Tender For Electrical Work To Be Done In Aluminium Compartments In Various Locations At Aiims Rishikesh; 1 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C 2 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire 3 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire 4 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 4 X 4 sq. mm + 2 X 4 sq. mm earth wire 5 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 4 X 10 sq. mm + 2 X 6 sq. mm earth wire 6 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch 7 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet 8 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 A switch 9 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 A socket outlet 10 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.6 Module (200mmX75mm) 11 Supplying and fixing suitable size GI/PVC box withmodular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 &15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. 12 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)4 way (4 + 12), Double door 13 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)8 way (4 + 24), Double door 14 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles intheexistingMCBDBcompletewithconnections,testingand commissioning etc. as required & as directed by Engineering Incharge.Single pole 15 Supplying and fixing following rating, four pole, 415 V, TPN MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 A