Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Provide all materials, labour, T&P etc. complete and constructed pump house of size (3.0X3.60) cum chlorinating room of size (1.80X2.60) and By Pass Chamber as per departmental type design and drawing. |
| 2 | Repairing & painting of existing pump house of cum chlorinating room of sizeincluding supply of all labour, material, T&P etc complete. |
| 3 | Rising Main for Zone 1 to 14 |
| 4 | Supply of following sizes of D.I pipesclass K-7/9 withalljointingmaterials including supply of all type of specials asperIS- 8329/2000 or its latest amendments including F.O.R. destination and all taxes and insurance etc. complete |
| 5 | 200 mm dia DI.K-9 |
| 6 | 150 mm dia DI.K-9 |
| 7 | Supply of following sizes of D.I double flangedsluicevalveasperI.S:14846:2000 working pressure 10 Kg/cm2 F.O.R. destination and all taxes and insurance. |
| 8 | 200 mm |
| 9 | 150 mm |
| 10 | Carting of following sizes D.I.D/F Sluice valve and specials from departmental store to site of work and lowering theminto the trenches, fixing in position and jointing them with pipelines and testing etc. complete (including supply of jointing materials) |
| 11 | 200 mm |
| 12 | 150 mm |
| 13 | Excavationfor pipe line trenches in ordinary soil(loam,clayorsand)includingliftupto 1.5m and refilling, watering, ramming of excavated earth into trenches anddisposal of surplus earth up to 50m from the center of thefoundation trenches. |
| 14 | Carting of following sizes D.I. pipes class K- 7/9 and specials to the site of work lowering them in to trench and laying true to alignment includingtestingofpipelinebutexcluding cost of trenching and cutting of pipes etc. formaking of length but including making joints. |
| 15 | 200 mm dia DI.K-9 |
| 16 | 150 mm dia DI.K-9 |
| 17 | Dismantling of following type road and stackingofusefulmaterial andtemporary reinstatementofroadwitholdmaterialsetc.complete. |
| 18 | Bituminous Road |
| 19 | Reinstatement of following type road and stackingofusefulmaterial andtemporary reinstatementofroadwitholdmaterialsetc.complete. |
| 20 | Bituminous Road |
| 21 | Supply of all material labour, T&P etc. Required and construct of Sluice Valve Chamber Masonry Type as per type design. |
| 22 | Thrust Block |
| 23 | R.C.C. with cement, coarse sand & 20 mm gauge stone ballast in proportion of 1:1.5:3 in thrust blocks of pipe line excluding supply of reinforcement & its bending but including its fixing & binding the same with 0.50 mm thick binding wire in position & necessary centering & shuttering including curing and supply of all materials, labour, T & P etc. required for proper completion of the work. |
| 24 | Mild steel or iron work in R.C.C. wrought to required shape as necessary including bending for proper completion of the work including supply of steel & wastage etc. |
| 25 | R.C.C. OHT |
| 26 | RENOVATION OF EXISTING OVER HEAD TANKS WHICH INCLUDES FOLLOWING ITEMS:Providing and erection of scaffolding and shuttering material like challi, gurra, nail, bans, ballia, patra etc. required for complete of work on all surgace area of OHT from top dome to G.L. so as to give strong and safe plateform to workers to work on all part of OHT for repair and strengthning as per direction of engineer in charge. Surface Preparation- The surface of structure to be treated for strengthning shall be reoughened properly either by raking joints or by haching the cement concrete surface with a specially made haching tool or otherwise alternatively to /make the surface rough and dust free byproviding spatter key or wire brush.Injection grouting in vertical surface/wall placing and fixing nozzle by drilling machine in tank wall having minimum dia of nozzle 15mm and provide on a regular interval not exceeding 1m including construction joints. Injection of pidicrete AM (Ploymer based on shrinkage high strength grout) admisxed with cement through nozle under pressure by sump @ 250gms per bag of cement sealing the nozzle after frounting with Ploymer product mixed with cement, making tank body in working and seapage free condition.Changeofsteelladderinsidethetank,repairof MH cover of top dome, change of mosqeuto jali with new one complete. Supply and fixing of 20mm dia G.I.Pipe railing in stair case and balcony. (Taking only 25% new and 75% old materials) Laying and fixing of 3mm thick MS wire mesh on roof of slab for nominal reinforcement including cost of all labour, materials, T&P etc required for completion of work25 mm thick 1:2:4 plain cement concrete flooring in apron with cement coarse sand and 20mm gauge stone ballast, laid in panels Finished with 3mm floating coat of neat cement of cement including 75mm thick base concrete of 1:4:8 including supply of all material. PaintingofoutersurfaceofOHTwithwheather proof paint (like apex etc.) as per direction of engineer in-charge. Painting of iron work with 1 coat primer & 2 coats of approved emultion paint as per direction of engineer incharge. |
| 27 | Zone-1, 1600 kL Capacity 16 M Staging |
| 28 | Zone-2, 1900 kL Capacity 18 M Staging |
| 29 | Zone-3, 1600 kL Capacity 18 M Staging |
| 30 | Zone-4, 1900 kL Capacity 18 M Staging |
| 31 | Zone-7, 1200 kL Capacity 16 M Staging |
| 32 | Zone-9, 600 kL Capacity 18 M Staging |
| 33 | Zone-12, 600 kL Capacity 16 M Staging |
| 34 | Construction of New OHT |
| 35 | Supply of all materials labour T&P etc. complete and construction of R.C.C. (M30 Grade)Over Head Tank of following capacity and staging above ground level with all work complete, including cost of soil testing. All the components of OHT will be casted in M30 concrete & specially in M-30 construction of water bearing structure with cement, coarse sand and approved stone grit as per I.S. 11682, I.S.3370 part (I) & (II) and I.S.456.Minimum depth of foundation below original ground level will be 2.5M. Seismic effects and wind load should be taken into consideration as I.S. 1893 for earthquake resistance and as per I.S. 875 part-III for wind load on structure (this area is in seismic Zone IV and high damage risk zone for wind).The cost of OHT should be quoted assuming the bearing capacity of soil as 8 M.T.per sqm. including 1M wide RCC staircase from ground level to balcony. M.S. ladder made of 50x50x6 mm angle section and 20mm plain M.S. bars (specification of M.S. should be as per IS 800-2007) with hand rails of 20mm medium class G.I. pipes on both sides in three rows from balcony to top dome resting on an RCC platform (75cmx75cm and 10cm thick) projecting from top ring beam and one aluminum ladder inside the tank body (from manhole in top dome to bottom as per design and specification approved by Engineer in charge. 1 m wide R.C.C. M25 balcony around the tank at the junction point of vertical wall and conical wall. Proper railing of 20mm dia medium class G.I. pipe (in 3 rows) on both sides of stair case, around the balcony, at each landing and from landing with top ring beam upto manhole on the top dome and at the periphery of top dome. The G.I. Pipes will be supported on M.S. posts made of or RCC post, spaced at intervals not more than 1.5m.Proper ventilator at top dome in circular shape of 1.2 m dia. along with an R.C.C. cover of minimum 1.50m dia and with mosquito net of standard quality along with expanded metaled jali between top dome and RCC cover. Water level indicator fabricated with good quality minimum 45mm x 45mm x 6mm M.S. angle with indicator board scale made 50x50x6mm M.S. angle section, of 3mm thick M.S. plate should have a clear width of minimum 25cm painted with good paint with brass wire rope, pulley, copper ball float, pointer etc. Lightening conductor should be as per I.S.S.2309 or its latest amendments of latest electricity rules. C.I. manhole cover of min 60x60cm size with locking arrangement, Supply, fixing & jointing of C.I.D./F Pipes (for inlet, outlet, washout and overflow pipes) and specials, duck foot bend and fixing of the sluice valve at outlet and wash put pipe with all specials; construction of sluice valve chamber, floor and apron with semi circular drain around the apron with 25mm PCC 1:2:4 over 75 mm PCC 1:4:8, Apex painting on outer surface of OHT, painting on MS ladder, railing, vertical pipe etc. as per approved make; excavation in all type of soil and all other works required for proper and complete construction |
| 36 | Zone-5, 1800 kL Capacity 22 M Staging |
| 37 | Zone-6, 1800 kL Capacity 18 M Staging |
| 38 | Zone-8, 1200 kL Capacity 18 M Staging |
| 39 | Zone-10, 2200 kL Capacity 22 M Staging |
| 40 | Zone-11, 1900 kL Capacity 20 M Staging |
| 41 | Zone-13, 600 kL Capacity 22 M Staging |
| 42 | Zone-14, 600 kL Capacity 22 M Staging |
| 43 | Construction of CWR |
| 44 | Zone-1, 400 kL Capacity |
| 45 | Zone-2, 500 kL Capacity |
| 46 | Zone-3, 400 kL Capacity |
| 47 | Zone-4, 500 kL Capacity |
| 48 | Zone-7, 300 kL Capacity |
| 49 | Zone-8, 600 kL Capacity |
| 50 | Zone-10, 600 kL Capacity |
| 51 | Distribution System Zone 1 to 14 |
| 52 | Excavation of earth in ordinary soil (loam, clay or sand)forlayingofpipelineincludingrefilling anddisposal of surplus earth for different size of pipe lift up to1.5m and50 m away. |
| 53 | Supplyoffollowingsizesofpipeincludingrail way freight and cartage as per IS 8329/2000 and IS4984/2016ortheirlatestamendmentsupto divisional store including all taxes etc. complete. |
| 54 | HDPE Pipe (Grade PE-100) PN-6 |
| 55 | 90mm diaO.D. |
| 56 | 110mm dia O.D. |
| 57 | 140 mm dia O.D. |
| 58 | 160 mm dia O.D. |
| 59 | DI Pipe K-7 |
| 60 | 200mm dia |
| 61 | 250mm dia |
| 62 | 300mm dia |
| 63 | 350mm dia |
| 64 | 400mm dia |
| 65 | 450mm dia |
| 66 | 500mm dia |
| 67 | Carting, laying and jointing by Electrofusion Method of the following sizes ofpipe intothetrenchesincludingcostofall jointingmaterial,labour,T&Pandtestingetc, complete. The rate includes all material, labour and T&P for electrofusion jointing of HDPE pipe. |
| 68 | HDPE Pipe (Grade PE-100) PN-6 |
| 69 | 90mm diaO.D. |
| 70 | 110mm dia O.D. |
| 71 | 140 mm dia O.D. |
| 72 | 160 mm dia O.D. |
| 73 | DI Pipe K-7 |
| 74 | 200mm dia |
| 75 | 250mm dia |
| 76 | 300mm dia |
| 77 | 350mm dia |
| 78 | 400mm dia |
| 79 | 450mm dia |
| 80 | 500mm dia |
| 81 | Supply of following types of fitting including rail wayfreight,cartageuptostore, all taxesand insurance.D.I.D/FSluiceValve/ScourValveas per IS 14846:2000 suitable for workingpressure10 kg/cm2. |
| 82 | D.I.D/F Sluice Valve |
| 83 | 80mm dia |
| 84 | 100mm dia |
| 85 | 125mm dia |
| 86 | 150mm dia |
| 87 | 200mm dia |
| 88 | 250mm dia |
| 89 | 300mm dia |
| 90 | 350mm dia |
| 91 | 400mm dia |
| 92 | 450mm dia |
| 93 | 500mm dia |
| 94 | Scour Valve 80mm dia |
| 95 | Supply of under ground sluice value type firehydrant consisting of 80 mm dia sluice valve,80mm dia tail pieces, 80mm dia duck foot bend and 63 mm dia standard makes iron coupling with cap and etc. Complete conforming to latest/relevent I.S.specifications including all taxes and insurance. |
| 96 | Supply of 20 mm dia screwed down type air valve with gun metal seat, F.O.R. destination,including all taxes and insurance. |
| 97 | 20 mm dia |
| 98 | CartingoffollowingsizesD.I.D/FSluicevalve andspecialsfromdepartmentalstoretositeof work and lowering them into the trenches, fixing inpositionandjointingthemwithpipelinesand testing etc. complete (including supply of jointing materials) |
| 99 | D.I.D/F Sluice Valve |
| 100 | 80mm dia |
| 101 | 100mm dia |
| 102 | 125mm dia |
| 103 | 150mm dia |
| 104 | 200mm dia |
| 105 | 250mm dia |
| 106 | 300mm dia |
| 107 | 350mm dia |
| 108 | 400mm dia |
| 109 | 450mm dia |
| 110 | 500mm dia |
| 111 | Scour Valve 80 mm dia |
| 112 | Carting of 80 mm dia flanged fire hydrant to the site of works, lowering them into already prepared trenches and fixing them in position including baring and threading the main etc. Complete including thr cost of bailing out of water, supply of jointing materials such as nut-bolts, rubber insertions, white lead etc. Including their testing complete. |
| 113 | Carting from site store the 20 mm dia screwed down air valves, to the site of works, lowring them into already prepared trenches and fixing them in position including boring and threading the main etc. Complete and including the cost of bailing out of water , supply of jointing materials such as nut-bolts, rubber insertions, white lead etc.Including their testing complete. |
| 114 | Supply of all type materials and construct following chamber as per type design with supply of all labour, T & P etc. complete. |
| 115 | Masonry Type |
| 116 | Surface Box Type |
| 117 | Fire Hydrant Chamber |
| 118 | Air Valve Chamber |
| 119 | ScourValve Chamber |
| 120 | Dismantlingoffollowingtyperoadandstacking of useful material and temporary reinstatement of road with old materials etc. complete. |
| 121 | CC Road |
| 122 | Bituminous Road |
| 123 | B.O.E Road |
| 124 | Interlocking Road |
| 125 | Reinstatement of following type road and stacking of useful material and temporary reinstatement of road with old materials etc. complete. |
| 126 | CC Road |
| 127 | Bituminous Road |
| 128 | Bituminous Road PWD |
| 129 | B.O.E. Surface (Assuming 40% new brick and 60% old bricks used) |
| 130 | Interlocking Surface (Assuming 40% new brick and 60% old bricks used) |
| 131 | Provision for crossings of nalas & culvert includingsiftingoftelephonecablesetc.Along the alignment of pipeline including supply of C.I. tytonpipeand specialsetc.complete.(3.5M. Wide Road) |
| 132 | Provision forInstallation of ductpipesby Augerboringmethodincludingmakingofentry andexitpitsupto3mtrdepth,allrelatedcivil works like excavation etc. lowering of pipe segmentsinthejackingpit,layingjointingof pipeline through jacking process as per the instruction of Engineer-in-charge all complete. |
| 133 | Road Crossing through trenchless technique |
| 134 | Road Crossing through trenchless technique (200mm to 350 mm |
| 135 | Sand Filling |
| 136 | Interconnection of new pipeline with existing pipeline including trenching,jointing,testing etc complete. PVC/HDPE to HDPE |
| 137 | Interconnection of new pipeline with existing pipeline including trenching,jointing,testing etc complete. DI/CI to DI upto 350 mm dia |
| 138 | Construction of booster pump rooms including all required material labour T&P as per approved drawing and desigen plinth area rate. |
| 139 | Boundary Wall Gate and approchroad and site devlopment |
| 140 | Construction of Boundary Wall including Supply all materials, labour, T&P etc. required for proper completion of work as per type design. |
| 141 | Supplyandfixing3.6M&1.20MwideMSGatewith pillersincludingfabrication andsupplyofsteeland construction of boundary pillarsetc. completefor pump house |
| 142 | Provideallmaterials,labour,T&Petc.Requiredfor propercompletionofworkandconstructInterlocking Tiles approach road, laid dry and joints intact with coarse sand mortar including preparation of base etc. |
| 143 | Drain |
| 144 | Provide all materials labour, T&P etc. complete and construction of One Set staff quarter for operators & chaukidar as per departmental type design and drawing |
| 145 | Construction ofMaster Control Station. Building shall be RCC framed structure including all amenities like water supply, drainage, fire fighting, electrical fittings.required fall cellings/ wall panneling including all required furniturefor 10 persons in confrence rooms and other officers room as per standerd All specification shall be conforming to PWD/CPWD/C&DS building specification. |
| 146 | Construction ofRecharging Unit of ground water by rain water in water works sites as per the drawingor approved by Engineer in charge including supply of all materials, labour, T&P etc. required for proper completion of work. |
| 147 | HOUSE CONNECTION IN NEW PIPE LINE |
| 148 | Materials |
| 149 | 20 mm dia (OD) HDPE pipe (12.5 KG/CM2) |
| 150 | 15 mm dia (OD) GI pipe Class- B |
| 151 | Providing & supplying of clamp saddle (MS saddle for DI Pipe and Electrofusion Saddle For HDPE Pipe) for House service connections shall be of fastened strap type with threaded outlet for service connection.Clamp saddle shall be suitable for nominal size of distribution mains pipe line. The strap shall be elastomer coated ( insulated) type for firm grip on pipe as well as to protect the coating on the pipe and to insulate the unidentical metals. The saddle shall be single strap type up to pipe size of NB 600 and service outlet 15mm. Fasteners shall be of threaded nut bolt washer type. The sealing between the saddle and mains shall be obtained by using a profiled elastomer seal matching to the curvature of the pipe. The seal shall be elastomer type, suitable for all potable water application. The material of construction of the body, straps, fasteners etc. shall be non-corrosive material sucha as engineering plastic (PE/PP) or stainless steel of a combination of both and shall ne inclusive of all cost such as testing,inspection charges, transporation up to site, transit, insurance, loading, unloading, stacking etc. complete. |
| 152 | 90 to 110 NB x 15 mm |
| 153 | 140 to 160 NB x 15 mm |
| 154 | 200 to 250 NB x 15 mm |
| 155 | 300 to 350 NB x 15 mm |
| 156 | Labour |
| 157 | Making ferrule connection in. Distribution mainswith saddle piece, service connections, fittings, and fixing of G.M. Ferrule of 15 mm size inculding tapping the main and.cutting threading and fitting GI pipe and specials including supply of all binding materials such as white lead and teflon tape including making hole in wall and plastering the same with mortar including cost of mortar and also including the cost of crossing the drain including all labour, T&P complete as per direction of EIC |
| 158 | Dismantlingoffollowingtyperoadandstacking of useful material and temporary reinstatement of road with old materials etc. complete. |
| 159 | CC Road |
| 160 | Bituminous Road |
| 161 | B.O.E Road |
| 162 | Interlocking Road |
| 163 | Reinstatement of following type road and stacking of useful material and temporary reinstatement of road with old materials etc. complete. |
| 164 | CC Road |
| 165 | Bituminous Road |
| 166 | Bituminous Road PWD |
| 167 | B.O.E. Surface (Assuming 40% new brick and 60% old bricks used) |
| 168 | Interlocking Surface (Assuming 40% new brick and 60% old bricks used) |
| 169 | Construction of TW for 1200/1100 LPM |
| 170 | TRANSPORTATION |
| 171 | Transportation of rig machineincluding Loading , unloading, Erection, Dismantling & labour etc complete in all respect . |
| 172 | Transportation of 250psi compressor including Loading , unloading, Erection, Dismantling & labour etc complete in all respect . |
| 173 | Transportation of 3 cusec op unit including Loading , unloading, Erection, Dismantling & labour etc complete in all respect . |
| 174 | Transportation of TubewellL Assemblyincluding Loading , unloading with labour etc complete in all respect . |
| 175 | CONSTRUCTION OF TUBE WELL (DRILLING) As per IS 2800 (Part I & II) |
| 176 | DC Drilling upto 200M |
| 177 | Logging of Bore |
| 178 | Drilling of 600mm dia bore from G.L. to 47 m BGL. |
| 179 | Drilling of 500mm dia bore from 47 m BGL to 100m BGL. |
| 180 | Drilling of 500mm dia bore from 101m BGL to 165m BGL. |
| 181 | LOWERING OF TUBE WELL ASSEMBLY AND SHROUDING OF T.W. BY GRAVEL- |
| 182 | Welding and lowering of TW Assembly (including electrodes welding set and generator etc. required for completion of work) as per following : Lowering of 300mm X 200mm dia (tube well assembly in bore hole and shrouding of pea gravel between annular space of bore hole and T.W. assembly from G.L. to 150m BGL. |
| 183 | Lowering of 300mm dia MSERW 7.1mm thick plain pipe from GL to 42 m BGL. |
| 184 | Lowering of 200mm dia MSERW plain/slotted pipe 7.1mm thick from 42m BGL to 100m BGL. |
| 185 | Lowering of 200mm dia MSERW plain/slotted pipe 7.1mm thick from 101m BGL to 150m BGL. |
| 186 | TUBE WELL: ASSEMBLY (As per IS 4270, IS 8110) |
| 187 | M.S. Tubewell assembly with all required parts like plain pipe, slotted pipe (as required upto 50% of plain pipes) well cap, bail pliug, clamp, reducer, centre guide, support structure etc as required & as per typed design complete in all respect. |
| 188 | 300mm dia size MSERW housing pipe 7.1mm thick including with 1 no 300 X200mm dia M.S reducer 16mm thick, 1 noM.S. well cap 12mm thick , 10 no M.S. ring 100X12mm thick, M.S. S/I clamp ,T.W. Support (I Section) etc comp in all respect . |
| 189 | 200mm dia MSERW 7.1mm thick plain /slotted pipe including with 20 no M.S ring 100X12mmthick , 1 noM.S. bail plug , 10 no center guide etc comp in all respect. |
| 190 | PEA-GRAVEL (As per IS 4097) |
| 191 | 1.60mm to 4.80mm size pea-gravel of Lalkuwan quarry duly screened, washed and proper stackingat site. |
| 192 | DEVELOPMNET OF TUBE WELL |
| 193 | Development of tube well by 250 PSI air compressor |
| 194 | Development of tube well by 3 cusec O.P. Unit |
| 195 | Development of tube well by 3 cusec O.P. Unit. |
| 196 | TEST |
| 197 | Chemical and bacteriological test. |
| 198 | Construction of TW for 800 LPM |
| 199 | TRANSPORTATION |
| 200 | Transportation of rig machineincluding Loading , unloading, Erection, Dismantling & labour etc complete in all respect . |
| 201 | Transportation of 250psi compressor including Loading , unloading, Erection, Dismantling & labour etc complete in all respect . |
| 202 | Transportation of 3 cusec op unit including Loading , unloading, Erection, Dismantling & labour etc complete in all respect . |
| 203 | Transportation of TubewellL Assemblyincluding Loading , unloading with labour etc complete in all respect . |
| 204 | CONSTRUCTION OF TUBE WELL (DRILLING) As per IS 2800 (Part I & II) |
| 205 | DC Drilling upto 200M |
| 206 | Logging of Bore |
| 207 | Drilling of 600mm dia bore from G.L. to 65 m BGL. |
| 208 | Drilling of 500mm dia bore from 65 m BGL to 100m BGL. |
| 209 | Drilling of 500mm dia bore from 101m BGL to 165m BGL. |
| 210 | LOWERING OF TUBE WELL ASSEMBLY AND SHROUDING OF T.W. BY GRAVEL- |
| 211 | Welding and lowering of TW Assembly (including electrodes welding set and generator etc. required for completion of work) as per following : Lowering of 200mm X 150mm dia (tube well assembly in bore hole and shrouding of pea gravel between annular space of bore hole and T.W. assembly from G.L. to 150m BGL. |
| 212 | Lowering of 200mm dia MSERW 7.1mm thick plain pipe from GL to 60m BGL. |
| 213 | Lowering of 150mm dia MSERW plain/slotted pipe 7.1mm thick from 60m BGL to 100m BGL. |
| 214 | Lowering of 150mm dia MSERW plain/slotted pipe 7.1mm thick from 101m BGL to 150m BGL. |
| 215 | TUBE WELL: ASSEMBLY (As per IS 4270, IS 8110) |
| 216 | M.S. Tubewell assembly with all required parts like plain pipe, slotted pipe (as required upto 50% of plain pipes) well cap, bail pliug, clamp, reducer, centre guide, support structure etc as required & as per typed design complete in all respect. |
| 217 | 200mm dia size MSERW housing pipe 7.1mm thick including with 1 no 200 X150mm dia M.S reducer 16mm thick, 1 noM.S. well cap 12mm thick , 10 no M.S. ring 100X12mm thick, M.S. S/I clamp ,T.W. Support (I Section) etc comp in all respect . |
| 218 | 150mm dia MSERW 7.1mm thick plain /slotted pipe including with 20 no M.S ring 100X12mmthick , 1 noM.S. bail plug , 10 no center guide etc comp in all respect. |
| 219 | PEA-GRAVEL (As per IS 4097) |
| 220 | 1.60mm to 4.80mm size pea-gravel of Lalkuwan quarry duly screened, washed and proper stackingat site. |
| 221 | DEVELOPMNET OF TUBE WELL |
| 222 | Development of tube well by 250 PSI air compressor |
| 223 | Cutting of T.W. cover by gas cutter, re-welding of T.W. cover by Electric welding after complete development of work. |
| 224 | Development of tube well by 3 cusec O.P. Unit |
| 225 | Cutting of housing cover by gas cutter |
| 226 | Development of tube well by 3 cusec O.P. Unit. |
| 227 | Re-welding of Tube well cover by Electric welding |
| 228 | TEST |
| 229 | Chemical and bacteriological test. |
| 230 | Construction of TW for 700 LPM |
| 231 | TRANSPORTATION |
| 232 | Transportation of rig machineincluding Loading , unloading, Erection, Dismantling & labour etc complete in all respect . |
| 233 | Transportation of 250psi compressor including Loading , unloading, Erection, Dismantling & labour etc complete in all respect . |
| 234 | Transportation of 3 cusec op unit including Loading , unloading, Erection, Dismantling & labour etc complete in all respect . |
| 235 | Transportation of TubewellL Assemblyincluding Loading , unloading with labour etc complete in all respect . |
| 236 | CONSTRUCTION OF TUBE WELL (DRILLING) As per IS 2800 (Part I & II) |
| 237 | DC Drilling upto 200M |
| 238 | Logging of Bore |
| 239 | Drilling of 600mm dia bore from G.L. to 47 m BGL. |
| 240 | Drilling of 500mm dia bore from 47 m BGL to 100m BGL. |
| 241 | Drilling of 500mm dia bore from 101m BGL to 165m BGL. |
| 242 | LOWERING OF TUBE WELL ASSEMBLY AND SHROUDING OF T.W. BY GRAVEL- |
| 243 | Welding and lowering of TW Assembly (including electrodes welding set and generator etc. required for completion of work) as per following : Lowering of 300mm X 150mm dia (tube well assembly in bore hole and shrouding of pea gravel between annular space of bore hole and T.W. assembly from G.L. to 150m BGL. |
| 244 | Lowering of 300mm dia MSERW 7.1mm thick plain pipe from GL to 42m BGL. |
| 245 | Lowering of 150mm dia MSERW plain/slotted pipe 7.1mm thick from 42m BGL to 100m BGL. |
| 246 | Lowering of 150mm dia MSERW plain/slotted pipe 7.1mm thick from 101m BGL to 150m BGL. |
| 247 | TUBE WELL: ASSEMBLY (As per IS 4270, IS 8110) |
| 248 | M.S. Tubewell assembly with all required parts like plain pipe, slotted pipe (as required upto 50% of plain pipes) well cap, bail pliug, clamp, reducer, centre guide, support structure etc as required & as per typed design complete in all respect. |
| 249 | 300mm dia size MSERW housing pipe 7.1mm thick including with 1 no 300 X150mm dia M.S reducer 16mm thick, 1 noM.S. well cap 12mm thick , 10 no M.S. ring 100X12mm thick, M.S. S/I clamp ,T.W. Support (I Section) etc comp in all respect . |
| 250 | 150mm dia MSERW 7.1mm thick plain /slotted pipe including with 20 no M.S ring 100X12mmthick , 1 noM.S. bail plug , 10 no center guide etc comp in all respect. |
| 251 | PEA-GRAVEL (As per IS 4097) |
| 252 | 1.60mm to 4.80mm size pea-gravel of Lalkuwan quarry duly screened, washed and proper stackingat site. |
| 253 | DEVELOPMNET OF TUBE WELL |
| 254 | Development of tube well by 250 PSI air compressor |
| 255 | Development of tube well by 3 cusec O.P. Unit |
| 256 | Development of tube well by 3 cusec O.P. Unit. |
| 257 | TEST |
| 258 | Chemical and bacteriological test. |
| 259 | Pumping Plant & Instrumentation Including Servo Stablizer and Chlorinating Plant For New/Existing Tubewells |
| 260 | SITC of 1200 LPM submersible clear water pumping plant ( suitable head as per site condition and direction of engineer in charge) suitable to operate on 415+ %5 volt, 50 Hz, 3 phase A.C. supply (as per IS 8034-1989) with 150 mm dia column pipe 24 meter,150 mm dia NRV,150 mm dia CI D/F Bend 90 Degree,150 mm dia CI A/F Tee, 150 mm dia D/F pipe (1.5 m long 2 nos. and 1 m long 1 no.), earthing, painting, Toolset, stabilizer, wiring of pump house internal and external, chainpully block , and all pumping plant accessories with nut bolts and rubber packing etc. |
| 261 | SITC of 800 LPM submersible clear water pumping plant ( suitable head as per site condition and direction of engineer in charge) suitable to operate on 415+ %5 volt, 50 Hz, 3 phase A.C. supply (as per IS 8034-1989) with 100 mm dia column pipe 24 meter,100 mm dia NRV,100 mm dia CI D/F Bend 90 Degree,100 mm dia CI A/F Tee, 100 mm dia D/F pipe (1.5 m long 2 nos. and 1 m long 1 no.), earthing, painting, Toolset, stabilizer, wiring of pump house internal and external, chainpully block , and all pumping plant accessories with nut bolts and rubber packing etc. |
| 262 | SCADA compatable chlorinatingSystem |
| 263 | Supply & Erection of Servo Stabilizer of 15 KVA |
| 264 | Supply & Erection of Servo Stabilizer of 20 KVA |
| 265 | Supply & Erection of Servo Stabilizer of 30KVA |
| 266 | Supply & Erection of Servo Stabilizer of 40 KVA |
| 267 | CE / UL certified Intelligent smart energy meter |
| 268 | Motor OperatedActuator having positioning card with Sluice Valve (150mm) |
| 269 | Motor OperatedActuator having positioning card with Sluice Valve (100mm) |
| 270 | CE / UL certified Electromagneticflowmeter of size:150mm |
| 271 | CE / UL certified Electromagneticflowmeter of size:100mm |
| 272 | Digital Soft starter (7.5 KW) |
| 273 | Digital Soft starter (15 - 22KW) |
| 274 | Digital Soft starter (22 -30KW) |
| 275 | Digital Soft starter (30 -45KW) |
| 276 | Auto phase reversal unit with inbuilt time delay & enclosure conforming to IEC: 60947-1 & IEC:60947-b-1) (100 Amps) |
| 277 | CE / UL certified Hydrostatatic type sub soil water level transmitter |
| 278 | CE / UL certified Pressure Transmitter |
| 279 | CE / UL certified Surge protector for control panel |
| 280 | CE / UL certified 7\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 281 | Control panel with IP 54 protection, industrial grade from all equipments (separate for control (24V) and power equipments. |
| 282 | Complete Cabling for tubewell including all power & control cables of all equipment at pumphouse and OHT |
| 283 | Suppy and Installation of Suitable Size Armored Cable including copper lugs etc. complete work. |
| 284 | Internal electrification of pump house and chlorinating room. |
| 285 | SITC ofSCADA And Automation for New/Existing TWs |
| 286 | Fully Automation of T/W through SCADA complete in all respect e.g. supply installationtesting of all required RTU, wireless communication device, control panel, PLC, Programming,software, Licences, wiring etc complete in all respect including mobile based app development and interconnection with LCS,MCS central control room Barabanki & central control room Lucknow as per 24 x 7 water supply requirement. |
| 287 | Pumping Plant & Instrumentation Of CWR Zone 1 |
| 288 | V.T. Pump- Motor Set |
| 289 | 1900 LPM 40M head Clear Water 1450 RPM,surfacedischarge,self water lubricated, Bottom Suction with 150 mm dia size & 6 M long column Assembly ( Column Pipeshaft & Rubber spider) Discharge head, Top shaft, rachet to prevent reverse rotation, suitable to couple with 3 phase 4 Pole, Vertical hollow shaft1450 RPM squirrel cage 400 V±10% 50 Hz, AC, Motor etc. (or suitable head, H.P, RPM of pump motor & size & length of coloumn pipes as per site condition and direction of engineer in charge) |
| 290 | Starter |
| 291 | Provision of Digital Soft Starter to operate Upto 35 HP motor(or suitable Capacity as per site condition and direction of engineer in charge) at 0.4KV +10%3phase,50Hz. A.C. and to control the above motors. It shall comprise of all protection devicesas per latest I.S.S. specifications. |
| 292 | L.T. Switchgear Panel Board |
| 293 | Provision of 1 no. panelextensible typeswitchboard suitable for 0.4 KV3 phase 50 HZ. A.C. in cubical pattern, floor mountingcompletewith insulatedbus bars of suitable size forrequiredload. The switch board shall consist of the following : a. Oneno.Incoming Panelcomprisingof100AmpsMCCB indoor vertical isolation horizontally drawouttype withrelays as per ISS.Panelwill be comprisingof voltmeterwith selector switch, power factor meter,frequencymeter. KWH meter and ammetercomplete with selector switch, motor protection relay etc to operate 03 nos. 35 H.P. motor(or suitable Capacity as per site condition and direction of engineer in charge). . b. 3 Nos. outgoing panelsfor pumping plants. Each panel of 100Amps capacity MCCB with ammeter and C.T.with selector switch, KW meter, single phasing preventer, capacitor etc to operate 03 nos. 35 H.P. motor. c. 2 No. outgoing panels for misc. work comprising of 100Amp MCCB. |
| 294 | Provision and laying of PVC armoured Power cables of requiredsizes with earthing material.for internal wiring i.e Panel to Starters and from Starters to Motors |
| 295 | Delivery pipes and specials as per details given below (or suitable size as per site condition and direction of engineer in charge): 150 mm size individual delivery and 250 mm size common delivery with jointing material, valves, Tee, bends etc.a. 150 mm dia Detachable Joint-3 Nosb. 150 mm dia Bend- 3 Nosc. 150 X 250 mm Tee- 3 Nos d. 250 mm Reflux Valve-1 Nos.e. 250 mm dia Duckfoot Bend-1 Nos.f. 250 mm dia Common Header-15 M g. 250 mm dia Blind Flange-1 No |
| 296 | Provision of MS Girder for pump base etc. |
| 297 | Chukkered Plate and Grills to cover the Gaps between Girder and Adjacent Pumps |
| 298 | Internal electrification of Pump House (CWR), Pannel roomand campus with Light & Fan wiring and& other Necessary works. |
| 299 | Supply of Electro menhanical type chlorinating plant 0 to 30 LPHcapacity pump set Suitable for 500 Kg./Cm2 working pressure to feedsodiumhypochloridesolutioncomplete ste, Sodium Hypochloride liquid is used in this type of chlorinator which contains 120 gms of chlorine in 1000 ml Quantity Confirming quality Manegment System Standard NS-EN ISO 9001-2000 |
| 300 | H.O.T. crane of 3 Tones capacity , Lift 4.5 Mtr |
| 301 | Testing of pumps & other equipment at work site |
| 302 | Painting of equipment with two coats. |
| 303 | CE / UL certified Intelligent smart energy meter |
| 304 | Motor Operatedsluice valve with Actuator for Pumps(150mm)(or suitable size as per site condition and direction of engineer in charge) |
| 305 | Motor Operatedsluice valve with Actuator for Common Header (250mm)(or suitable size as per site condition and direction of engineer in charge) |
| 306 | Electromagneticflowmeter of size: 250mm for common header(or suitable size as per site condition and direction of engineer in charge) |
| 307 | Auto phase reversal unit with inbuilt time delay & enclosure conforming to IEC: 60947-1 & IEC:60947-b-1) (160 Amps) |
| 308 | CE / UL certifiedRadar type Level Transmitter for CWR |
| 309 | CE / UL certifiedSmart Pressure Transmitter |
| 310 | CE / UL certified Surge protector for control panel |
| 311 | CE / UL certified 7\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 312 | Complete Cabling for ZPS including all power & control cable of all equipments at ZPS and OHT |
| 313 | Control panel with IP 54 protection, industrial grade fro all equipments (separate for control (24V) and power equipments. |
| 314 | Installation, commissioning & testing |
| 315 | Pumping Plant & Instrumentation Of CWR Zone 2 |
| 316 | V.T. Pump- Motor Set |
| 317 | 2700 LPM 40M head Clear Water 1450 RPM, surfacedischarge,self water lubricated, Bottom Suction with 200 mm dia size 6 M long column Assembly ( Column Pipeshaft & Rubber spider) Discharge head, Top shaft, rachet to prevent reverse rotation, suitable to couple with 3 phase 4 Pole, Vertical hollow shaft1450 RPM squirrel cage 400 V±10% 50 Hz, AC, Motor etc. (or suitable head, H.P, RPM of pump motor & size & length of coloumn pipes as per site condition and direction of engineer in charge) |
| 318 | Starter |
| 319 | Provision of Digital Soft Starter to operate Upto 40 HP motor(or suitable Capacity as per site condition and direction of engineer in charge) at 0.4KV +10%3phase,50Hz. A.C. and to control the above motors. It shall comprise of all protection devicesas per latest I.S.S. specifications. |
| 320 | L.T. Switchgear Panel Board |
| 321 | Provision of 1 no. panelextensible typeswitchboard suitable for 0.4 KV3 phase 50 HZ. A.C. in cubical pattern, floor mountingcompletewith insulatedbus bars of suitable size forrequiredload. The switch board shall consist of the following : a. Oneno.Incoming Panelcomprisingof100AmpsMCCB indoor vertical isolation horizontally drawouttype withrelays as per ISS.Panelwill be comprisingof voltmeterwith selector switch, power factor meter,frequencymeter. KWH meter and ammetercomplete with selector switch, motor protection relay etc to operate 03 nos. 40 H.P. motor(or suitable Capacity as per site condition and direction of engineer in charge).. b. 3 Nos. outgoing panelsfor pumping plants. Each panel of 100Amps capacity MCCB with ammeter and C.T.with selector switch, KW meter, single phasing preventer, capacitor etc to operate 03 nos. 40 H.P. motor. c. 2 No. outgoing panels for misc. work comprising of 100Amp MCCB. |
| 322 | Provision and laying of PVC armoured Power cables of requiredsizes with earthing material.for internal wiring i.e Panel to Starters and from Starters to Motors |
| 323 | Delivery pipes and specials as per details given below(or suitable size as per site condition and direction of engineer in charge) : 200 mm size individual delivery and 250 mm size common delivery with jointing material, valves, Tee, bends etc. a. 200 mm dia Detachable Joint-3 Nosb. 200 mm dia Bend- 3 Nos c. 200 X 250 mm Tee- 3 Nos d. 250 mm Reflux Valve-1 Nos.e. 250 mm dia Duckfoot Bend-1 Nos.f. 250 mm dia Common Header-15 Mg. 250 mm dia Blind Flange-1 No |
| 324 | Provision of MS Girder for pump base etc. |
| 325 | Chukkered Plate and Grills to cover the Gaps between Girder and Adjacent Pumps |
| 326 | Internal electrification of Pump House (CWR), Pannel roomand campus with Light & Fan wiring and& other Necessary works. |
| 327 | Supply of Electro menhanical type chlorinating plant 0 to 30 LPHcapacity pump set Suitable for 500 Kg./Cm2 working pressure to feedsodiumhypochloridesolutioncomplete ste, Sodium Hypochloride liquid is used in this type of chlorinator which contains 120 gms of chlorine in 1000 ml Quantity Confirming quality Manegment System Standard NS-EN ISO 9001-2000 |
| 328 | H.O.T. crane of 3 Tones capacity , Lift 4.5 Mtr |
| 329 | Testing of pumps & other equipment at work site |
| 330 | Painting of equipment with two coats. |
| 331 | CE / UL certified Intelligent smart energy meter |
| 332 | Motor Operatedsluice valve with Actuator for Pumps(200mm)(or suitable size as per site condition and direction of engineer in charge) |
| 333 | Motor Operatedsluice valve with Actuator for Common Header (250mm)(or suitable size as per site condition and direction of engineer in charge) |
| 334 | Electromagneticflowmeter of size: 250mm for common header(or suitable size as per site condition and direction of engineer in charge) |
| 335 | Auto phase reversal unit with inbuilt time delay & enclosure conforming to IEC: 60947-1 & IEC:60947-b-1) (160 Amps) |
| 336 | CE / UL certifiedRadar type Level Transmitter for CWR |
| 337 | CE / UL certifiedSmart Pressure Transmitter |
| 338 | CE / UL certified Surge protector for control panel |
| 339 | CE / UL certified 7\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 340 | Complete Cabling for ZPS including all power & control cable of all equipments at ZPS and OHT |
| 341 | Control panel with IP 54 protection, industrial grade fro all equipments (separate for control (24V) and power equipments. |
| 342 | Installation, commissioning & testing |
| 343 | Pumping Plant & Instrumentation Of CWR Zone 3 |
| 344 | V.T. Pump- Motor Set |
| 345 | 1900 LPM 40M head Clear Water 1450 RPM,surfacedischarge,self water lubricated, Bottom Suction with150 mm dia & 6 M long column Assembly ( Column Pipeshaft & Rubber spider) Discharge head, Top shaft, rachet to prevent reverse rotation, suitable to couple with 3 phase 4 Pole, Vertical hollow shaft1450 RPM squirrel cage 400 V±10% 50 Hz, AC, Motor etc. (or suitable head, H.P, RPM of pump motor & size & length of coloumn pipes as per site condition and direction of engineer in charge) |
| 346 | Starter |
| 347 | Provision of Digital Soft Starter to operate Upto 35 HP motor(or suitable Capacity as per site condition and direction of engineer in charge)at 0.4KV +10%3phase,50Hz. A.C. and to control the above motors. It shall comprise of all protection devicesas per latest I.S.S. specifications. |
| 348 | L.T. Switchgear Panel Board |
| 349 | Provision of 1 no. panelextensible typeswitchboard suitable for 0.4 KV3 phase 50 HZ. A.C. in cubical pattern, floor mountingcompletewith insulatedbus bars of suitable size forrequiredload. The switch board shall consist of the following : a. Oneno.Incoming Panelcomprisingof100AmpsMCCB indoor vertical isolation horizontally drawouttype withrelays as per ISS.Panelwill be comprisingof voltmeterwith selector switch, power factor meter,frequencymeter. KWH meter and ammetercomplete with selector switch, motor protection relay etc to operate 03 nos. 35 H.P. motor(or suitable Capacity as per site condition and direction of engineer in charge). . b. 3 Nos. outgoing panelsfor pumping plants. Each panel of 100Amps capacity MCCB with ammeter and C.T.with selector switch, KW meter, single phasing preventer, capacitor etc to operate 03 nos. 35 H.P. motor. c. 2 No. outgoing panels for misc. work comprising of 100Amp MCCB. |
| 350 | Provision and laying of PVC armoured Power cables of requiredsizes with earthing material.for internal wiring i.e Panel to Starters and from Starters to Motors |
| 351 | Delivery pipes and specials as per details given below(or suitable size as per site condition and direction of engineer in charge) : 150 mm size individual delivery and 250 mm size common delivery with jointing material, valves, Tee, bends etc. a. 150 mm dia Detachable Joint-3 Nosb. 150 mm dia Bend- 3 Nosc. 150 X 250 mm Tee- 3 Nos d. 250 mm Reflux Valve-1 Nos. e. 250 mm dia Duckfoot Bend-1 Nos. f. 250 mm dia Common Header-15 Mg. 250 mm dia Blind Flange-1 No |
| 352 | Provision of MS Girder for pump base etc. |
| 353 | Chukkered Plate and Grills to cover the Gaps between Girder and Adjacent Pumps |
| 354 | Internal electrification of Pump House (CWR), Pannel roomand campus with Light & Fan wiring and& other Necessary works. |
| 355 | Supply of Electro menhanical type chlorinating plant 0 to 30 LPHcapacity pump set Suitable for 500 Kg./Cm2 working pressure to feedsodiumhypochloridesolutioncomplete ste, Sodium Hypochloride liquid is used in this type of chlorinator which contains 120 gms of chlorine in 1000 ml Quantity Confirming quality Manegment System Standard NS-EN ISO 9001-2000 |
| 356 | H.O.T. crane of 3 Tones capacity , Lift 4.5 Mtr |
| 357 | Testing of pumps & other equipment at work site |
| 358 | Painting of equipment with two coats. |
| 359 | CE / UL certified Intelligent smart energy meter |
| 360 | Motor Operatedsluice valve with Actuator for Pumps(150mm) (or suitable size as per site condition and direction of engineer in charge) |
| 361 | Motor Operatedsluice valve with Actuator for Common Header (250mm) (or suitable size as per site condition and direction of engineer in charge) |
| 362 | Electromagneticflowmeter of size: 250mm for common header (or suitable size as per site condition and direction of engineer in charge) |
| 363 | Auto phase reversal unit with inbuilt time delay & enclosure conforming to IEC: 60947-1 & IEC:60947-b-1) (160 Amps) |
| 364 | CE / UL certifiedRadar type Level Transmitter for CWR |
| 365 | CE / UL certifiedSmart Pressure Transmitter |
| 366 | CE / UL certified Surge protector for control panel |
| 367 | CE / UL certified 7\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 368 | Complete Cabling for ZPS including all power & control cable of all equipments at ZPS and OHT |
| 369 | Control panel with IP 54 protection, industrial grade fro all equipments (separate for control (24V) and power equipments. |
| 370 | Installation, commissioning & testing |
| 371 | Pumping Plant & Instrumentation Of CWR Zone 4 |
| 372 | V.T. Pump- Motor Set |
| 373 | 2200 LPM 40M head Clear Water 1450 RPM, surfacedischarge,self water lubricated, Bottom Suction with 200 mm dia size 6 M long column Assembly ( Column Pipeshaft & Rubber spider) Discharge head, Top shaft, rachet to prevent reverse rotation, suitable to couple with 3 phase 4 Pole, Vertical hollow shaft1450 RPM squirrel cage 400 V±10% 50 Hz, AC, Motor etc. (or suitable head, H.P, RPM of pump motor & size & length of coloumn pipes as per site condition and direction of engineer in charge) |
| 374 | Starter |
| 375 | Provision of Digital Soft Starter to operate Upto 35 HP motor(or suitable Capacity as per site condition and direction of engineer in charge) at 0.4KV +10%3phase,50Hz. A.C. and to control the above motors. It shall comprise of all protection devicesas per latest I.S.S. specifications. |
| 376 | L.T. Switchgear Panel Board |
| 377 | Provision of 1 no. panelextensible typeswitchboard suitable for 0.4 KV3 phase 50 HZ. A.C. in cubical pattern, floor mountingcompletewith insulatedbus bars of suitable size forrequiredload. The switch board shall consist of the following : a. Oneno.Incoming Panelcomprisingof100AmpsMCCB indoor vertical isolation horizontally drawouttype withrelays as per ISS.Panelwill be comprisingof voltmeterwith selector switch, power factor meter,frequencymeter. KWH meter and ammetercomplete with selector switch, motor protection relay etc to operate 03 nos. 35 H.P. motor(or suitable Capacity as per site condition and direction of engineer in charge).b. 3 Nos. outgoing panelsfor pumping plants. Each panel of 100Amps capacity MCCB with ammeter and C.T.with selector switch, KW meter, single phasing preventer, capacitor etc to operate 03 nos. 35 H.P. motor. c. 2 No. outgoing panels for misc. work comprising of 100Amp MCCB. |
| 378 | Provision and laying of PVC armoured Power cables of requiredsizes with earthing material.for internal wiring i.e Panel to Starters and from Starters to Motors |
| 379 | Delivery pipes and specials as per details given below(or suitable size as per site condition and direction of engineer in charge) : 200 mm size individual delivery and 250 mm size common delivery with jointing material, valves, Tee, bends etc. a. 200 mm dia Detachable Joint-3 Nosb. 200 mm dia Bend- 3 Nos c. 200 X 250 mm Tee- 3 Nos d. 250 mm Reflux Valve-1 Nos.e. 250 mm dia Duckfoot Bend-1 Nos.f. 250 mm dia Common Header-15 Mg. 250 mm dia Blind Flange-1 No |
| 380 | Provision of MS Girder for pump base etc. |
| 381 | Chukkered Plate and Grills to cover the Gaps between Girder and Adjacent Pumps |
| 382 | Internal electrification of Pump House (CWR), Pannel roomand campus with Light & Fan wiring and& other Necessary works. |
| 383 | Supply of Electro menhanical type chlorinating plant 0 to 30 LPHcapacity pump set Suitable for 500 Kg./Cm2 working pressure to feedsodiumhypochloridesolutioncomplete ste, Sodium Hypochloride liquid is used in this type of chlorinator which contains 120 gms of chlorine in 1000 ml Quantity Confirming quality Manegment System Standard NS-EN ISO 9001-2000 |
| 384 | H.O.T. crane of 3 Tones capacity , Lift 4.5 Mtr |
| 385 | Testing of pumps & other equipment at work site |
| 386 | Painting of equipment with two coats. |
| 387 | CE / UL certified Intelligent smart energy meter |
| 388 | Motor Operatedsluice valve with Actuator for Pumps(200mm)(or suitable size as per site condition and direction of engineer in charge) |
| 389 | Motor Operatedsluice valve with Actuator for Common Header (250mm)(or suitable size as per site condition and direction of engineer in charge) |
| 390 | Electromagneticflowmeter of size: 250mm for common header(or suitable size as per site condition and direction of engineer in charge) |
| 391 | Auto phase reversal unit with inbuilt time delay & enclosure conforming to IEC: 60947-1 & IEC:60947-b-1) (160 Amps) |
| 392 | CE / UL certifiedRadar type Level Transmitter for CWR |
| 393 | CE / UL certifiedSmart Pressure Transmitter |
| 394 | CE / UL certified Surge protector for control panel |
| 395 | CE / UL certified 7\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 396 | Complete Cabling for ZPS including all power & control cable of all equipments at ZPS and OHT |
| 397 | Control panel with IP 54 protection, industrial grade fro all equipments (separate for control (24V) and power equipments. |
| 398 | Installation, commissioning & testing |
| 399 | Pumping Plant & Instrumentation Of CWR Zone 7 |
| 400 | V.T. Pump- Motor Set |
| 401 | 1500 LPM 40M head Clear Water 1450 RPM,surfacedischarge,self water lubricated, Bottom Suction with150 mm dia & 6 M long column Assembly ( Column Pipeshaft & Rubber spider) Discharge head, Top shaft, rachet to prevent reverse rotation, suitable to couple with 3 phase 4 Pole, Vertical hollow shaft1450 RPM squirrel cage 400 V±10% 50 Hz, AC, Motor etc. (or suitable head, H.P, RPM of pump motor & size & length of coloumn pipes as per site condition and direction of engineer in charge) |
| 402 | Starter |
| 403 | Provision of Digital Soft Starter to operate Upto 35 HP motor at 0.4KV +10%3phase,50Hz. A.C. and to control the above motors. It shall comprise of all protection devicesas per latest I.S.S. specifications. |
| 404 | L.T. Switchgear Panel Board |
| 405 | Provision of 1 no. panelextensible typeswitchboard suitable for 0.4 KV3 phase 50 HZ. A.C. in cubical pattern, floor mountingcompletewith insulatedbus bars of suitable size forrequiredload. The switch board shall consist of the following : a. Oneno.Incoming Panelcomprisingof100AmpsMCCB indoor vertical isolation horizontally drawouttype withrelays as per ISS.Panelwill be comprisingof voltmeterwith selector switch, power factor meter,frequencymeter. KWH meter and ammetercomplete with selector switch, motor protection relay etc to operate 03 nos. 35 H.P. motor(or suitable Capacity as per site condition and direction of engineer in charge)..b. 3 Nos. outgoing panelsfor pumping plants. Each panel of 100Amps capacity MCCB with ammeter and C.T.with selector switch, KW meter, single phasing preventer, capacitor etc to operate 03 nos. 35 H.P. motor. c. 2 No. outgoing panels for misc. work comprising of 100Amp MCCB. |
| 406 | Provision and laying of PVC armoured Power cables of requiredsizes with earthing material.for internal wiring i.e Panel to Starters and from Starters to Motors |
| 407 | Delivery pipes and specials as per details given below(or suitable size as per site condition and direction of engineer in charge) : 150 mm size individual delivery and 250 mm size common delivery with jointing material, valves, Tee, bends etc. a. 150 mm dia Detachable Joint-3 Nosb. 150 mm dia Bend- 3 Nosc. 150 X 200 mm Tee- 3 Nos d. 200 mm Reflux Valve-1 Nos.e. 200 mm dia Duckfoot Bend-1 Nos.f. 200 mm dia Common Header-15 Mg. 200 mm dia Blind Flange-1 No |
| 408 | Provision of MS Girder for pump base etc. |
| 409 | Chukkered Plate and Grills to cover the Gaps between Girder and Adjacent Pumps |
| 410 | Internal electrification of Pump House (CWR), Pannel roomand campus with Light & Fan wiring and& other Necessary works. |
| 411 | Supply of Electro menhanical type chlorinating plant 0 to 30 LPHcapacity pump set Suitable for 500 Kg./Cm2 working pressure to feedsodiumhypochloridesolutioncomplete ste, Sodium Hypochloride liquid is used in this type of chlorinator which contains 120 gms of chlorine in 1000 ml Quantity Confirming quality Manegment System Standard NS-EN ISO 9001-2000 |
| 412 | H.O.T. crane of 3 Tones capacity , Lift 4.5 Mtr |
| 413 | Testing of pumps & other equipment at work site |
| 414 | Painting of equipment with two coats. |
| 415 | CE / UL certified Intelligent smart energy meter |
| 416 | Motor Operatedsluice valve with Actuator for Pumps(150mm)(or suitable size as per site condition and direction of engineer in charge) |
| 417 | Motor Operatedsluice valve with Actuator for Common Header (200mm)(or suitable size as per site condition and direction of engineer in charge) |
| 418 | Electromagneticflowmeter of size: 200mm for common header(or suitable size as per site condition and direction of engineer in charge) |
| 419 | Auto phase reversal unit with inbuilt time delay & enclosure conforming to IEC: 60947-1 & IEC:60947-b-1) (100 Amps) |
| 420 | CE / UL certifiedRadar type Level Transmitter for CWR |
| 421 | CE / UL certifiedSmart Pressure Transmitter |
| 422 | CE / UL certified Surge protector for control panel |
| 423 | CE / UL certified 7\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 424 | Complete Cabling for ZPS including all power & control cable of all equipments at ZPS and OHT |
| 425 | Control panel with IP 54 protection, industrial grade fro all equipments (separate for control (24V) and power equipments. |
| 426 | Installation, commissioning & testing |
| 427 | Pumping Plant & Instrumentation Of CWR Zone 8 |
| 428 | V.T. Pump- Motor Set |
| 429 | 2500 LPM 40M head Clear Water 1450 RPM, surfacedischarge,self water lubricated, Bottom Suction with 200 mm dia size 6 M long column Assembly ( Column Pipeshaft & Rubber spider) Discharge head, Top shaft, rachet to prevent reverse rotation, suitable to couple with 3 phase 4 Pole, Vertical hollow shaft1450 RPM squirrel cage 400 V±10% 50 Hz, AC, Motor etc. (or suitable head, H.P, RPM of pump motor & size & length of coloumn pipes as per site condition and direction of engineer in charge) |
| 430 | Starter |
| 431 | Provision of Digital Soft Starter to operate Upto 40 HP motor(or suitable Capacity as per site condition and direction of engineer in charge) at 0.4KV +10%3phase,50Hz. A.C. and to control the above motors. It shall comprise of all protection devicesas per latest I.S.S. specifications. |
| 432 | L.T. Switchgear Panel Board |
| 433 | Provision of 1 no. panelextensible typeswitchboard suitable for 0.4 KV3 phase 50 HZ. A.C. in cubical pattern, floor mountingcompletewith insulatedbus bars of suitable size forrequiredload. The switch board shall consist of the following : a. Oneno.Incoming Panelcomprisingof100AmpsMCCB indoor vertical isolation horizontally drawouttype withrelays as per ISS.Panelwill be comprisingof voltmeterwith selector switch, power factor meter,frequencymeter. KWH meter and ammetercomplete with selector switch, motor protection relay etc to operate 03 nos. 40 H.P. motor(or suitable Capacity as per site condition and direction of engineer in charge)..b. 3 Nos. outgoing panelsfor pumping plants. Each panel of 100Amps capacity MCCB with ammeter and C.T.with selector switch, KW meter, single phasing preventer, capacitor etc to operate 03 nos. 40 H.P. motor. c. 2 No. outgoing panels for misc. work comprising of 100Amp MCCB. |
| 434 | Provision and laying of PVC armoured Power cables of requiredsizes with earthing material.for internal wiring i.e Panel to Starters and from Starters to Motors |
| 435 | Delivery pipes and specials as per details given below(or suitable size as per site condition and direction of engineer in charge) : 200 mm size individual delivery and 250 mm size common delivery with jointing material, valves, Tee, bends etc. a. 200 mm dia Detachable Joint-3 Nosb. 200 mm dia Bend- 3 Nos c. 200 X 250 mm Tee- 3 Nos d. 250 mm Reflux Valve-1 Nos.e. 250 mm dia Duckfoot Bend-1 Nos.f. 250 mm dia Common Header-15 Mg. 250 mm dia Blind Flange-1 No |
| 436 | Provision of MS Girder for pump base etc. |
| 437 | Chukkered Plate and Grills to cover the Gaps between Girder and Adjacent Pumps |
| 438 | Internal electrification of Pump House (CWR), Pannel roomand campus with Light & Fan wiring and& other Necessary works. |
| 439 | Supply of Electro menhanical type chlorinating plant 0 to 30 LPHcapacity pump set Suitable for 500 Kg./Cm2 working pressure to feedsodiumhypochloridesolutioncomplete ste, Sodium Hypochloride liquid is used in this type of chlorinator which contains 120 gms of chlorine in 1000 ml Quantity Confirming quality Manegment System Standard NS-EN ISO 9001-2000 |
| 440 | H.O.T. crane of 3 Tones capacity , Lift 4.5 Mtr |
| 441 | Testing of pumps & other equipment at work site |
| 442 | Painting of equipment with two coats. |
| 443 | CE / UL certified Intelligent smart energy meter |
| 444 | Motor Operatedsluice valve with Actuator for Pumps(200mm)(or suitable size as per site condition and direction of engineer in charge) |
| 445 | Motor Operatedsluice valve with Actuator for Common Header (250mm)(or suitable size as per site condition and direction of engineer in charge) |
| 446 | Electromagneticflowmeter of size: 250mm for common header(or suitable size as per site condition and direction of engineer in charge) |
| 447 | Auto phase reversal unit with inbuilt time delay & enclosure conforming to IEC: 60947-1 & IEC:60947-b-1) (160 Amps) |
| 448 | CE / UL certifiedRadar type Level Transmitter for CWR |
| 449 | CE / UL certifiedSmart Pressure Transmitter |
| 450 | CE / UL certified Surge protector for control panel |
| 451 | CE / UL certified 7\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 452 | Complete Cabling for ZPS including all power & control cable of all equipments at ZPS and OHT |
| 453 | Control panel with IP 54 protection, industrial grade fro all equipments (separate for control (24V) and power equipments. |
| 454 | Installation, commissioning & testing |
| 455 | Pumping Plant & Instrumentation Of CWRZone 10 |
| 456 | V.T. Pump- Motor Set |
| 457 | 2400 LPM 40M head Clear Water 1450 RPM, surfacedischarge,self water lubricated, Bottom Suction with 200 mm dia size 6 M long column Assembly ( Column Pipeshaft & Rubber spider) Discharge head, Top shaft, rachet to prevent reverse rotation, suitable to couple with 3 phase 4 Pole, Vertical hollow shaft1450 RPM squirrel cage 400 V±10% 50 Hz, AC, Motor etc. (or suitable head, H.P, RPM of pump motor & size & length of coloumn pipes as per site condition and direction of engineer in charge) |
| 458 | Starter |
| 459 | Provision of Digital Soft Starter to operate Upto 40 HP motor(or suitable Capacity as per site condition and direction of engineer in charge) at 0.4KV +10%3phase,50Hz. A.C. and to control the above motors. It shall comprise of all protection devicesas per latest I.S.S. specifications. |
| 460 | L.T. Switchgear Panel Board |
| 461 | Provision of 1 no. panelextensible typeswitchboard suitable for 0.4 KV3 phase 50 HZ. A.C. in cubical pattern, floor mountingcompletewith insulatedbus bars of suitable size forrequiredload. The switch board shall consist of the following : a. Oneno.Incoming Panelcomprisingof100AmpsMCCB indoor vertical isolation horizontally drawouttype withrelays as per ISS.Panelwill be comprisingof voltmeterwith selector switch, power factor meter,frequencymeter. KWH meter and ammetercomplete with selector switch, motor protection relay etc to operate 03 nos. 40 H.P. motor(or suitable Capacity as per site condition and direction of engineer in charge).. b. 3 Nos. outgoing panelsfor pumping plants. Each panel of 100Amps capacity MCCB with ammeter and C.T.with selector switch, KW meter, single phasing preventer, capacitor etc to operate 03 nos. 40 H.P. motor. c. 2 No. outgoing panels for misc. work comprising of 100Amp MCCB. |
| 462 | Provision and laying of PVC armoured Power cables of requiredsizes with earthing material.for internal wiring i.e Panel to Starters and from Starters to Motors |
| 463 | Delivery pipes and specials as per details given below(or suitable size as per site condition and direction of engineer in charge) : 200 mm size individual delivery and 250 mm size common delivery with jointing material, valves, Tee, bends etc. a. 200 mm dia Detachable Joint-3 Nosb. 200 mm dia Bend- 3 Nos c. 200 X 250 mm Tee- 3 Nos d. 250 mm Reflux Valve-1 Nos.e. 250 mm dia Duckfoot Bend-1 Nos.f. 250 mm dia Common Header-15 Mg. 250 mm dia Blind Flange-1 No |
| 464 | Provision of MS Girder for pump base etc. |
| 465 | Chukkered Plate and Grills to cover the Gaps between Girder and Adjacent Pumps |
| 466 | Internal electrification of Pump House (CWR), Pannel roomand campus with Light & Fan wiring and& other Necessary works. |
| 467 | Supply of Electro menhanical type chlorinating plant 0 to 30 LPHcapacity pump set Suitable for 500 Kg./Cm2 working pressure to feedsodiumhypochloridesolutioncomplete ste, Sodium Hypochloride liquid is used in this type of chlorinator which contains 120 gms of chlorine in 1000 ml Quantity Confirming quality Manegment System Standard NS-EN ISO 9001-2000 |
| 468 | H.O.T. crane of 3 Tones capacity , Lift 4.5 Mtr |
| 469 | Testing of pumps & other equipment at work site |
| 470 | Painting of equipment with two coats. |
| 471 | CE / UL certified Intelligent smart energy meter |
| 472 | Motor Operatedsluice valve with Actuator for Pumps(200mm)(or suitable size as per site condition and direction of engineer in charge) |
| 473 | Motor Operatedsluice valve with Actuator for Common Header (250mm)(or suitable size as per site condition and direction of engineer in charge) |
| 474 | Electromagneticflowmeter of size: 250mm for common header(or suitable size as per site condition and direction of engineer in charge) |
| 475 | Auto phase reversal unit with inbuilt time delay & enclosure conforming to IEC: 60947-1 & IEC:60947-b-1) (160 Amps) |
| 476 | CE / UL certifiedRadar type Level Transmitter for CWR |
| 477 | CE / UL certifiedSmart Pressure Transmitter |
| 478 | CE / UL certified Surge protector for control panel |
| 479 | CE / UL certified 7\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 480 | Complete Cabling for ZPS including all power & control cable of all equipments at ZPS and OHT |
| 481 | Control panel with IP 54 protection, industrial grade fro all equipments (separate for control (24V) and power equipments. |
| 482 | Installation, commissioning & testing |
| 483 | Automation of CWR For All ZONEs |
| 484 | CE & UL approved manufacturer’s RTU/ PLC in IP 54 encloser suitable to communicate with GSM based modem unit with CPU and power supply with analog and digital parameter and features as specified, onefor each tubewellto store and transmit data on GSM backbone. RTU/PLC designed with logic to transfer data at multiple stations. G.S.M./G.P.R.S. based wireless communication with 4G Modem for RTU/ PLC Capable to transfer and gather data from remote sites to control stations, all accessories included with signal enhancer anteena made for pumping plant |
| 485 | Automation of All Zone OHT |
| 486 | Automation of existing/new OHT & associated infrastructure as per actual site requirement like existing/new Tubewells related valves, pressure transmitters,level sensors, chlorination system, OHT outlet flowmeter, OHT outlet acutator valves with positioning card,required RTU panel, control & power wiring, earthing including SITC /repairing of already existing equipments (in case of existing OHT)complete in all respect in a way to complete automation as per CPHEEO drink from tap mannual further associated guidelines. |
| 487 | DMA /ESR Automation for Zone-1 |
| 488 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 489 | Double Solenoid Flow Control Valve 350 mm Dia |
| 490 | Pressure Transmitter |
| 491 | Mannual Pressure Transmitter |
| 492 | CE / UL certified Electromagnetic flowmeter of size 350 mm Dia |
| 493 | SCADA Compatible Chlorinating Plant |
| 494 | Design, SITC of Booster pumps asper 24 x 7 water supply requirements with 50% standby of peak water demand along with main piping and actuator valves and bypass arrangement,extra pressure transmiiter, VFD drive, PLC panel, TDS analyser, power and control wiring complete in all respect considering all DMAs |
| 495 | Resedual Chlorine Analyser |
| 496 | DMA /ESR Automation for Zone-2 |
| 497 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 498 | Double Solenoid Flow Control Valve 250 mm |
| 499 | Double Solenoid Flow Control Valve 300 mm |
| 500 | Pressure Transmitter |
| 501 | Mannual Pressure Transmitter |
| 502 | CE / UL certified Electromagnetic flowmeter of size250 mm Dia |
| 503 | Design, SITC of Booster pumps asper 24 x 7 water supply requirements with 50% standby of peak water demand along with main piping and actuator valves and bypass arrangement,extra pressure transmiiter, VFD drive, PLC panel, TDS analyser, power and control wiring complete in all respect considering all DMAs |
| 504 | CE / UL certified Electromagnetic flowmeter of size 300 mm Dia |
| 505 | SCADA Compatible Chlorinating Plant |
| 506 | Resedual Chlorine Analyser |
| 507 | DMA /ESR Automation for Zone-3 |
| 508 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 509 | Double Solenoid Flow Control Valve350 mm Dia |
| 510 | Pressure Transmitter |
| 511 | Mannual Pressure Transmitter |
| 512 | CE / UL certified Electromagnetic flowmeter of size 350 mm Dia |
| 513 | Design, SITC of Booster pumps asper 24 x 7 water supply requirements with 50% standby of peak water demand along with main piping and actuator valves and bypass arrangement,extra pressure transmiiter, VFD drive, PLC panel, TDS analyser, power and control wiring complete in all respect considering all DMAs |
| 514 | SCADA Compatible Chlorinating Plant |
| 515 | Resedual Chlorine Analyser |
| 516 | DMA /ESR Automation for Zone-4 |
| 517 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 518 | Double Solenoid Flow Control Valve 200 mm dia |
| 519 | Double Solenoid Flow Control Valve 300 mm dia |
| 520 | Pressure Transmitter |
| 521 | Mannual Pressure Transmitter |
| 522 | CE / UL certified Electromagnetic flowmeter of size200 mm dia |
| 523 | Design, SITC of Booster pumps asper 24 x 7 water supply requirements with 50% standby of peak water demand along with main piping and actuator valves and bypass arrangement,extra pressure transmiiter, VFD drive, PLC panel, TDS analyser, power and control wiring complete in all respect considering all DMAs |
| 524 | CE / UL certified Electromagnetic flowmeter of size300 mm dia |
| 525 | SCADA Compatible Chlorinating Plant |
| 526 | Resedual Chlorine Analyser |
| 527 | DMA /ESR Automation for Zone-5 |
| 528 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 529 | Double Solenoid Flow Control Valve 350 mm dia |
| 530 | Pressure Transmitter |
| 531 | Mannual Pressure Transmitter |
| 532 | CE / UL certified Electromagnetic flowmeter of size 350 mm dia |
| 533 | SCADA Compatible Chlorinating Plant |
| 534 | Resedual Chlorine Analyser |
| 535 | DMA /ESR Automation for Zone-6 |
| 536 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 537 | Double Solenoid Flow Control Valve350 mm dia |
| 538 | Pressure Transmitter |
| 539 | Mannual Pressure Transmitter |
| 540 | CE / UL certified Electromagnetic flowmeter of size 350 mm dia |
| 541 | SCADA Compatible Chlorinating Plant |
| 542 | Resedual Chlorine Analyser |
| 543 | DMA /ESR Automation for Zone-7 |
| 544 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 545 | Double Solenoid Flow Control Valve |
| 546 | Pressure Transmitter |
| 547 | Mannual Pressure Transmitter |
| 548 | CE / UL certified Electromagnetic flowmeter of size |
| 549 | Design, SITC of Booster pumps asper 24 x 7 water supply requirements with 50% standby of peak water demand along with main piping and actuator valves and bypass arrangement,extra pressure transmiiter, VFD drive, PLC panel, TDS analyser, power and control wiring complete in all respect considering all DMAs |
| 550 | SCADA Compatible Chlorinating Plant |
| 551 | Resedual Chlorine Analyser |
| 552 | DMA /ESR Automation for Zone-8 |
| 553 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 554 | Double Solenoid Flow Control Valve250 mm dia |
| 555 | Double Solenoid Flow Control Valve300 mm dia |
| 556 | Pressure Transmitter |
| 557 | Mannual Pressure Transmitter |
| 558 | CE / UL certified Electromagnetic flowmeter of size 250mm dia |
| 559 | CE / UL certified Electromagnetic flowmeter of size 300mm dia |
| 560 | SCADA Compatible Chlorinating Plant |
| 561 | Resedual Chlorine Analyser |
| 562 | DMA /ESR Automation for Zone-9 |
| 563 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 564 | Double Solenoid Flow Control Valve300 mm |
| 565 | Pressure Transmitter |
| 566 | Mannual Pressure Transmitter |
| 567 | CE / UL certified Electromagnetic flowmeter of size 300 mm |
| 568 | Design, SITC of Booster pumps asper 24 x 7 water supply requirements with 50% standby of peak water demand along with main piping and actuator valves and bypass arrangement,extra pressure transmiiter, VFD drive, PLC panel, TDS analyser, power and control wiring complete in all respect considering all DMAs |
| 569 | SCADA Compatible Chlorinating Plant |
| 570 | Resedual Chlorine Analyser |
| 571 | DMA /ESR Automation for Zone-10 |
| 572 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 573 | Double Solenoid Flow Control Valve 200 mm dia |
| 574 | Double Solenoid Flow Control Valve 300 mm dia |
| 575 | Pressure Transmitter |
| 576 | Mannual Pressure Transmitter |
| 577 | CE / UL certified Electromagnetic flowmeter of size 200 mm dia |
| 578 | CE / UL certified Electromagnetic flowmeter of size 300 mm dia |
| 579 | SCADA Compatible Chlorinating Plant |
| 580 | Resedual Chlorine Analyser |
| 581 | DMA /ESR Automation for Zone-11 |
| 582 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 583 | Double Solenoid Flow Control Valve350 mm dia |
| 584 | Pressure Transmitter |
| 585 | Mannual Pressure Transmitter |
| 586 | CE / UL certified Electromagnetic flowmeter of size350 mm dia |
| 587 | SCADA Compatible Chlorinating Plant |
| 588 | Resedual Chlorine Analyser |
| 589 | DMA /ESR Automation for Zone-12 |
| 590 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 591 | Double Solenoid Flow Control Valve300 mm dia |
| 592 | Pressure Transmitter |
| 593 | Mannual Pressure Transmitter |
| 594 | Design, SITC of Booster pumps asper 24 x 7 water supply requirements with 50% standby of peak water demand along with main piping and actuator valves and bypass arrangement,extra pressure transmiiter, VFD drive, PLC panel, TDS analyser, power and control wiring complete in all respect considering all DMAs |
| 595 | CE / UL certified Electromagnetic flowmeter of size 300 mm dia |
| 596 | SCADA Compatible Chlorinating Plant |
| 597 | Resedual Chlorine Analyser |
| 598 | DMA /ESR Automation for Zone-13 |
| 599 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 600 | Double Solenoid Flow Control Valve250 mm dia |
| 601 | Pressure Transmitter |
| 602 | Mannual Pressure Transmitter with Display |
| 603 | CE / UL certified Electromagnetic flowmeter of size 250 mm dia |
| 604 | SCADA Compatible Chlorinating Plant |
| 605 | Resedual Chlorine Analyser |
| 606 | DMA /ESR Automation for Zone-14 |
| 607 | Survey, design asset mapping, SITC of following equipments along with other requied infrastucture/equipments as per requirements and guidelines of 24x7 water supply requirements. The job includes SITC of all required software and hardwares not mentioned elsewhere & min. 8 hrs battery backup.. |
| 608 | Double Solenoid Flow Control Valve250 mm dia |
| 609 | Pressure Transmitter |
| 610 | Mannual Pressure Transmitter with Display |
| 611 | CE / UL certified Electromagnetic flowmeter of size 250 mm dia |
| 612 | SCADA Compatible Chlorinating Plant |
| 613 | Resedual Chlorine Analyser |
| 614 | SITC of SCADA MCS |
| 615 | SITC of MCS SCADAfor each DMA of all Zones including TWs, CWR, ESR/OHT complete in all respect. (or as per site condition and direction of engineer in charge or as per CPHEEO manual Drink from Tap Dec.2024) |
| 616 | Sub Station OfCWR Zone |
| 617 | Design & SITC of electric substation for CWR including 02 Nos.(01 Working+01 Standby) Transformer, 11 KV HT swicthgear panel with 01 No incoming and 02 Nos. outgoing VCB alongwith LT control panel having sufficient No of ACB/MCCB of suitable size for actual site equipment reqiremwnts with electrical interlocks and complete power and control cabling works, APFC, earthing, lighting arrester, TPMO Switch, safety SITCs barbed wire, H-Pole, foundation/plinth, lighting, Rubber mating, internal, external electrification, laisioning from Discom, NOC from electrical safety department,testing & commisioning complete in all respect with all labour material & T&Ps having capacity 100KVA/160KVA, 11/0.415 KV |
| 618 | Trail & Run |
| 619 | Three Months Trial & Run OfTubewell & SCADA with all consumable items |
| 620 | Three Months Trial & Run OfCWR with all consumable items |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy