| Sl. No. | Item Description |
| 1 | Civil Works |
| 2 | Construction of R.C.C Overhead Tank |
| 3 | Submission of vetted design, drawing and Supply of all materials, labour, T&P etc. and construct an RCC over head tank of M-30 concrete with following capacity with minimum freeboard of 15cm, RCC staircase and 1.2m wide balcony, G.I. Pipe and angle iron posts around the balcony and at the dome periphery, two column RCC staircasewith SS railing in a slope of 3:1 from the balcony to the top of tank and inside the tank, supply and fixing 10mm gauge M.H. cover of 60cm x 60cm size with locking device, ventilator, lightening conductor,digitalwater level indicator, fixing of puddle collars and bell mouths, supply and fixing M.S. clamps with RCC coloumn, 25 mm thick PCC 1:2:4 floor over 80 mm PCC 1:4:8 in appron, 150 mm semicircular drain around the tank, escape channel of 20m length, box type enclosure at the entrance of the staircase having locking arrangements, water proofing, three coats of approved quality Apex paint and testing of tank for water tightness etc. and including testing bearing capacity of soil , site clearance and other unforeseen items as per specifications in tender document and manuals etc. The depth of foundation is minimum 2.50m from existing Ground level on pile/ raft foundation or at more depth based on design of tank for which no extra claim shall be entertained. Made up level of OHt shall be taken as 0.60m above road level. Extra earth required for made up level shall be arranged by the contractor at his own cost.All works complete upto the satisfaction of Engineer-in-charge. |
| 4 | For Zone I -500 KL @ 20m staging:-Supply and fixing of C.I D/F pipes and C.I D/F sluice valvewith required specials such as reducers, duck foot bend, bell mouth etc in inlet of the tank including supply of MS clamps, rubber insertion sheet, nut bolts, washer etc complete as detailed for each pipe line a. C.I D/f pipe inlet - 2nos of 150 mm diab. C.I D/f pipe outlet - 2nos of 250mm diac. C.I D/f pipe overflow - 2nos of 250mm diad. C.I D/f pipe washout - 1nos of 100mm dia |
| 5 | For Zone II- 1400 KL @ 20m staging:-Supply and fixing of C.I D/F pipes and C.I D/F sluice valvewith required specials such as reducers, duck foot bend, bell mouth etc in inlet of the tank including supply of MS clamps, rubber insertion sheet, nut bolts, washer etc complete as detailed for each pipe line a. C.I D/f pipe inlet - 3nos of200 mm diab. C.I D/f pipe outlet - 2nos of 350mm diac. C.I D/f pipe overflow - 1nos of 350mm diad. C.I D/f pipe washout - 1nos of 100mm dia |
| 6 | For Zone III- 1400 KL @ 22m staging:-Supply and fixing of C.I D/F pipes and C.I D/F sluice valvewith required specials such as reducers, duck foot bend, bell mouth etc in inlet of the tank including supply of MS clamps, rubber insertion sheet, nut bolts, washer etc complete as detailed for each pipe line a. C.I D/f pipe inlet - 2nos of250 mm diab. C.I D/f pipe outlet - 2nos of 450mm diac. C.I D/f pipe overflow - 1nos of 450mm diad. C.I D/f pipe washout - 1nos of 100mm dia |
| 7 | Supply of materials, labour, T&P and construct brick masonary sluice valve chamber including RCC cover as per type dept. design at inlet, outlet and washout pipes. The RCC cover shall be casted in SS channel section with handles on both sides. (Chambers for washout and overflow may be combined) |
| 8 | The words U.P.Jal nigam (Urban) stating year of construction, capacity of OHT as per directions of Engineer-in-charge shall be painted prominently in letter not less than 30 cm in height. Maintenance for 12 months including supply of all materials etc complete. |
| 9 | Zone-I |
| 10 | 500 KL @ 20m staging |
| 11 | Zone-II |
| 12 | 1400 KL @ 20m staging |
| 13 | Zone-III |
| 14 | 1400 KL @ 22m staging |
| 15 | Construction of Pump Houses |
| 16 | Provide all materials, labour, T&P etc. complete and construct Pump house size (3.6x3.0)m Chlorinating room size (1.8 x 2.5x 3.0)m as per departmental type design and specifivations given in tender document including supply of labour, material etc for completion of works upto the satisfaction of Engineer-in-charge |
| 17 | Zone-I (1no), Zone-II(3no) and Zone-III(1no) |
| 18 | Renovation of Pump house |
| 19 | Renovation of Exisiting Pump House Building including electrification works, Replacement all type of Sluice valve,Cut-Out,Stater, clorination Plant/Dozer, instalation ofkirloskar make pump, relacement and lowering of Extra Required clolumn pipe upto suitabe depth blow water lewel and other required T&P material etc complete as required at site in directionof engineer in charege[Zone-I (1no), and Zone-III(4no)] |
| 20 | Distribution Network |
| 21 | Supply of the following D.I. pipes (k-7) including specials conforming to I.S -8329/2000 or its latest amendment(s). Including F.O.R. destinations rate per metre in Rs., anywhere in U.P. including cost of one Rubber Gasket per pipe length & inclusive of all Taxes & Duties, Third Party Inspection Charges, Packing & Forwarding Charges, Transit Insurance Charges, Road Transportation Charges etc. |
| 22 | Zone-I |
| 23 | 250mm diaD.I. (K-7 pipes) |
| 24 | 200 mm diaD.I. (K-7 pipes) |
| 25 | Zone-II |
| 26 | 350 mm diaD.I. (K-7 pipes) |
| 27 | 300 mm diaD.I. (K-7 pipes) |
| 28 | 250mm diaD.I. (K-7 pipes) |
| 29 | 200 mm diaD.I. (K-7 pipes) |
| 30 | Zone-III |
| 31 | 450 mm diaD.I. (K-7 pipes) |
| 32 | 350 mm diaD.I. (K-7 pipes) |
| 33 | 300 mm diaD.I. (K-7 pipes) |
| 34 | 250mm diaD.I. (K-7 pipes) |
| 35 | 200 mm diaD.I. (K-7 pipes) |
| 36 | Supply of the following HDPE Pipes PN-6/ PE-100 including electrofusion specials as per I.S. code no. 4984/14151/ 12786/13488 or its latest amendment in coils/ slandered lengths with necessary jointing material like elctrofusion coupler for Joints/ junctions, flanged joint, inclusive of third party inspection charges packing and forwarding charges, transit insurance charges, road transportation charges etc. F.O.R. destination etc. complete |
| 37 | Zone-I |
| 38 | 160 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 39 | 140 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 40 | 110 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 41 | Zone-II |
