through type withinternal surge protection device of 4 KV with voltage band 140-280V with LED rod with fixture box type and making electrical connection to ceiling rose all as directed |
| 54 | Supply and fix of hexagon shaped LED bulkhead industrial luminaire with Pressure die cast housing and Polycarbonate diffuser and silicon gasket. The luminaire should have a color CRI > 80, and CCT of 5700K. The luminaire shall be compliant with IP66 & IK 10 classification. Luminaire shall be designed to emit at least 1000 nominal lumens at a system efficacy of at least 100 lumen/watt with a maximum system wattage of 10 Watts. The electronic driver used shall have a power factor >0.95 and THD <15% and suitable for an operating voltage range of 180-270V AC and 4 Kv inbuilt surge protection. Manufacturer shall have in house lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Havells Cat no HEXAFT10WLED857SSYMBOPC equivalent in Signify/Wipro |
| 55 | S & F LED bulb 9 Watt White(6000K-6500 K)/Warm(2700K-3200K) with BEE Energy star rating of three star or more and emission of minimum 100 lm/W complete all as specified |
| 56 | S & F LED bulb 12 Watt White(6000K-6500 K)/Warm(2700K-3200K) with BEE Energy star rating of three star or more and emission of minimum 100 lm/W complete all as specified |
| 57 | S & F SITC of high-quality integrated LED Street Light with a minimum system lumen of4750 Lm and system wattage not exceeding 45W with a nominal efficiency 105 lumen/watt. CCT of 5700K with SDCM of < 5 and CRI >70. The housing should be of non-corrosive high-pressure die-cast aluminum with high efficiency LEDs as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07 with PF > 0.95. Lifetime of 50K hours @L70. The Luminaire should have Powered by integral, Isolated LED electronic driver (SMPS based constant current supply) with lower THD, Output Open / Short Circuit protection, Phase to Phase protection (Operation at 440 V AC), Over Voltage protection, Surge Voltage protection upto 4 kV.Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/ULaccredited lab to verify above parameters complete all as specified and directed.. Havells Cat noENDURASUNBEAMSL45WLED757SASYTOPCSENSO equivalent in Signify/Wipro |
| 58 | Supply and fixing of new generation, post top, energy saving spun aluminium landscape luminaries with high power 40W suitable for Pole dia76mm confirming to IP65 Ruby (Clear) Of Havells cat part LHEVBGP7PN6K040. Make Havells |
| 59 | Supply & Fixing MCB single pole, 240 volts, 6 to 32 Ampere, rupturing capacity 10 KA, ‘B’ curve type conforming to Osafe of HPL / Acti 9 series of Schneider /Ekinox3 of Legrand /equivalent in Havells/Hager/L&T/Siemens complete all as specified and directed. |
| 60 | S & F MCB SPN, 240 volts, 40 to 63 Ampere, rupturing capacity 10 KA, ‘B’ curve type conforming to Osafe of HPL / Acti 9 series of Schneider /Ekinox3 of Legrand /equivalent in Havells/Hager/L&T/Siemens completeall as specified and directed. |
| 61 | Supply and fix Sheet metal DB,double door,SPN 8 way for MCB, 240 volt with 200 amps rated bus bar , neutral bar / connectors suitable copper thimbles , lugs etc complete all as specified and directed. Make : EKINOX3 series of Legrand/Acti 9 metalic series of Schneider /Osafe series of HPL/Metallica of Havells/Hager/L&T/Siemens |
| 62 | Supply and fix MCCB 100 Amps 4 pole415 Volt,25 KA breaking capacity conforming to Osafe of HPL / Acti 9 series of Schneider /Ekinox3 of Legrand /equivalent in Havells/Hager/L&T/Siemens complete all as specified and directed . |
| 63 | Supply & fixingMCCB 3 pole of capacity 63 Amps with breaking capacity 16 Kilo Amps including all electrical connections and fixing arrangment conforming to Osafe of HPL / Acti 9 series of Schneider /Ekinox3 of Legrand /equivalent in Havells/Hager/L&T/Siemens complete all as specified and directed . |
| 64 | Supply and fix MCB DB, TPN 6 way double door Vertical type suitable for mounting of MCCB as incomer with suitable 200 amps rated bus bars , Neutral links , blanking plates conforming to Osafe of HPL / Acti 9 series of Schneider /Ekinox3 of Legrand /equivalent in Havells/Hager/L&T/Siemens completeall as specified and directed. |
| 65 | S/F MCB TPN63Amps 415 volts as per Osafe of HPL / Acti 9 series of Schneider /Ekinox3 of Legrand /equivalent in Havells/Hager/L&T/Siemens completeall as specified and directed. |
| 66 | Supply and fix MCB DB, TPN 4 way double door with suitable 200 amps rated bus bars , Neutral links , blanking plates conforming to Osafe of HPL / Acti 9 series of Schneider /Ekinox3 of Legrand /equivalent in Havells/Hager/L&T/Siemens completeall as specified and directed. all as specified and directed. |
| 67 | M&L for concealed conduit sub main wiring of2 run ofsingle core multi stranded FRLS PVC insulated and unsheathed copper conductor as per IS-694 FR cable red and black colour of size 6 sqmm1100 volts grade with 6.0 sqmm multi strand copper conductor PVC insulated and unsheathed cable in green colour earth continuity wire connected to common earth dollyin PVC pipe including cutting chasing complete with all accessories as specified and directed. |
| 68 | M&L for submain wiring with two RUNS of single core 4 sqmm for main wire and one run of single core 4 sqmm as earth wire of stranded FRLS copper conductor PVC insulated unsheathed cables drawn through and including concealed conduits in wall and necessary cutting and chassing forrigidPVC conduit ISI marked not less than 20 mm dia andall accessories complete all as specified & directed. |
| 69 | Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including4mm suspension wire, one twin core cable flat or circulat of size 10 Sqmm 2 Core complete. |
| 70 | Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including4mm suspension wire, one twin core cable flat or circulat of size 6 Sqmm 2 Core complete. |
| 71 | Supply & fix bakelite Hylem sheet 3mm thick of size 10\"x12\" superior quality, including cutting of sheet to fix switch socket & regulator, including unscrewing the existing switch, socket, regulator and refixing the same on new sheet with new machine screw complete all as specified and directed. |
| 72 | All as per item no 71 but size 7\"x5\"complete all as specified and directed. |
| 73 | M&L for fixing MS sunken box of 1.6 mm thick of box sizes of size 10\" x 12\"and making good to wall. |
| 74 | M&L for sunken boxes of size 7\" x 5\" |
| 75 | M&L for earthing complete with GI steel earth plate electrod 60x60cmx6.00mm thick bouried directly in ground /earth pit not less than 2.25m deep below the ground level with top edge of the plate not less than 1.5 m below the normal ground level connected to test point by using GI wire of dia 4 mm as earthing lead soldering/revated to earth plate at one end and connected DBby means of nut, bolts etc complete with PCC pit (1:3:6) type GI cover with handle funnel with watering pipe wire mess GI protection pipe for earthing lead all complete as specified and as per electric plate No.5 of SSR Part I |