| 1 | Supply, install commissioning and testing of split type wall mounted Air Conditioner units indoor/outdoor of capacity 1.5 TR (4500 K Cal / hr) single phase Non CFC / HCFC suitable for 230 volts + 10% , 50 Hz, AC supply complete with cordless remote control unitat any location with minimum 3 star rating and EER 3.2 and above.Note:-(a)Indoor unit copper coil with three speed blower fan of appropriate capacity including PCB, thermostatic control, air filter and drain for condensing water.(b)Outdoor unit comprising , Compressor with motor , air cooled copper condenser with fan and motor unit shall be installed out side the building / on roof.(c)Refrigerant copper pipe for suction and discharge line with insulation, condensing water drain pipe with control valves and safety accessories including control wiring for evaporator & condensing unit with suitable size of copper cable.(d)Making good the disturbed surfaces to match the existing surface after plugging the hole etc.(e)Electrical cable required to connect out door unit and indoor unit to voltage stabilizer inclusive in above rates. |
| 2 | Supply, install commissioning and testing of split type wall mounted Air Conditioner units indoor/outdoor of capacity 3 TR (9000 K Cal / hr) three phase Non CFC / HCFC suitable for 415 volts + 10% , 50 Hz, AC supply complete with cordless remote control unitat any location with minimum 3 star rating and EER 3.2 and above. Note:(a)Indoor unit copper coil with three speed blower fan of appropriate capacity including PCB, thermostatic control , air filter and drain for condensing water.(b)Outdoor unit comprising , Compressor with motor , air cooled copper condenser with fan and motor unit shall be installed out side the building / on roof.(c)Refrigerant copper pipe for suction and discharge line with insulation, condensing water drain pipe with control valves and safety accessories including control wiring for evaporator & condensing unit with suitable size of copper cable.(d)Making good the disturbed surfaces to match the existing surface after plugging the hole etc.(e)Electrical cable required to connect out door unit and indoor unit to voltage stabilizer inclusive in above rates. |
| 3 | Supply and fixing out door stand suitable for Split AC 1.5 TR as per sample complete all as specified and directed. |
| 4 | Supply and fixing out door stand suitable for Split AC 3 TR as per sample complete all as specified and directed. |
| 5 | Supply, installation, commissioning, testing of Metal Top Deep Freezer of Capacity 500 Ltr single phase 240 volt, 50 Hz complete all as specified and directed. |
| 6 | M & L for sub main wiring with two runs of single core 4 Sq.mm for phase and neutral conductor and one run of single core 4 Sq.mm as earth wire ofmulti stranded copper conductor FR-LSH PVC insulated unsheathed cable conforming to IS : 694 drawn through in & including PVC casing & capping with fixing accessories on wall / roof surface as per relevant IS standard not less than 25 mm width and all as complete specified and directed. |
| 7 | M & L for sub main wiring with four runs of single core 6 Sq.mm for phase conductor and one run ofsingle core 6 Sq.mm as earth continuity conductor ofmulti stranded copper conductor FR-LSH PVC insulated unsheathed cable conforming to IS : 694 drawn through in & including PVC casing & capping with fixing accessories on wall/roof surface as per relevant IS standard not less than 30 mm width and all as complete specified and directed. |
| 8 | Supply and Fixing industrial type socket with plug top, Single pole and neutral and earth plug 240V, 20 Amps with steel enclosure and one MCB SPN20 Amps complete all as specified and directed. |
| 9 | Supply and Fixing industrial type socket with plug top, triple pole and neutral and earth plug 415V, 32 Amps with steel enclosure and one MCB TPN 32 Amps complete all as specified and directed. |
| 10 | Supply and fixing voltage stabilizer electronic typefor automatic operation single phase naturally air cooled, indoor type, wall mounted for input variation between 170 V to 280 V with output voltage stabilized at 200V to 245 V with accuracy of + 1% and of capacity 5.0 KVA complete all as specified and directed |
| 11 | Supply and fixing copper tubing with of special annealed pressure copper of size 3/8\" bore including insulation , clip complete all as specified and directed. |
| 12 | Supply and fixing copper tubing with of special annealed pressure copper of size 5/8\" bore including insulation, clip complete all as specified and directed. |
| 13 | Supply and fixing copper tubing with of special annealed pressure copperof size 1/4\" bore including insulation, clip complete all as specified and directed. |
| 14 | Supply and fixing copper tubing with insulation , clip of special annealed pressure copper of size 1/2\" bore complete all as specified and directed. |
| 15 | S&F PVC insulated & sheathed copper round cable 1100 volts of size 4.0 sqmm 3 core incl copper thimble/pin type lugs connecting both side and testing complete all as specified and directed. |
| 16 | Supply and fixing PVC nylon braided industrial quality drain pipe of 20mm inner bore including fixing accessories on wall/roof etc all as directed. |
| 17 | S&F/Laying, connecting and testing of LT cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade as per IS 7098 with stranded aluminium conductor of size 10 sqmm 2 core complete all as specified and directed.. Note : Excavation, earth work, sand cushioning for cable and cable protection cover shall be measured & paid under respective item.(i).Lugs/Glands/saddles of suitable size required for fixing of cables in panels/junction boxes /on walls shall be included in the item rate. |
| 18 | Excavation in trenches in soft/loose soil not exceeding 1.5 m deep and not exceeding 1.5 m width and getting out including forming bottom surfaceforlaying cables/pipesall as specified and directed. |
| 19 | Returning, filling in including spreading, leveling, watering and well ramming in layers n exc25 cm thickafter the cablesare laid, jointed & tested complete all as specified and directed. |
| 20 | Removing of surplus excavated spoil not exceeding 50 M distance and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified. |
| 21 | Sand cushioning and spreading clean, dry, fine river sand for UG electric cable in two layers (8 cm thick before laying the cable & 15 cm thick after laying cable) total 23 cm thick including gentle punning the sand upto 18 cm (total thickness) and consolidated around cable for protection of under ground cable complete all as specified and directed. (Note :- Only punned down thickness shall be measured for payment). |
| 22 | Supply & Laying sub class `A’ bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection complete all as specified and directed. |
| 23 | M&L boring of holes under road, pavement, hard standing by manually depth not less than 75 cm for insertion of GI Pipe upto size of 80 mm bore light grade for short length complete all as specified and directed. Note :- GI pipe 50 mm dia light grade shall be measured and paid separately under relevant item of BOQ\". |
| 24 | Supplying and laying GI water tubing, 50 mm bore, light grade as in sleeving etc laid in trenches / ducts / horizontal bore hole/On pole complete all as specified and directed. |
| 25 | Supplying and Fixing of emergency crass Bell of size 12\"\"complete all as specified and directed. |
| 26 | M&L for point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi stranded copper conductor 2.5 sq mm nominal cross sectional area, single core, pvc insulated and unsheathed FRLS cable 1100 volts grade, ISI-694 marked with valid CML No in and including medium grade, PVC Concealed conduit of dia not less than 20 mm and conduit accessories concealed in wall, ISI marked with valid CML No (IS-9537-1983 for conduits and IS: 3419:1976 for conduit accessories), with mild steel/pressed steel sunken boxes (with earth duly) duly painted with two coats of anticorrosive paint over a coat of red oxide primer internally and two coats of black bituminous paint over a coat of red oxide primer externally, base frame of suitable size along with top enclosures and fixtures / complete accessories for fixing of modular switches/sockets including PVC insulated multi stranded copper conductor 2.5 sqmm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dully complete all as specified and directed. |
| 27 | S&F moduler switch socket 6 Amps -2/3 pin combined 2 module, ISI marked complete all as specified and directed. |
| 28 | S&F moduler Metal flush Box 4 module, ISI marked complete all as specified and directed. |
| 29 | S&F moduler Bell push 6 A 1 module, ISI marked complete all as specified and directed. |
| 30 | S&F/Laying, connecting and testing of LT cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade as per IS 7098 with stranded aluminium conductor of size 25 sqmm 4 core complete all as specified and directed. Note : Excavation, earth work, sand cushioning for cable and cable protection cover shall be measured & paid under respective item.(i).Lugs/Glands/saddles of suitable size required for fixing of cables in panels/junction boxes /on walls shall be included in the item rate. |
| 31 | Supply, install commissioning and testing of split type wall mounted Non Invertor Air Conditioner units indoor/outdoor of capacity 2 TR (6000 K Cal / hr) single phase Non CFC / HCFC suitable for 230 volts + 10% , 50 Hz, AC supply complete with cordless remote control unitat any location with minimum 3 star rating and EER 3.2 and above.(a)Indoor unit copper coil with three speed blower fan of appropriate capacity including PCB, thermostatic control , air filter and drain for condensing water.(b)Outdoor unit comprising , Compressor with motor , air cooled copper condenser with fan and motor unit shall be installed out side the building / on roof.(c)Refrigerant copper pipe for suction and discharge line with insulation, condensing water drain pipe with control valves and safety accessories including control wiring for evaporator & condensing unit with suitable size of copper cable.(d)Making good the disturbed surfaces to match the existing surface after plugging the hole etc.(e)Electrical cable required to connect out door unit and indoor unit to voltage stabilizer inclusive in above rates. |
| 32 | Supply and fixing out door stand suitable for Split AC 2 TR as per sample complete all as specified and directed. |
| 33 | S&F PVC insulated & sheathed copper round cable 1100 volts of size 6.0 sqmm 3 core incl copper thimble / pin type lugs connecting both side and testing complete all as specified and directed. |
| 34 | S&F/Laying, connecting and testing of LT cable XLPE insulated screened PVC bedded, , galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade as per IS 7098 with stranded aluminium conductor of size 185 sqmm 3.5 core complete all as specified and directed |
| 35 | Supply and fix ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 200 Amps complete all as specified and directed. |