| 42 | 160 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 43 | 140 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 44 | 110 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 45 | Zone-III |
| 46 | 160 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 47 | 140 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 48 | 110 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 49 | Excavation for pipeline trenches in ordinary soil (loam,clay or sand) including lift upto 1.5m and lead upto 50m and refilling, watering, ramming of excavted earth in to the trenches and disposal of surplus earth upto 50m from the center of the trenches. D.I.( K-7) pipes. Guidelines on Environmental construction and demolition (C&D) wastes and GRAP circulated by Central Pollution Control board 2017 and its latest ammendments shall be adhered to for excavation of trench during laying of pipeline. Surplus material after backfilling shall be immediately removed from site and temporary restoration shall be done to make road motorable |
| 50 | Zone-I |
| 51 | Zone-II |
| 52 | Zone-III |
| 53 | Carting from the following sizes of D.I.Pipes (class K-7) and specials to the site of work, lowering them in to trenches and laying true to alignment and gradient, cutting of pipes, making joints including cost of jointing material, rubber rings, labour, T&P etc including hydraulic testing of pipeline. It includes making alignment on city roads, making of trial pits to investigate location of various undergroung services like telephone cables, electric cables, existing water and sewer lines complete required for proper completion of work. only SBR rubber gaskets to be used as per IS 5382 and IS 12820 including making bypass arrangement. |
| 54 | Zone-I |
| 55 | 250mm diaD.I. (K-7 pipes) |
| 56 | 200 mm dia. D.I. (K-7 pipes) |
| 57 | Zone-II |
| 58 | 350 mm dia. D.I. (K-7 pipes) |
| 59 | 300 mm dia. D.I. (K-7 pipes) |
| 60 | 250 mm dia. D.I. (K-7 pipes) |
| 61 | 200 mm dia. D.I. (K-7 pipes) |
| 62 | Zone-III |
| 63 | 450 mm diaD.I. (K-7 pipes) |
| 64 | 350 mm dia. D.I. (K-7 pipes) |
| 65 | 300 mm dia. D.I. (K-7 pipes) |
| 66 | 250 mm dia. D.I. (K-7 pipes) |
| 67 | 200 mm dia. D.I. (K-7 pipes) |
| 68 | Carting from the following sizes of HDPE PN-6/ PE-100 and specials to the site of work, lowering them in to trenches and laying true to alignment and gradient, cutting of pipes, making joints including cost of jointing material, rubber rings, labour, T&P etc including hydraulic testing of pipeline. It includes making alignment on city roads, making of trial pits to investigate location of various undergroung services like telephone cables, electric cables, existing water and sewer lines complete required for proper completion of work. only SBR rubber gaskets to be used as per IS 5382 and IS 12820 including making bypass arrangement.Jointing between HDPE pipes shall be done as per latest IS: 7634 part-II. only bar coded electro-fusion machine (automatically readable) that can read the bar code of the fittings automatically |
| 69 | Zone-I |
| 70 | 160 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 71 | 140 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 72 | 110 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 73 | Zone-II |
| 74 | 160 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 75 | 140 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 76 | 110 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 77 | Zone-III |
| 78 | 160 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 79 | 140 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 80 | 110 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 81 | Supply of the following dia of valves, class I, working pressure 10 Kg/cm2 confirmingto IS: 780/1969 or its latest amendments, F.O.R. destination, carting and lowering them into the already preparedtrenches, fixing in position and jointingthem with pipelines and testing etc. completeand also including supply of jointing materials etc. complete .including alltaxes and insurance, as per instructions of Engineer -in -charge. |
| 82 | Sluice/wheel valve (Surface Box type) |
| 83 | 300∅ |
| 84 | 250∅ |
| 85 | 200∅ |
| 86 | 150∅ |
| 87 | 125∅ |
| 88 | 100∅ |
| 89 | Scour Valve - 80 mm dia |
| 90 | Air valve - 50 mm dia |
| 91 | Fire Hydrant - 80 mm dia. |
| 92 | Dismantling of roads for laying of pipe line including sorting out and stacking of serviceable materials, stacking and disposal of unserviceable materials including dismantling and cleaning of septic tanks if any |
| 93 | Zone-I |
| 94 | B.O.E road |
| 95 | Bituminous road |
| 96 | Cement Concrete Road |
| 97 | Interlocking Road / Paver |
| 98 | Zone-II |
| 99 | B.O.E road |
| 100 | Bituminous road |
| 101 | Cement Concrete Road |
| 102 | Interlocking Road / Paver |
| 103 | Zone-III |
| 104 | B.O.E road |
| 105 | Bituminous road |
| 106 | Cement Concrete Road |
| 107 | Interlocking Road / Paver |
| 108 | Reinstatement of following type of roads dismantled during laying of pipe line including leakage repair if any and supply of all materials, labour and T & P etc. required for proper completion of the work. |
| 109 | Zone-I |
| 110 | B.O.E road |
| 111 | Bituminous road |
| 112 | Cement Concrete Road |
| 113 | Interlocking Road (40 % new & 60% quantity old bricks) |
| 114 | Zone-II |
| 115 | B.O.E road |
| 116 | Bituminous road |
| 117 | Cement Concrete Road |
| 118 | Interlocking Road (40 % new & 60% quantity old bricks) |
| 119 | Zone-III |
| 120 | B.O.E road |
| 121 | Bituminous road |
| 122 | Cement Concrete Road |
| 123 | Interlocking Road (40 % new & 60% quantity old bricks) |
| 124 | Provision of Road Cutting and reinstatement for PWD Roads for both zones of any thickness including cleaning of debris, removal of materials and restoring the same to originl condition as per PWD norms |
| 125 | Supply of all labour, materials, T&P etc. all complete and construction of following valve chambers as per type design.for both zones |
| 126 | Sluice valve (masonary type) |
| 127 | Sluice/ wheel Valve ( surface box type) |
| 128 | Air valve |
| 129 | Fire hydrant |
| 130 | Nala crossing/culvert/ Road crossing more than 3.5m width with carrier pipe including proper encasing of pipe and restoring the drain to original condition inluding supply of all materials, labour, T&P etc complete upto the satisfaction of Engineer-in-charge |
| 131 | Nala crossing (small) upto 3.5m width with carrier pipe and restoring the drain to original condition |
| 132 | House Connection |
| 133 | Provision of new single brass tap ferrule water house hold Connection with fixing of saddle (electrofusion tapping saddle) for making connection with HDPE distribution pipeline minimum 10m, DI strap saddle, ferrule for making connection with pipes other than HDPE, connection fittings, GM ferrule of 15mm dia including brass tape with welded, 20mm dia (OD) HDPE pipe (PE-100/ PN-12.5) and 20mm dia OD G.I pipe (minimum 1m) Class B upto house holder as per type design drawings and .including dismentlingof all type road, excavation, laying and jointing for proper completion of workas per instructions of Engineer-in-charge. Making house connection with all data like AAdhar Card/ address proof/mobile no and geotagging of house connections |
| 134 | Zone-I |
| 135 | 200 mm dia.-250 mm dia |
| 136 | 140 mm dia-180 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 137 | 90 mm dia-125 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 138 | Zone-II |
| 139 | 300 mm dia.-500 mm dia |
| 140 | 200 mm dia.-250 mm dia |
| 141 | 140 mm dia-180 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 142 | 90 mm dia-125 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 143 | Zone-III |
| 144 | 300 mm dia.-500 mm dia |
| 145 | 200 mm dia.-250 mm dia |
| 146 | 140 mm dia-180 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 147 | 90 mm dia-125 mm dia HDPE Pipe PN‐6: Class PE‐100 |
| 148 | Provision of reinstatement work for water house hold Connection including supply of all materials, labour and T & P etc. required for proper completion of the work. |
| 149 | Zone-I |
| 150 | B.O.E road |
| 151 | Bituminous Road |
| 152 | Cement Concrete road |
| 153 | Interlocking Road / Paver |
| 154 | Zone-II |
| 155 | B.O.E road |
| 156 | Bituminous Road |
| 157 | Cement Concrete road |
| 158 | Interlocking Road / Paver |
| 159 | Zone-III |
| 160 | B.O.E road |
| 161 | Bituminous Road |
| 162 | Cement Concrete road |
| 163 | Interlocking Road / Paver |
| 164 | Shifting of old house connections in different sizes of pipes including supply, carting of specials, lowering them into trenches, cutting, fixing them in proper alignment and jointing including necessary excavation for connection etc all complete |
| 165 | Provision of interconnection in existing pipe network AC/PVC/ DI/HDPE pipe including supply, carting of specials, lowering them into trenches, cutting, fixing in proper alignment including bailing out wateretc all necessary works complete upto the satisfaction of Engineer-in-charge |
| 166 | 200 mm dia.-250mm dia |
| 167 | 140 mm dia-180mm dia |
| 168 | 90 mm dia-125 mm dia |
| 169 | Rising Main |
| 170 | Supply of the following D.I. pipes (k-9) including specials conforming to I.S -8329/2000 or its latest amendment(s). Including F.O.R. destinations rate per metre in Rs., anywhere in U.P. including cost of one Rubber Gasket per pipe length & inclusive of all Taxes & Duties, Third Party Inspection Charges, Packing & Forwarding Charges, Transit Insurance Charges, Road Transportation Charges etc. |
| 171 | Zone-I |
| 172 | TW1 to OHT 150 mm dia K‐9 |
| 173 | Zone-II |
| 174 | TW1,TW2 And TW3 to OHT 200 mm dia K‐9 |
| 175 | Zone-III |
| 176 | TW1,TW2,TW3 And TW4 to CWR 150 mm dia K‐9 |
| 177 | TW5 to CWR 200 mm dia K‐9 |
| 178 | CWR to OHT 250 mm dia K‐9 |
| 179 | Dismantling of roads for laying of pipe line including sorting out and stacking of serviceable materials, stacking and disposal of unserviceable materials including dismantling and cleaning of septic tanks if any |
| 180 | All Zone |
| 181 | Bituminous road |
| 182 | Cement Concrete Road |
| 183 | Reinstatement of following type of roads dismantled during laying of pipe line including leakage repair if any and supply of all materials, labour and T & P etc. required for proper completion of the work. |
| 184 | All Zone |
| 185 | Bituminous road |
| 186 | Cement Concrete Road |
| 187 | Excavation for pipeline trenches in ordinary soil (loam,clay or sand) including lift upto 1.5m and lead upto 50m and refilling, watering, ramming of excavted earth in to the trenches and disposal of surplus earth upto 50m from the center of the trenches. D.I.( K-9) pipes. Guidelines on Environmental construction and demolition (C&D) wastes and GRAP circulated by Central Pollution Control board 2017 and its latest ammendments shall be adhered to for excavation of trench during laying of pipeline. Surplus material after backfilling shall be immediately removed from site and temporary restoration shall be done to make road motorable |
| 188 | Carting from the following sizes of D.I.Pipes (class K-7) and specials to the site of work, lowering them in to trenches and laying true to alignment and gradient, cutting of pipes, making joints including cost of jointing material, rubber rings, labour, T&P etc including hydraulic testing of pipeline. It includes making alignment on city roads, making of trial pits to investigate location of various undergroung services like telephone cables, electric cables, existing water and sewer lines complete required for proper completion of work. only SBR rubber gaskets to be used as per IS 5382 and IS 12820 including making bypass arrangement. |
| 189 | Zone-I |
| 190 | 150 mm dia K‐9 |
| 191 | Zone-II |
| 192 | 200 mm dia K‐9 |
| 193 | Zone-III |
| 194 | 250 mm dia K‐9 |
| 195 | 200 mm dia K‐9 |
| 196 | 150 mm dia K‐9 |
| 197 | Supply & fixing of following sizes of C.I. Double flanged sluice valves as per I.S. 780/1969 class - 1 F.O.R. destination including all taxes and insurance. |
| 198 | 150mm dia |
| 199 | 200mm dia |
| 200 | 250mm dia |
| 201 | Supply of all materials,labour,T & P etc. and construct following valve chambers as direction of Engineer Incharge |
| 202 | 1) Sluice Valve chambers |
| 203 | Supply of all materials,labour, and T & P etc. and construct R.C.C. M-20 thrust blocks. For 200mm Dia pipe Includingsupply of mild steel reinforcement, its bending , fixing and bending with 0.50mm thick binding wire, necessary centering and shuttering including curing etc all complete |
| 204 | Supply of all labour, materials and T & P etc. and construct boundary wallas per approved drawing for OHT and Pumping stations including earth filling as deemed necessary for proper completion of work [Zone-I (135.20m),Zone-II(225.60) and Zone-III(235.2) =Total 596.00RM ] |
| 205 | Supply of all labour ,materials and T & P etc .and provide 3.60 m wide M.S. gate and 1 m wide wicket gate with pillars as per department type design drawing. |
| 206 | Construction of MCS Room (11.0 x 5.0 x 4.0m)including all labour,machinery etc and electrical fittings as per directions of Engineer-in-charge |
| 207 | Construction of 3.5m wide Cement interlocking tiles of approved thickness approach road to OHT and pumping station including preparation of subgrade with lean concrete 1:6:12, 8 cm thick and sand 5 cm thick supply of materials, labour etc all complete |
| 208 | Construction of Staff Quarter as per departmental type design including all elctrical and plumbing fittings and all works upto the satisfaction of Engineer-in-charge.(Zone-II) |
| 209 | Construction of Groundwater recharging unit by rain water harvesting in water works compound |
| 210 | ZONE - 01 |
| 211 | TRANSPORTATION |
| 212 | Transportation, Erection & Dismantling of Rig Machine |
| 213 | Transportation of Tubewell Assembly |
| 214 | Transportation, Erection & Dismantling of 350 PSI Compressure |
| 215 | Transportation, Erection & Dismantling of 3 Cusec O.P Unit |
| 216 | CONSTRUCTION OF TUBEWELL (DRILLING) |
| 217 | Drilling of 625 mm. dia bore from G.L. to 70 m BGL. |
| 218 | Drilling of 500 mm.dia bore from 70 M bglto 100 m BGL. |
| 219 | Drilling of 500 mm.dia bore from 100 M bglto 200 m BGL. |
| 220 | Bentonite Clay |
| 221 | Flushing of Bore |
| 222 | Electrical Logging of the Bore |
| 223 | LOWERING OF TUBE WELL ASSEMBLY AND SHROUDING OF TW BY GRAVEL |
| 224 | Lowering of300X200 mm.dia tube well assembly duly welded including welding electrode and shrouding of pea gravel complete in all respect. |
| 225 | 300mm dia MS ERW pipe from G.L. to 65 mBGL |
| 226 | 200 mm.dia M.S ERWplain/ slotted pipe from 65 m BGL to 100 m BGL |
| 227 | 200 mm.dia M.S ERWplain/ slotted pipe from 100 m BGL to 180 m BGL |
| 228 | 300 mm.dia size |
| 229 | 200 mm.dia size |
| 230 | PEA- GRAVEL |
| 231 | Supply of 1.6 mm to 4.8 mm size pea gravel duly screened and washed as per IS 4097 |
| 232 | DEVELOPMNET OF TUBE WELL |
| 233 | Development of Tube well by 350 PSI Compressor |
| 234 | Development of Tube well by 3 Cusec O.P. Unit |
| 235 | TEST : |
| 236 | Chemical and Bacteriological test of water sample from departmental approved lab |
| 237 | Watch & ward during construction of TW |
| 238 | PUMPING PLANT & INSTRUMENTATION FOR NEW TW |
| 239 | SITC of 1200 LPM, 62 M head (Both Tantetive) Submersiblepump motor set with 24m 150mm dia coloum pipe, NRV, CI D/F Bend 90º, CI A/F Tee, D/F Pipe (1.5 m long 02 nos & 1.0 m long 01 no) Earthing, Painting, Tools sets, wiring of pump house internal & external, Chain pulley block & all Pumping Plant accessories with nut bolts and rubber packing etc. |
| 240 | Submersible Pump Motor Set 1200 LPM, 62 M head (Both Tantetive) as Spare |
| 241 | SITC of Scada compatible Servo Voltage Stabilizer of suitable capacity with all required necessary accessories like SPP, TDR, HL cut off, RS 485 port for scada compatibility, overload protection, bypass arrangement and body earthing etc complete in all respect. |
| 242 | 3M long heavy duty coloum pipe (spare) |
| 243 | Automatic chlorination System |
| 244 | CE/UL CertifiedIntelligent Smart Energy Meter |
| 245 | Motor Operated Actuator with 150 mm dia DI sluice valve |
| 246 | CE/UL Certified Electromagnetic Flow meter of size 150 mm |
| 247 | Digital soft starter / VFD (As per instruction by engineer incharge) with RS485 Port- 400V Class, 45 KWor higher suitable Rating. |
| 248 | CE/UL Certified Pressure transmitter for Pump House |
| 249 | CE/UL certified hydrostatic type sub soil water level transmitter for tubewells |
| 250 | PUMPING PLANT & INSTRUMENTATION FOR EXISTING TW |
| 251 | SITC of 800 LPM, 63 M head (Both Tantetive) Submersiblepump motor set with 24m 150mm dia coloum pipe, NRV, CI D/F Bend 90º, CI A/F Tee, D/F Pipe (1.5 m long 02 nos & 1.0 m long 01 no) Earthing, Painting, Tools sets, wiring of pump house internal & external, Chain pulley block & all Pumping Plant accessories with nut bolts and rubber packing etc. |
| 252 | Submersible Pump Motor Set 800 LPM, 63 M head (Both Tantetive) as Spare |
| 253 | SITC of Scada compatible Servo Voltage Stabilizer of suitable capacity with all required necessary accessories like SPP, TDR, HL cut off, RS 485 port for scada compatibility, overload protection, bypass arrangement and body earthing etc complete in all respect. |
| 254 | 3M long heavy duty coloum pipe (spare) |
| 255 | Automatic chlorination System |
| 256 | CE/UL CertifiedIntelligent Smart Energy Meter |
| 257 | Motor Operated Actuator with 150 mm dia DI sluice valve |
| 258 | CE/UL Certified Electromagnetic Flow meter of size 150 mm |
| 259 | Digital soft starter / VFD (As per instruction by engineer incharge) with RS485 Port- 400V Class, 45 KWor higher suitable Rating. |
| 260 | CE/UL Certified Pressure transmitter for Pump House |
| 261 | CE/UL certified hydrostatic type sub soil water level transmitter for tubewells |
| 262 | AUTOMATION WORK OF TUBEWELLS (NEW & EXISTING) |
| 263 | CE&UL Certified PLC/RTU in IP54 enclosure suitable to communicate with GSM based modem unit with CPU and Power supply with analog and digital parameter and features as specified, for each Tubewell /OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations as specified in tender technical specification |
| 264 | GSM/GPRS based wireless communication with 4G modem for RTU/PLC capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer antenna made for pumping plant internet charges as specified in tender technical specification |
| 265 | Auto Phase Reversal Unit Suitble for above pumping plant with Inbuilt time delay and Enclosure (confirmation to IEC:60947-1 & IEC: 60947-b-1) 250 Amp |
| 266 | CE/UL certified surge protector for control panel |
| 267 | CE/UL Certified 7\" HMI Touch screen suitable to communication with PLC/RTU for local display and control of process parameter |
| 268 | Complete cabling for Tubewell including all power & control cables of all equipments at pump house and OHT |
| 269 | Control panel with IP-54 protection industrial grade for all equipments seprate for control 24V and power equipments |
| 270 | Installation, Testing and Commissioning for one Tubewell |
| 271 | AUTOMATION WORK AT ESR & DMA-01 |
| 272 | Electrical panel with Remote Terminal Unit |
| 273 | Isolation DI Sluice Valve with Actuator (Outlet of ESR) 200 mm |
| 274 | Electro Magnetic Flow meter (Outlet of ESR) Size 200 mm |
| 275 | Flow Control Valve suitable for drinking water Size 200 mm |
| 276 | Manual Pressure Transmitter with display |
| 277 | Automatic Chlorination System |
| 278 | Battery operated / electricity or both (as per engineer incharge) Chlorine Analyzer |
| 279 | CE/UL Certified Radar type level transmitter for OHT |
| 280 | Solar based digital Pressure Transmitter with battery & IP 67 protection with data logger 02 nos for each DMA |
| 281 | CE/UL certified Sutable capacity UPS with batteries at ESR for operation of actuators & other equipments if required |
| 282 | AUTOMATION WORK AT DMA-02 |
| 283 | Isolation DI Sluice Valve with Actuator (Outlet of ESR) 250 mm |
| 284 | Electro Magnetic Flow meter (Outlet of ESR) Size 250 mm |
| 285 | Flow Control Valve suitable for drinking water Size 250 mm |
| 286 | Manual Pressure Transmitter with display |
| 287 | Automatic Chlorination System |
| 288 | Battery operated / electricity or both (as per engineer incharge) Chlorine Analyzer |
| 289 | Solar based digital Pressure Transmitter with battery & IP 67 protection with data logger 02 nos for each DMA |
| 290 | Trial run of Pumping Plant and all other E&M / Automation equipments installed at new & existing tubewells and ESR of Zone-01 with Electricity, Chlorine & Operation charges till hand over of scheme to concerning ULB |
| 291 | ZONE - 02 |
| 292 | TRANSPORTATION |
| 293 | Transportation, Erection & Dismantling of Rig Machine |
| 294 | Transportation of Tubewell Assembly |
| 295 | Transportation, Erection & Dismantling of 350 PSI Compressor |
| 296 | Transportation, Erection & Dismantling of 3 Cusec O.P Unit |
| 297 | CONSTRUCTION OF TUBEWELL (DRILLING) |
| 298 | Drilling of 625 mm. dia bore from G.L. to 70 m BGL. |
| 299 | Drilling of 500 mm.dia bore from 70 M bglto 100 m BGL. |
| 300 | Drilling of 500 mm.dia bore from 100 M bglto 200 m BGL. |
| 301 | Bentonite Clay |
| 302 | Flushing of Bore |
| 303 | Electrical Logging of the Bore |
| 304 | LOWERING OF TUBE WELL ASSEMBLY AND SHROUDING OF TW BY GRAVEL |
| 305 | Lowering of300X200 mm.dia tube well assembly duly welded including welding electrode and shrouding of pea gravel complete in all respect. |
| 306 | 300mm dia MS ERW pipe from G.L. to 65 mBGL |
| 307 | 200 mm.dia M.S ERWplain/ slotted pipe from 65 m BGL to 100 m BGL |
| 308 | 200 mm.dia M.S ERWplain/ slotted pipe from 100 m BGL to 180 m BGL |
| 309 | 300 mm.dia size |
| 310 | 200 mm.dia size |
| 311 | PEA- GRAVEL |
| 312 | Supply of 1.6 mm to 4.8 mm size pea gravel duly screened and washed as per IS 4097 |
| 313 | DEVELOPMNET OF TUBE WELL |
| 314 | Development of Tube well by 350 PSI Compressor |
| 315 | Development of Tube well by 3 Cusec O.P. Unit |
| 316 | TEST : |
| 317 | Chemical and Bacteriological test of water sample from departmental approved lab |
| 318 | Watch & ward during construction of TW |
| 319 | PUMPING PLANT & INSTRUMENTATION |
| 320 | SITC of 1200 LPM, 67 M head (Both Tentative) Submersiblepump motor set with 24m 150mm dia coloum pipe, NRV, CI D/F Bend 90º, CI A/F Tee, D/F Pipe (1.5 m long 02 nos & 1.0 m long 01 no) Earthing, Painting, Tools sets, wiring of pump house internal & external, Chain pulley block & all Pumping Plant accessories with nut bolts and rubber packing etc. |
| 321 | Submersible Pump Motor Set 1200 LPM, 67 M head (Both Tentative) as Spare |
| 322 | SITC of Scada compatible Servo Voltage Stabilizer of suitable capacity with all required necessary accessories like SPP, TDR, HL cut off, RS 485 port for scada compatibility, overload protection, bypass arrangement and body earthing etc complete in all respect. |
| 323 | 3M long heavy duty coloum pipe (spare) |
| 324 | Automatic chlorination System |
| 325 | CE/UL CertifiedIntelligent Smart Energy Meter |
| 326 | Motor Operated Actuator with 150 mm dia DI sluice valve |
| 327 | CE/UL Certified Electromagnetic Flow meter of size 150 mm |
| 328 | Digital soft starter / VFD (As per instruction by engineer incharge) with RS485 Port- 400V Class, 45 KWor higher suitable Rating. |
| 329 | CE/UL Certified Pressure transmitter for Pump House |
| 330 | CE/UL certified hydrostatic type sub soil water level transmitter for tubewells |
| 331 | AUTOMATION WORK OF TUBEWELLS |
| 332 | CE&UL Certified PLC/RTU in IP54 enclosure suitable to communicate with GSM based modem unit with CPU and Power supply with analog and digital parameter and features as specified, for each Tubewell /OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations as specified in tender technical specification |
| 333 | GSM/GPRS based wireless communication with 4G modem for RTU/PLC capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer antenna made for pumping plant internet charges as specified in tender technical specification |
| 334 | Auto Phase Reversal Unit Suitable for above pumping plant with Inbuilt time delay and Enclosure (confirmation to IEC:60947-1 & IEC: 60947-b-1) 250 Amp |
| 335 | CE/UL Certified 7\" HMI Touch screen suitable to communication with PLC/RTU for local display and control of process parameter |
| 336 | Complete cabling for Tubewell including all power & control cables of all equipments at pump house and OHT |
| 337 | Control panel with IP-54 protection industrial grade for all equipments separate for control 24V and power equipments |
| 338 | CE/UL certified surge protector for control panel |
| 339 | Installation, Testing and Commissioning for one Tubewell |
| 340 | AUTOMATION WORK AT ESR & DMA-01 |
| 341 | Electrical panel with Remote Terminal Unit |
| 342 | Isolation DI Sluice Valve with Actuator (Outlet of ESR) 250 mm |
| 343 | Electro Magnetic Flow meter (Outlet of ESR) Size 250 mm |
| 344 | Flow Control Valve suitable for drinking water Size 250 mm |
| 345 | Manual Pressure Transmitter with display |
| 346 | Automatic Chlorination System |
| 347 | Battery operated / electricity or both (as per engineer incharge) Chlorine Analyzer |
| 348 | CE/UL Certified Radar type level transmitter for OHT |
| 349 | Solar based digital Pressure Transmitter with battery & IP 67 protection with data logger 02 nos for each DMA |
| 350 | CE/UL certified Sutable capacity UPS with batteries at ESR for operation of actuators & other equipments if required |
| 351 | AUTOMATION WORK AT DMA-02 |
| 352 | Isolation DI Sluice Valve with Actuator (Outlet of ESR) 350 mm |
| 353 | Electro Magnetic Flow meter (Outlet of ESR) Size 350 mm |
| 354 | Flow Control Valve suitable for drinking water Size 350 mm |
| 355 | Manual Pressure Transmitter with display |
| 356 | Automatic Chlorination System |
| 357 | Battery operated / electricity or both (as per engineer incharge) Chlorine Analyzer |
| 358 | Solar based digital Pressure Transmitter with battery & IP 67 protection with data logger 02 nos for each DMA |
| 359 | Trial run of Pumping Plant and all other E&M / Automation equipments installed at tubewells and ESR of Zone-01 with Electricity, Chlorine & Operation charges till hand over of scheme to concerning ULB |
| 360 | ZONE - 03 |
| 361 | TRANSPORTATION |
| 362 | Transportation, Erection & Dismantling of Rig Machine |
| 363 | Transportation of Tubewell Assembly |
| 364 | Transportation, Erection & Dismantling of 350 PSI Compressor |
| 365 | Transportation, Erection & Dismantling of 3 Cusec O.P Unit |
| 366 | CONSTRUCTION OF TUBEWELL (DRILLING) |
| 367 | Drilling of 625 mm. dia bore from G.L. to 70 m BGL. |
| 368 | Drilling of 500 mm.dia bore from 70 M bglto 100 m BGL. |
| 369 | Drilling of 500 mm.dia bore from 100 M bglto 200 m BGL. |
| 370 | Bentonite Clay |
| 371 | Flushing of Bore |
| 372 | Electrical Logging of the Bore |
| 373 | LOWERING OF TUBE WELL ASSEMBLY AND SHROUDING OF TW BY GRAVEL |
| 374 | 300mm dia MS ERW pipe from G.L. to 65 mBGL |
| 375 | 200 mm.dia M.S ERWplain/ slotted pipe from 65 m BGL to 100 m BGL |
| 376 | 200 mm.dia M.S ERWplain/ slotted pipe from 100 m BGL to 180 m BGL |
| 377 | TUBE WELL ASSEMBLY : |
| 378 | 300 mm.dia size |
| 379 | 200 mm.dia size |
| 380 | PEA- GRAVEL |
| 381 | Supply of 1.6 mm to 4.8 mm size pea gravel duly screened and washed as per IS 4097 |
| 382 | DEVELOPMNET OF TUBE WELL |
| 383 | Development of Tube well by 350 PSI Compressor |
| 384 | Development of Tube well by 3 Cusec O.P. Unit |
| 385 | TEST : |
| 386 | Chemical and Bacteriological test of water sample from departmental approved lab |
| 387 | Watch & ward during construction of TW |
| 388 | PUMPING PLANT & INSTRUMENTATION FOR NEW TW |
| 389 | SITC of 1200 LPM, 36 M head (Both Tentative) pump motor set with 24m 150mm dia coloum pipe, NRV, CI D/F Bend 90º, CI A/F Tee, D/F Pipe (1.5 m long 02 nos & 1.0 m long 01 no) Earthing, Painting, Tools sets, wiring of pump house internal & external, Chain pulley block & all Pumping Plant accessories with nut bolts and rubber packing etc. |
| 390 | Submersible Pump Motor Set 1200 LPM, 36 M head (Both Tentative) as Spare |
| 391 | SITC of Scada compatible Servo Voltage Stabilizer of suitable capacity with all required necessary accessories like SPP, TDR, HL cut off, RS 485 port for scada compatibility, overload protection, bypass arrangement and body earthing etc complete in all respect. |
| 392 | 3M long heavy duty coloum pipe (spare) |
| 393 | Automatic chlorination System |
| 394 | CE/UL CertifiedIntelligent Smart Energy Meter |
| 395 | Motor Operated Actuator with 150 mm dia DI sluice valve |
| 396 | CE/UL Certified Electromagnetic Flow meter of size 150 mm |
| 397 | Digital soft starter / VFD (As per instruction by engineer incharge) with RS485 Port- 400V Class, 45 KWor higher suitable Rating. |
| 398 | CE/UL Certified Pressure transmitter for Pump House |
| 399 | CE/UL certified hydrostatic type sub soil water level transmitter for tubewells |
| 400 | PUMPING PLANT & INSTRUMENTATION FOR EXISTING TW |
| 401 | SITC of 800 LPM, 35 M head (Both Tantetive) Submersiblepump motor set with 24m 150mm dia coloum pipe, NRV, CI D/F Bend 90º, CI A/F Tee, D/F Pipe (1.5 m long 02 nos & 1.0 m long 01 no) Earthing, Painting, Tools sets, wiring of pump house internal & external, Chain pulley block & all Pumping Plant accessories with nut bolts and rubber packing etc. |
| 402 | Submersible Pump Motor Set 800 LPM, 50 M head (Both Tantetive) as Spare |
| 403 | SITC of Scada compatible Servo Voltage Stabilizer of suitable capacity with all required necessary accessories like SPP, TDR, HL cut off, RS 485 port for scada compatibility, overload protection, bypass arrangement and body earthing etc complete in all respect. |
| 404 | 3M long heavy duty coloum pipe (spare) |
| 405 | Automatic chlorination System |
| 406 | CE/UL CertifiedIntelligent Smart Energy Meter |
| 407 | Motor Operated Actuator with 150 mm dia DI sluice valve |
| 408 | CE/UL Certified Electromagnetic Flow meter of size 150 mm |
| 409 | Digital soft starter / VFD (As per instruction by engineer incharge) with RS485 Port- 400V Class, 45 KWor higher suitable Rating. |
| 410 | CE/UL Certified Pressure transmitter for Pump House |
| 411 | CE/UL certified hydrostatic type sub soil water level transmitter for tubewells |
| 412 | PUMPING PLANT & INSTRUMENTATION FOR EXISTING TW |
| 413 | SITC of 800 LPM, 50 M head (Both Tantetive) Submersiblepump motor set with 24m 150mm dia coloum pipe, NRV, CI D/F Bend 90º, CI A/F Tee, D/F Pipe (1.5 m long 02 nos & 1.0 m long 01 no) Earthing, Painting, Tools sets, wiring of pump house internal & external, Chain pulley block & all Pumping Plant accessories with nut bolts and rubber packing etc. |
| 414 | Submersible Pump Motor Set 800 LPM, 50 M head (Both Tantetive) as Spare |
| 415 | SITC of Scada compatible Servo Voltage Stabilizer of suitable capacity with all required necessary accessories like SPP, TDR, HL cut off, RS 485 port for scada compatibility, overload protection, bypass arrangement and body earthing etc complete in all respect. |
| 416 | 3M long heavy duty coloum pipe (spare) |
| 417 | Automatic chlorination System |
| 418 | CE/UL CertifiedIntelligent Smart Energy Meter |
| 419 | Motor Operated Actuator with 150 mm dia DI sluice valve |
| 420 | CE/UL Certified Electromagnetic Flow meter of size 150 mm |
| 421 | Digital soft starter / VFD (As per instruction by engineer incharge) with RS485 Port- 400V Class, 45 KWor higher suitable Rating. |
| 422 | CE/UL Certified Pressure transmitter for Pump House |
| 423 | CE/UL certified hydrostatic type sub soil water level transmitter for tubewells |
| 424 | AUTOMATION WORK OF TUBEWELLS |
| 425 | CE&UL Certified PLC/RTU in IP54 enclosure suitable to communicate with GSM based modem unit with CPU and Power supply with analog and digital parameter and features as specified, for each Tubewell /OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations as specified in tender technical specification |
| 426 | GSM/GPRS based wireless communication with 4G modem for RTU/PLC capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer antenna made for pumping plant internet charges as specified in tender technical specification |
| 427 | Auto Phase Reversal Unit Suitable for above pumping plant with Inbuilt time delay and Enclosure (confirmation to IEC:60947-1 & IEC: 60947-b-1) 250 Amp |
| 428 | CE/UL Certified 7\" HMI Touch screen suitable to communication with PLC/RTU for local display and control of process parameter |
| 429 | Complete cabling for Tubewell including all power & control cables of all equipments at pump house and OHT |
| 430 | Control panel with IP-54 protection industrial grade for all equipments separate for control 24V and power equipments |
| 431 | CE/UL certified surge protector for control panel |
| 432 | Installation, Testing and Commissioning for one Tubewell |
| 433 | Trial run of Pumping Plant and all other E&M / Automation equipments installed at new & existing tubewells and ESR of Zone-01 with Electricity, Chlorine & Operation charges till hand over of scheme to concerning ULB |
| 434 | PUMPING PLANT & INSTRUMENTATION AT CWR |
| 435 | Supply of 3000 LPM, 36 mtr Head, (Both Tantetive) SS impeller & shaft Water Lubricated VT Pump set coupled with squirrel cage VHS TEFC 40 HP induction motor (Operating Voltage 415 V + 10%, 3 ph, 50 cycle) with Bowl assembly discharge head, head shaft, strainer and 4.5 mts Column Assembly to feed. (2w+1s) |
| 436 | SITC OF control panel having 1 Nos. incoming having 400 amp ACB draw out type & outgoing Panels ( 3 No.) 400 amp MCCB, 01 Nos 63 Amp MCCB for aux light & suitable to operatedon 400 ± 6 %volt , 3 Phase , 50 Hz, AC supply Panel C.Ts, P.T AVF Meter,KWH meter P.F Meter, Bus Bar chamber, Relays and other Protective Devices Complete in all Respects. |
| 437 | Digital Soft Starter / VFD Panel 45 KW Suitable to operate 300 to 500 V input Voltage. |
| 438 | Auto Phase reversal unit / Automatic switch with inbuilt the delay & enclosure (Confirms to IEC: 60947-1 & IEC: 60947-6-1)160 Amp Rating |
| 439 | MAIN PIPING AND VALVES FOR CWR :- |
| 440 | 200 mm dia sluice valve with actuator for pump |
| 441 | 200 mm dia DI reflux valve |
| 442 | 300 X 200 X 300 mm size C.I.,A/F Tee |
| 443 | 300 mm M.S. D/F pipe 1 mt. long |
| 444 | 300 mm M.S. D/F pipe 2 mt. long |
| 445 | 300 mm M.S. D/F pipe 1.5 mt long |
| 446 | 300 mm dia C.I.D/F. Bend- 90 degree |
| 447 | 300 mm size M.S. blind flange |
| 448 | 300 mm size Sluice Valve with Actuator (Common Header) |
| 449 | Reflux Valve 300 mm Size for Common Header |
| 450 | 300 x 300 x 300 mm CI Tee |
| 451 | 300 mm dia Sluice Valve with Actuator (for Bye pass) |
| 452 | 300 mm M.S. D/F pipe 1 mt. long (for Bye pass) |
| 453 | Nut bolt and rubber packing for jointing as per requirement |
| 454 | Other material such as dismantling joints, reducer in largeras required at the time of installation |
| 455 | CE/UL Certified 300mm Size Electromagnetic Flowmeters |
| 456 | Power Wiring : |
| 457 | Supply of 16 Sqmm. 3 core copper conductor cable from Starter to Motor. |
| 458 | Installation, Testing, Commissioning of VT Pumps with Power Wiring Earthing, Cable Trey including required material for Proper installation. |
| 459 | SITC of 3 Ton, 12 mtr. Lift chain pulley Block with four way motion HOT, Gantry I-section Girder, square rod with travelling trolley. |
| 460 | Electromegnatic chlorinatimg plant of suitable capacity SCADA compatible |
| 461 | CE/UL Certified Radar type Level Transmiter for SUMP |
| 462 | CE/UL Certified Pressure transmitter for each pump. |
| 463 | CE/UL Certified Surge protector for control panel. |
| 464 | Rubber mat for Electrical purpose as per IS 5424. |
| 465 | Fire extinguisher ISI mark confirming to IS 15683- 4.5 Kg. |
| 466 | Internal & External electrification of Pumping plant. |
| 467 | Tools & Sppanners set Complete. |
| 468 | Water works Campus with Solar Panel LED light |
| 469 | SUB STATION AT CWR 160 KVA CAPACITY :- |
| 470 | Supply, installation, testing & commissioning of indoor type floor mounted metal clad, 11 KV VCB panel with 1No. 630 Amp. incoming VCB & 2 Nos 630 Amp. outgoing VCB totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS with all necessory protection and also should be compatible to SCADA operation |
| 471 | Supply, installation, testing & commissioning of 100 KVA, 11/0.44 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type oil cooled, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +7.5% & -15%, LV side @ 2.5% stapping complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180-2014 (Part 1 to Part 5) & as per specificationcomplete in all respects as required at site. |
| 472 | Supply, installation, testing and commissioning of LT Panel comprising of following details. 02 No. 400 Amp. Incoming ACB Panel shall be mechanically and electrically interlocked completely and 01 Nos 400 Amp ACB as Outgoing and 01 Nos 63 Amp Outgoing for Auxiliary Load with motorized and microprocessor based suitable for SCADA and all necessary protection equipments and metering equipment as per requirement. |
| 473 | Supply of 70 Sq mm size XLPE cable from 11 KV UPPCL metering panel to HT incoming panel, and HT panel to both transformers. |
| 474 | Supply of 70 sq mm 3.5 core PVCinsulated armored aluminum cable from transformer to LT panel. |
| 475 | Supply of HT Cable end termination joint kit. |
| 476 | Complete in all respect earthing system shall executed as per IS : 3043 and I.E. rules. |
| 477 | Installation and commissioning of 11 KV / 0.44 KV substation, 160 KVA transformers including HT panel and LT panel with cable tray including all labor T&P complete in all respect. |
| 478 | Electrification of Sub-Station (HT Room, LT Room, Metering Room & Transformer Area) |
| 479 | Rubber mat for Electrical purpose as per IS 5424. |
| 480 | Electrification of water works with Solar Panel LED light |
| 481 | NOC for substation from electrical safety department |
| 482 | Heavy duty leak proof fire bucket as per IS 2546/1974 |
| 483 | Fire bucket stand for 6 bucket |
| 484 | Fire extinguisher ISI mark confirming to IS 15683- 4.5 Kg. |
| 485 | Test and trial run for three months for sub station |
| 486 | AUTOMATION WORK OF CWR :- |
| 487 | CE&UL Certified PLC/RTU in IP54 enclosure suitable to communicate with GSM based modem unit with CPU and Power supply with analog and digital parameter and features as specified, for each tubewell /OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations as specified in tender technical specification |
| 488 | GSM/GPRS based wireless communication with 4G modem for RTU/PLC caopabke to transfer and gather data from remote sites to control stations all accessories included with signal enhancer antenna made for pumping plant internet charges as specified in the tender technical specification |
| 489 | CE/UL CertifiedIntelligent Smart Energy Meter |
| 490 | CE/UL Certified 7\" HMI Touch screen suitable to communication with PLC/RTU for local display and control of process parameter |
| 491 | Complete cabling for ZPS including all power and control cables of all equipments |
| 492 | Control panel with IP-54 protection industrial grade for all equipments seprate for control 24V and power equipments |
| 493 | Security serveillance IP camera with recorder |
| 494 | Installation, Testing and Commng of above Equipments |
| 495 | AUTOMATION WORK AT ESR & DMA-01 |
| 496 | Electrical panel with Remote Terminal Unit |
| 497 | Isolation DI Sluice Valve with Actuator (Outlet of ESR) 300 mm |
| 498 | Electro Magnetic Flow meter (Outlet of ESR) Size 300 mm |
| 499 | Flow Control Valve suitable for drinking water Size 300 mm |
| 500 | Manual Pressure Transmitter with display |
| 501 | Automatic Chlorination System |
| 502 | Battery operated / electricity or both (as per engineer incharge) Chlorine Analyzer |
| 503 | CE/UL Certified Radar type level transmitter for OHT |
| 504 | Solar based digital Pressure Transmitter with battery & IP 67 protection with data logger 02 nos for each DMA |
| 505 | CE/UL certified Sutable capacity UPS with batteries at ESR for operation of actuators & other equipments if required |
| 506 | AUTOMATION WORK AT DMA-02 |
| 507 | Isolation DI Sluice Valve with Actuator (Outlet of ESR) 450 mm |
| 508 | Electro Magnetic Flow meter (Outlet of ESR) Size 450 mm |
| 509 | Flow Control Valve suitable for drinking water Size 450 mm |
| 510 | Manual Pressure Transmitter with display |
| 511 | Automatic Chlorination System |
| 512 | Battery operated / electricity or both (as per engineer incharge) Chlorine Analyzer |
| 513 | Solar based digital Pressure Transmitter with battery & IP 67 protection with data logger 02 nos for each DMA |
| 514 | Trial run of Pumping Plant and all other E&M / Automation equipments installed at CWR and ESR of Zone-03 with Electricity, Chlorine & Operation charges till hand over of scheme to concerning ULB |
| 515 | SCADADISPLAY (MCS) |
| 516 | CE/UL & BIS certified industrial grade LED Monitor with latest configuration as per specification, 65\" (up to 50 Tubewells) |
| 517 | Desktop PC with i5/i7 processor with UPS as per specification mentioned in technical bid document |
| 518 | CE/UL certified 5 KVA UPS with batteries as per specification mentioned in technical bid document |
| 519 | Full development version of required TAGS SCADA software with customization of software for MCS as per requirement as per specification mentioned in technical bid document |
| 520 | CE/UL certified master control room PLC with redundant CPU & power supply at MCS in IP 54 encloser as per specification mentioned in technical bid document |
| 521 | CE/UL certified Field gateway agent for transferring data from MCS to Central control room |
| 522 | Laptop with i5/i7 12th generation processor including wireless keyboard, mouse as per specification mentioned in technical bid document for scada execution & monitoring at Jal Nigam Office. |
| 523 | GSM based wireless/ Broadband/ Equipment communication system for PLC capable to transfer & received data & gather data from remote sites to control station. All accessories included signal enhancer antenna along with running expenses till DLP |
| 524 | CE/UL Certified Firewall for network protection |
| 525 | Surge protector for Ethernet communication protection |
| 526 | CE/UL Certified industrial grade Ethernet Switch |
| 527 | Mobile App Facility system architecture (industries internet based & viewed through apps for increased local & Remote Visibility |
| 528 | Canon/HP or equivalent Laser Printer 1108 plus 02 Nos (01 Nos for mcs room & other one nos for jal nigam office) or equivalent |
| 529 | Security Surveillance IP Camera with recorder |
| 530 | Installation, commissioning and testing including required furniture, A/C, etc. |
| 531 | Trial run of all other E&M / Automation equipments installed at MCS Room of Scheme with Electricity, Data transmission & Operation charges till hand over of scheme to concerning ULB |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail