| Sl. No. | Item Description |
| 1 | Upkeep of Central AC plant chilled water type 150 TR capacity (2x50 TR running + 1x 50TR standby) installed at P-5 bldg at CAD depot in for detecting defects and minor repairs such as oiling, greasing in summer/ monsoon/ winter seasons including check & cleaning, weekly, monthly, quarterly maintenance all as specified in particular specifications including first hand repairs, maintenance and cleaning of electric motors of compressor, condensor, chilledunit, blower pump, AHU, cooling tower condensor pump, chilled unit pump, water supply pipe line, refregeration pipe line, expansion valves solenoid valves, liquid line filter, HP/LP cutouts, oil failure instruments, temperature gauge, chilled water pipe line, heating/cooling humidity state, electric panel wiring interlocking system heaters, measuring instruments, water/refrigerent control valve etc complete required for keeping plant in functional state all as specified and directed by EIC for smooth and efficient performance of AC plant to achieve desired inside conditions through out the period comprising of the following:-* Compressor make/type Voltas 5H 60-03 Nos* Electric motor 50 HP compressor, Make : Alstom- 03 Nos* Shell and tube type condensor 50TR make : Voltas- 03 Nos* Mono block pump set 12.5 HP for condensor- 02 Nos* Mono block pump set 12.5 HP for chilled unit \"Becon\"- 02 Nos* Chilled unit shell and tube type direct expansion type Voltas - 03 Nos* Cooling tower fan force draught made of FRP of make \"Mihir\"- 01 No* Make up water tank 100 TR capacity 5000 ltrs capacity- 03 Nos* Electric panel board comprising of starters, MCBs measuring instrumets etc make : \"Power Media\"- 01 No* AHU with electric dirvn motor \"Voltas\"- 01 No* Dehumidification system- 01 Unit* Humidification system - 01 UnitContd.../- |
| 2 | * Control system complete - 01 set* Winter heating system complete - 01 set* Water circulation system with GI pipe and valve - 01 set* Electric wiring from panel to A/C plants & motors including inter locking - 01 NoNotes:- (i) The upkeep cost of each plantshall deemed to be included, T&P used and other petty items such as cotton waste, kerosene oil, nuts, bolts and labour. (ii)The replacement of Major defective items shall be measured and paid seperately as supply only.(iii) Any other work required to make central AC plant in perfect working condition through out not specifically mentioned is also deemed to be included under this item.(iv) The rate quoted shall cover the entire contract periodof 11 Months including Sundays and Holidays. |
| 3 | Upkeep of central AC plant chilled water type 126 TR capacity (42 TRx3 Units) installed at P-5 bldg at CAD Depot for detecting defects and minor repairs such as oiling, greasing in summer/monsoon/winter seasons includingcheck & cleaning, weekly, monthly, quarterly all as specified in particular specifications including first hand repairsmaintenance and cleaning of electric motors of compressor, condensor,chilled unit, blower pump, AHU, cooling tower condensor pump, chilled unit pump, water supply pipe line, referigeration pipe line, expansion valves, solenoid valves, liquid line filter, HP/LP cutouts, oil failure instruments, temperature gauge, chilled water pipe line, heating/cooling humidity state, electric panel wiring inter locking system heaters, measuring instruments, water/refrigerent control valve etc complete required for keeping plant in functional state all as specified and directed by EIC for smooth and efficient performance of AC plant to achieve desired inside conditions through out the period comprising of the following :-*Compressor make/type Voltas 5H 60-03 Nos*Electric motor 50 HP compressor, Make: Alstom - 03 Nos*Shell and tube type condensor 42 TR make : Voltas - 03 Nos*Mono block pump set 12.5 HP for condensor-02 Nos*Mono block pump set 12.5 HP for chilled unit \"Becon\"- 02 Nos*Chilled unit shell and tube type direct expansion type Voltas - 03 Nos*Cooling tower fan force draught made of FRP of make \"Mihir\"- 01 No*Make up water tank 15000 ltrs capacity - 01 No*Electric panel board comprising of starters, MCBs measuring instrumets etc make: \"Power Media\"- 01 No*AHU with electric dirvn motor \"Voltas\" - 04 Nos*Dehumidification system - 04 Units*Humidification system - 04 Units*Control system complete - 03 setsContd.../- |
| 4 | Winter heating system complete - 01 setWater circulation system with GI pipe and valve - 01 setElectric wiring from panel to AC plants & motors including inter locking - 01 NoNote :- (i) The upkeep cost of each plantshall deemed to be included, T&P used and other petty items such as cotton waste, kerosene oil, nuts, bolts and labour. (ii) The replacement of Major defective items shall be measured and paid seperately as supply only.(iii) Any other work required to make central AC plant in perfect working condition through out not specifically mentioned is also deemed to be included under this item.(iv) The rate quoted shall cover the entire contract periodof 11 Months including Sundays and Holidays |
| 5 | Upkeep for Central AC Chiller plant scroll type capacity 3 X 37.5 TR central AC plant of Make : Blue Star Model No:XWC3S-039AR2 (02X 37.5 TR running and 01 X 37.5 TR Standby) installed at P-104 B Sub Depot at CAD Depot for defect and minor repairs such as oiling ,greasing in summer /Mansoon/winter season including check & cleaning, weekly, monthly, quarterly all as specified in perticular specification including first hand repairs maintenance and cleaning of Electic motor of Condensor, chilled unit, blower pump, AHU, Cooling tower condensor pump, chilled unit pump, water supply pipe line, refrigeration pipe line, Expansion Valves, Liquid line filter, HP/LP Cut outs, Oil failure instrument, Temperature gauge, chilled water pipe line, heating/cooling humidity state, Electric Panel wiring, measuring instruments, water/ refrigerent control valve etc complete required for keeping plant in functional state all as specified and directed by EIC for smooth and efficient performance of AC plant to achieve desired inside conditions through out the period comprising of the following:-*Scroll compressor of capacity 12.5 TR - 09 Nos*Expansion Valve Make-Danfoss model No-TGEX11 TR - 09 Nos*Catchall filter make-Danfoss model No-DCL305 - 09 Nos*Condensor Shafty Valve Suitable for 350 PSI working Pressure Make-SANLAN - 09 Nos*Pressure Gauge suitable for working 0 to 21 Kg/CM2 - 28 Nos*Temprature Gauge - 22 Nos*Condensor Unit - 03 Nos*Chiller Unit - 03 Nos*Plant panel Board with PCB controller and Computer based Micro Controller - 03 Nos*AHU Unit with Moter 10 Hp - 01 NosContd.../- |
| 6 | *Monoblock Pump of capacity 7.5 Hp for Condensor - 03 Nos*Monoblock Pump of capacity 10 Hp for Chiller Water - 03 Nos*LT panel for AC Chiller Plant - 01 Nos*Cooling Tower - 01 NosNote:- (i) The upkeep cost of each plant shall deemed to be included, T&P used and other petty items such as cotton waste, kerosene oil, nuts, bolts and labour. (ii)The replacement of Major defective items shall be measured and paid separately as supply only.(iii) Any other work required to make central AC plant in perfect working condition through out not specifically mentioned is also deemed to be included under this item.(iv) The rate quoted shall cover the entire contract periodof 11 Months including Sundays and Holidays |
| 7 | Servicing and maintenance Heat generating system installed at 104 AC shed in B sub Depot detecting defects and minor repair such as oiling, greasing, in summer/ mansoon/ winter seasons including check and cleaning, weekly, monthly, quaterly maintenance all as specified in particular specification incl first hand repair maintenance and cleaning of water tanks, water supply pipe line, Draing of water through pipe, cleaning of Hot Water pump, Maintenance of heating coil, Repair of valves connceted to heat genetating system, complete required for keeping heat generator system in functional state all as specified and directed by EIC for Smooth and Efficient performance of AC plant to achieve desired inside condition throughout the period comprising of the following :- *Heating Coil 21 KW - 02 Nos*Water Tank 45 Ltr - 01 Nos*Hot Water pump set 10 HP - 02 NosNote:- (i) The upkeep cost of each plant shall deemed to be included, T&P used and other petty items such as cotton waste, kerosene oil, nuts, bolts and labour. (ii) The replacement of Major defective items shall be measured and paid separately as S&F.(iii) The Rate quoted shall cover the entire contract period of 11 Month including sunday and holidays. |
| 8 | Supply only refrigerant gas R-22 /R-134A for AC plant by contractors cylinder complete all as specified and directed. |
| 9 | Supply only refrigerant gas R-407C for AC plant by contractor cylinder complete all as specified and directed. |
| 10 | Supply only LP/HP cutout model MP-15 Code No 06-0150 complete all as specified and directed. Make : Indfoss/ Danfoss/ Switzer |
| 11 | Supply only safety/ failure switch model MP-55 Code No 060-B9424 complete all as specified and directed. Make : Indfoss/ Danfoss/ Switzer |
| 12 | Supply only solenoid valve make: Indfoss or equivalent as approved by GE complete all as specified and directed. |
| 13 | Supply only shaft seal assembly for compressor voltas 5H 60 complete all as specified and directed. Make : Voltas or equivalent as approved by GE. |
| 14 | Supply only V belt for blower fan motor as per sample complete all as specified and directed. |
| 15 | Supply only V belt for compressor as per sample complete all as specified and directed. |
| 16 | Supply only ball bearing for blower motor/ cooling tower motor/ pump complete all as specified and directed. Make : SKF/ NBC |
| 17 | Supply only ball/roller bearing for compressor motor 50 HP complete all as specified and directed. Make SKF/ NBC |
| 18 | Supply only compressor oil complete all as specified and directed. Make: Sheetal N-68/ ESSOL/ Indian Oil. |
| 19 | Supply only pressure gauge for suction/ discharge for refrigerant R-22/ R-407C complete all as specified and directed. Make: SCIENTIFIC Range : 30 to 150 and 0-300 lb/sqm inch or equivalent as approved by GE. |
| 20 | Supply only De-scaling compound complete all as specified and directed.Make : Genco type 101/Scale Guard |
| 21 | Supply only blower shaft bearing including pedestal, complete all as specified and directed.Make: SKF/ NBC |
| 22 | Supply only hand shut off valves/ angle valve size : 1/4 inch complete all as specified and directed. |
| 23 | Supply only single phase preventor VSP-2, 415 Volts, complete all as specified and directed. Make : MINILAC or equivalent as approved by GE. |
| 24 | Supply only power contactor of capacity 45 Amp (MN 45), 415 Volts, 3 phase, 50 Hz complete all as specified and directed.Make : L&T/Siemens/Crompton |
| 25 | Supply only power contactor of capacity 25 Amp (MN 25), 415 Volts, 3 phase, 50 Hz complete all as specified and directed. Make : L&T/Siemens/Crompton |
| 26 | Supply only contactor of capacity 16 Amp (MN 16), 415 Volts, 3 phase, 50 Hz, complete all as specified and directed.Make : L&T or equivalent as approved. |
| 27 | Supply only star delta Timer programmable Electronic timer switch having power requirment 24 V AC/DC power consumption 5W, Electronic timer 3-60 sec with 1 NO inst & 1 No delayed complete all as specified and directed. |
| 28 | Supply only over load relay for blower motor/cooling tower motor/pumps 6-10 Amps, complete all as specified and directed. Make : L&T/Siemens/Crompton |
| 29 | Supply only over load relay for blower motor/cooling tower motor/pumps 9-15 Amps, complete all as specified and directed. Make : L&T/Siemens/Crompton |
| 30 | Supply only over load relay for compressor motor 30 to 50 Amps, complete all as specified and directed. Make : L&T/Siemens/Crompton |
| 31 | Supply only suction reed for compressor 5 H 60, complete all as specified and directed. make : Voltas or equivalent as approved by GE. |
| 32 | Supply only discharge reed for compressor 5H 60, complete all as specified and directed. Make : Voltas or equivalent as approved by GE. |
| 33 | Supply only lub oil filter element of compressor, complete all as specified and directed. Make : Voltas or equivalent as approved by GE. |
| 34 | Supply only crank case heater, complete all as specified and directed. Make : Voltas or equivalent as approved by GE. |
| 35 | Supply only indicator lamp assembly suitable for 440 volts supply complete all as specified and directed.Make : L&T/Siemens/C&S/BCH |
| 36 | Supply only canvas connection for AHU complete all as specified and directed. |
| 37 | Supply only PVC nozzles for cooling tower complete all as specified and directed. |
| 38 | Supply only MS sheet for fan section of AHU MHP-7 model complete all as specified and directed. |
| 39 | Supply only primary air filter sliding type viscous upto 10 micron of Existing size and shape complete all as specified and directed. Make: MOOSA/ UCCO.Note: The fixing charges from item No. 5.00to item No. 36.00are inclusive in the quoted rate of item No 1.00, 2.00, 3.00 & 4.00. |
| 40 | Repairs/ maintenance of cooling tower by drying the basin, cleaning, making basin leak proof, replacement of unserviceable PVC fills and applying 2 coats of synthetic enamel paint inside and outside complete all as specified and directed.Note:- (i) PVC fills shall be measured and paid separately. (ii) The rate quoted shall cover the entire contract period of 11 Months including Sundays and Holidays. |
| 41 | Supply only PVC fills of full size 600mm x 600mm x 150mm complete all as specified and directed. |
| 42 | Supply only PVC fills of full size 600mm x 300mm x 150mm complete all as specified and directed. |
| 43 | Taking down existing old rusted hot/cold MS pipe of size 100 mm dia and Supply and laying MS Pipe \"C\" class 100 mm dia complete all as specified and directed. |
| 44 | Supply and fix in repalcement of 12/13 mm thick nitrile rubber insulation on hot and cold pipe of size 100/150mm dia and fitting like valve, flanges and union etc complete all as specified and directed.Make: Accoflex, Armacell, K flex |
| 45 | Rewinding of 50HP electric motor with fine enameled bared copper conductor of same gauge weight and turn alognwith insulating materials such as impregnated paper, cotton tap, varnish etc and keeping the rewinding into the hot air oven till moisture evaporate and achieving proper insulation results and re-assemble the motor complete all as specified and directed. |
| 46 | All as per item No 42.00 above but 12.5/15 HP complete all as specified and directed. |
| 47 | All as per item No 42.00 above but 7.5 /5HP complete all as specified and directed. |
| 48 | All as per item No 42.00 above but 1 / 2 HP complete all as specified and directed. |
| 49 | Material and labour for taking out the defective pump set of capacity upto 5 HPto 12.5 HP ofAC plant fromexisting position by carefully disconnecting all water pipe lines and electrical cablesand carrying out overhauling by dismantling the pump casing, cleaning of the impeller and supply and replacement of Gunmetal bush (01 No), gland plate (01 No.) alongwith studs, nuts, gland packing rope, greasing and re-assembling and re-installing in its original position and testing on completion complete all as specified and directed.Note:- Spare parts other than mentioned above under this itemwill be measured and paid separately as supply only. |
| 50 | Supply only end ball / roller bearing with good quality grease suitable for pump sets 5HPto 12.5 HP complete all as specified and directed. Make: NBC/SKF/Tata |
| 51 | Supply only star coupling key any size as per sample complete all as specified and directed. |
| 52 | Supply only pump shaft suitable for pump sets 5 HPto 12.5 HP capacity complete all as specified and directed. |
| 53 | Supply only pump impeller brass suitable for pump sets 5 HP to 12.5 HP capacity complete all as specified and directed. |
| 54 | Supply only gun metal bush bearing complete set of two as per sample for 5 HP to 12.5 HP pump complete all as specified and directed. |
| 55 | Taking down carefully old unserviceable, burnt out sealed unit compressor of Refrigerator of capacity 165/175/185/200 Ltrs of any make, by means of unscrewing foundation nut bolts, disconnecting from suction & discharge side mechanically & electrically, of any make and keeping a side for further disposal complete all as specified and directed. |
| 56 | All as per item No 52.00 above but Refrigerator of capacity 240/286/300/315 Ltrs of any make complete all as specified and directed. |
| 57 | All as per item No 52.00 above but Water cooler of capacity 40/80 Ltrs of any make complete all as specified and directed. |
| 58 | All as per item No 52.00 above but Deep Freezer ofcapacity of 310/500Ltrs ofany make complete all as specified and directed. |
| 59 | All as per item No 52.00 above but Window type & split type AC of capacity 1.5/2 TR of any make complete all as specified and directed.Note:- (i) Job also include removing AC from any site/height/location and transporting AC unit to repair in workshop and back to site if necessary.(ii) Replacement of spares shall be measured and paid separately as supply only and fixing is deemed to be included under this item. |
| 60 | Supply and fix new sealed unit compressor of approved make and capacity 230 VAC for Refrigerator of capacity 165/175/185/200 Ltrs of any make complete all as specified and directed. |
| 61 | All as per item No 57.00 above but Refrigerator of capacity 240/286/300/315 Ltrs of any make complete all as specified and directed. |
| 62 | All as per item No 57.00 above but Compressor for water cooler of capacity 40/80 Ltrs complete all as specified and directed. |
| 63 | All as per item No 57.00 above but Deep Freezer of capacity of 310/500Ltrs of any make complete all as specified and directed. |
| 64 | All as per item No 57.00 above but Compressor for Window type & split type AC of capacity 1.5 TR complete all as specified and directed. |
| 65 | Taking out old unserviceable thermostat and supply & fix new thermostat of approved make and suitable size & model for Auto \"D\" thermostat with knob /Bimetal thermostate with heater Assembly for refrigerator or equivalent complete all as specified and directed. |
| 66 | All as per item No 62.00 above but Thermostat Nofor water coller or equivalent complete all as specified and directed. |
| 67 | All as per item No 62.00 above but Thermostat with knob for any type AC or equivalent complete all as specified and directed. |
| 68 | All as per item No 62.00 above but Thermostat with knob for suitable for deep freezer of any capacity complete all as specified and directed. |
| 69 | Taking out old unserviceable relay unit and supply and fix new relay kit (OLP + LMS relay or box type) as per samplefor refrigerator complete all as specified and directed. |
| 70 | Taking out old unserviceable relay kit and S&F new relay kit as per samplefor water cooler, No 412Y/512Y or equivalent complete all as specified and directed. |
| 71 | Taking out old unserviceable relay of any type and S&F new potential box type relay/ PTC relay of suitable model for window/ split type AC/ deep freezer complete all as specified and directed. |
| 72 | Taking out old/burnt starting capacitors of 220V,50 Hz and supply & fix new starting capacitor of 40 to 60 MFD complete all as specified and directed. |
| 73 | All as per item No 69.00 above but Starting capacitor 80 - 100 MFD complete all as specified and directed. |
| 74 | All as per item No 69.00 above but Starting capacitor 100 - 120 MFD complete all as specified and directed. |
| 75 | Taking out old/burnt running capacitors and supply & fix new running capacitors of 10/15/25 MFD complete all as specified and directed. |
| 76 | All as per item No 72.00 above but Running capacitor 36 MFD complete all as specified and directed. |
| 77 | All as per item No 72.00 above but Running capacitor 55+6 MFD complete all as specified and directed. |
| 78 | Taking out old/burnt fan motor capacitors and supply & fix new fan motor capacitors 4MFD/ 6 MFD suitable for Split AC, Window AC, Desert Cooler complete all as specified and directed. |
| 79 | Material and labour for replacement of unserviceable/ leakage cooling coil complete suitable for existing model of Refrigerator of capacity 286/300 Ltrs complete all as specified and directed. |
| 80 | Supply and fix in replacement evaporator freezer assembly for single door refrigerator up to 210 Ltr capacity of any make & capacity complete all as specified and directed. |
| 81 | Supply and fix in replacement of broken freezer door complete with casing and lock nut as per sample for refrigerator of any capacity complete all as specified and directed. |
| 82 | Supply and fix new door handle as per sample in replacement of old broken handle of Deep Freezer complete all as specified and directed. |
| 83 | Supply and fix new door gasket in replacement of old unserviceable door gasket of Deep Freezer of any capacity complete all as specified and directed. |
| 84 | Supply and fix in replacement of vegetable tray complete suitable for existing model of refrigerator of any capacity complete all as specified and directed. |
| 85 | Supply and fix in replacement of chiller tray complete suitable for existing model of refrigerator of any capacity complete all as specified and directed. |
| 86 | Supply and fix in replacement of bulb pintype/thread type suitable for existing model of refrigerator of any capacity complete all as specified and directed. |
| 87 | Supply and fix in replacement ofbroken door panel gasket including door switch complete suitable for existing model of refrigeratior of any capacity complete all as specified and directed. |
| 88 | Supply and fix in replacement gas drier filter suitable for refrigerator, water Cooler deep freezer Split AC, window AC of any make & capacity complete all as specified and directed. |
| 89 | Supply and fix in replacement copper capillary tube size 31 gauge for refrigerator/ Deep freezer complete all as specified and directed. |
| 90 | Supply and fix in replacement copper capillary tube size 36 gauge for refrigerator/ Deep freezer complete all as specified and directed. |
| 91 | Supply and fix in replacement copper capillary tube size 40/50 gauge for water Cooler complete all as specified and directed. |
| 92 | Supply and fix in replacement copper capillary tube size 60 gauge for Split/ window AC complete all as specified and directed. |
| 93 | Supply and fix in replacement copper pipe ½” dia, wall thickness 0.032 mm including insulation complete all as specified and directed. |
| 94 | Supply and fix in replacement copper pipe 1/4\" dia, wall thickness 0.030 mm complete all as specified and directed. |
| 95 | Supply and fix in replacement copper pipe 5/16\" dia, wall thickness 0.035 mm complete all as specified and directed. |
| 96 | Supply and fix in replacement copper pipe 5/8\" dia, wall thickness 0.035 mm complete all as specified and directed. |
| 97 | Supply and fix in replacement copper pipe 3/8\" dia, wall thickness 0.035 mm complete all as specified and directed. |
| 98 | Supply and fix in replacement electronic timer circuit/ manual timer for double door refrigerator of any make & capacity complete all as specified and directed. |
| 99 | Supply and fix in replacement electronic power supply control PCB for double door refrigerator of any make & capacity complete all as specified and directed. |
| 100 | Supply and fix in replacement evaporator fan motor for double door refrigerator of any make & capacity complete all as specified and directed. |
| 101 | Supply and fix in replacement ofbroken top door panel gasket complete suitable for existing model of water cooler of any capacity complete all as specified and directed. |
| 102 | Supply and fix in replacement of burnt out condenser fan motor, single shaft 1/35, HP capacity, single phase, 230 VAC for water cooler complete all as specified and directed. |
| 103 | Supply and fix in replacement of burnt out condenser fan motor, single shaft1/83 HP capacity, single phase, 230 V, AC for water cooler complete all as specified and directed. |
| 104 | Supply and fix in replacement of burnt out condenser fan motor, single shaft1/10 HP capacity, single phase, 230 V , AC for water cooler complete all as specified and directed. |
| 105 | Supply and fix in replacement of UNSV push cock of SS, 15 mm dia for water cooler complete all as specified and directed. |
| 106 | Supply and fix in replacement of UNSV stop cock, 15 mm dia for water cooler complete all as specified and directed. |
| 107 | Supply and fix fan blade (As per sample) in replacement for water cooler/ deep freezer/ refrigerator of any capacity complete all as specified and directed. |
| 108 | Taking out old unserviceable/broken float valve & Supply and fix new float valve complete for water cooler of any capacity complete all as specified and directed. |
| 109 | Material and labour for repair/ replacement of corroded bottom portion of the water cooler of any make & capacity with MS angle iron of suitable size as per existing, including welding/ brazing with MS sheet 1.6mm thick at the base of water cooler for mounting of compressor, blower motor, etc complete all as specified and directed. |
| 110 | Material and labour for replacement of old wornout/ burnt wiring of water cooler/ deep freezer/ refrigerator by using copper conductor wire PVC sheathed of suitable size and length complete all as specified and directed. |
| 111 | All as per item No. 107.00 but for window/split type A/C of any capacity complete all as specified and directed. |
| 112 | Supply and fix in replacement of electronic circuit (PCB) Original / Assembled(External type) complete including controlling unit i.e. (remote) all as per existing system and suitable for 1.5/2.0 TR capacity split type / window ACcompatible with all AC\"s Brands in original position complete all as specified and directed. |
| 113 | Taking out burnt/ unserviceable fan/blower motor of window type AC of any type & capacity and S&F new fan/ blower motor double shaft single/double speed, single phase, 230 V, AC of 1/4HP, 1/5HP, 1/6HP or any other capacity as required complete, making suitable fixing arrangment for existing place (as per sample) complete all as specified and directed. Make: - AUE/ Fracmaster/ Popular |
| 114 | Supply and fix fan blade (As per sample) in replacement for window type AC/split type AC of any capacity complete all as specified and directed. |
| 115 | Material and labour for taking out old broken drain outlet pipe of any type attached to indoor unit of split type AC & Supply and fix new drain outlet PVC pipe 20mm dia from indoor unit to nearest suitable drain outlet for split type AC of any capacity complete all as specified and directed. |
| 116 | Servicing only window type AC 1.5/2 TR complete with chemical wash to condenser and cooling coil, cleaning of entire elements of AC, oiling/ greasing to motor including taking out & refixing the machine at its original location complete all as specified and directed. |
| 117 | Servicing only for split type AC of any capacity, including chemical wash or equivalent, to condenser and cooling coil, cleaning the entire parts, oiling/ greasing to condenser motor, cooling coil blower motor complete all as specified and directed. |
| 118 | Material and labour for disconnecting the water cooler of capacity 40/60 Ltrs/hr from electric and water connection. Cleaning the condensor unit by using carbon tetra chloride cleaning the condensor fins, oiling/ greasing the fan motor, checking of alignment of motor, cleaning of water storage tank, fixing back the water cooler and testing complete all as specified and directed. |
| 119 | Material and labour for servicing the deep freezer unit completely for trouble free working and satisfactory performance by means of cleaning each part of the machine carefully, greasing/ oiling every moveable part, cleaning the condenser and cooling coil complete with the help of wire brush, soda wash and pressure air through blower and cleaning the machine for better working complete all as specified and directed. |
| 120 | Material and labour for gas charging for Refrigerator of any capacity & make with R-22, R-134(a), R-600 and R-600 gas as required quantity including all allied works such as vaccumising the complete system, leak test, pressure test, replacement of copper filters, copper capillary tube, copper tubing of suitable size and required length flare nut, dead plug, dead cap etc. complete with testing and commissioning all as specified and directed.Note:- (i) Job includes dismantling equipment from any site height and transporting to workshop if necessary and reinstalled in site and testing. (ii) Job to be guaranteed for minimum one year. |
| 121 | All as per item No 117.00 but for Water cooler of any capacity & make complete all as specified and directed. |
| 122 | All as per item No 117.00 but for Deep Freezer of any capacity & make complete all as specified and directed. |
| 123 | All as per item No 117.00 but for Window type AC/ Split type AC of 1.5 TR capacity complete all as specified and directed. |
| 124 | All as per item No 117.00 but for Window type AC/ Split type AC of 2 TR capacity complete all as specified and directed. |
| 125 | Taking down unserviceable/ damaged/ rusted condensor unit of 1.5/2 TR split type AC complete by means of disconnecting electrical connection and suction and discharge pipe line and supply & fix new condensor unit consisting of body, motor, condensor & blade suitable forexisting dismantled model or equivalent approved by Engineer-in-Charge and connect to suction and discharge pipe line to compressor after refixing compressor of existing unitas directed and testing and commissioning complete for satisfactory performance of unit after gas charging complete all as specified and directed. |
| 126 | Supply and fix in replacement of unserviceable/rusted condensor unit complete suitable for existing model of refirigerator of capacity up to 210 Ltr complete all as specified and directed. |
| 127 | Supply and fix in replacement of unserviceable/rusted condensor unit complete suitable for existing model of Refrigerator of capacity 286 ltr to 310 Ltrs complete all as specified and directed. |
| 128 | Supply and fix in replacement condenser coil complete with copper tube and aluminium fins suitable for deep freezer 200-300 ltrs capacity of any make and necessary welding/ bracing work complete all as specified and directed. |
| 129 | Supply and fix in replacement condenser coil complete with copper tube and aluminium fins suitable for water cooler 40/80 ltrs, 60/120 ltrs & 150 ltrs capacity of any make with welding/bracing work complete all as specified and directed. |
| 130 | Material and labour for replacement of 1/4\", 5/16\", 1/2\" 5/8\" and 3/8\" nearest tube size insulation with superlon insulation to copper tubing as required length from indoor to outdoor unit of split AC as directed by Engineer in charge after taking down old, deteriorated insulation complete all as specified and directed. |
| 131 | Supply and fix MCB protected power unit include MCB SP 16A to 25 A, 220V, 50 Hz Complete all as specified and directed. Make:- Havells Cat Part No : DHDMCSN0251025 |
| 132 | Supply and fix in replacement two pole contactor up to 30 Amp capacity 230 V, 50Hz suitable for split type AC complete all as specified and directed. Make:- L&T/ Havells / BCH / Siemens / ABB |
| 133 | Supply and fix in replacement PVC air filter suitable for window/ split type AC of any make & capacity complete all as specified and directed. |
| 134 | Supply and fix in replacement of louver blades synchronous motor/ swing motor for 1.5/ 2 ton window/ split type AC indoor unit of any make and capacity as per sample complete all as specified and directed. |
| 135 | Supply and fix in replacement of electronic display assembly suitable for window/ split type air conditioner of any make and capacity as per the sample complete all as specified and directed. |
| 136 | Supply and fix in replacement of temperature sensor assembly for window/ split type air conditioner 1.5/2.0 TR as per sample complete all as specified and directed. |
| 137 | Supply and fix in replacement of cooling coil unit suitable for 1.5/2.0 Ton window type AC including welding/ bracing work etc of existing model & make complete all as specified and directed. |
| 138 | Supply and fix in replacement of cooling coil suitable for 1.5/2.0 Ton split type AC indoor unit including welding/ bracing work etc of existing model & make complete all as specified and directed. |
| 139 | Supply and fix in replacement of heavy duty air conditioner outdoor unit mounting bracket/ stand suitable for 1.5/2.0TR split type air conditioner as per sample complete all as specified and directed. |
| 140 | Supply and fix in repair Pin/ service valve of size 1/2\", 1/4\", 3/8\", 5/8\" suitable for refrigerator, deep freezer, water cooler and Air conditioner of any make and model complete all as specified and directed. |
| 141 | Dismantling blower/ Condenser fan motor of window type AC of 1.5/2.0 TR capacity and Supply and fixing new fan motor alongwith fan of existing make and size and refixing in position, connecting and testing on load complete all as specified and directed. Make: Marathon/ Crompton/ Voltas/ GE/ Carrier/ Samsung |
| 142 | All as per item No 138.00 but for split air conditioner of 1.5 /2.0TR capacity complete all as specified and directed. |
| 143 | Supply and fix new 5 Amp pin top in replacement of old broken pin top of any make complete all as specified and directed. |
| 144 | Supply and fix new 15 Amp pin top in replacement of old broken pin top of any make complete all as specified and directed. |
| 145 | Supply and fix in replacement of broken/ damage front grill assembly complete suitable for existing model of window AC of any capacity complete all as specified and directed. |
| 146 | Material and labour for repairs/ servicing of old desert cooler by dismantling and cleaning completely, scraping inner & outer side incl flaps to remove old dirt and applying one coat of synthetic enamel paint (inner & outer both surface) of existing colour replacing wood wool pad mimimum 15mm thick from three side, binding with GI wire, assembling and testing including oiling/ greasing of fan motor, servicing of water pump etc complete all as specified and directed. |
| 147 | Supply and fix in repair/ replacement 1800 cfm fan motor having copper wounded with blade suitable for the following sizes desert cooler SP 230 Volt 50 Hz including commissioning and testing complete all as specified and directed. |
| 148 | All as per item No 144.00 above but 3000 cfm complete all as specified and directed. |
| 149 | All as per item No 144.00 above but 4000/5000 cfm complete all as specified and directed. |
| 150 | All as per item No 144.00 above but 6000 cfm complete all as specified and directed. |
| 151 | Supply and fix in repair 1800 cfm fanblade of metal body suitable for the following sizes desert cooler SP 230 Volt 50 Hz including commissioning and testing complete all as specified and directed. |
| 152 | All as per item No 148.00 above but 3000 cfm complete all as specified and directed. |
| 153 | All as per item No 148.00 above but 4000/5000 cfm complete all as specified and directed. |
| 154 | All as per item No 148.00 above but 6000 cfm complete all as specified and directed. |
| 155 | Supply and fix in repair 1800 cfm fan blade of PVC body suitable for the following sizes desert cooler SP 230 Volt 50 Hz including commissioning and testing complete all as specified and directed. |
| 156 | All as per item No 152.00 above but 3000 cfm complete all as specified and directed. |
| 157 | All as per item No 152.00 above but 4000/5000 cfm complete all as specified and directed. |
| 158 | All as per item No 152.00 above but 6000 cfm complete all as specified and directed. |
| 159 | Supply and fix in repair submersible water pump SP 230 Volt 50 Hz 4-6 mtr head with PVC 10mm dia flexible hose connected and commissioning and testing complete all as specified and directed. |
| 160 | Material and labour for replacement of PVC water tube and distribution with 3 way PVC connection assembly complete for Air cooler/ desert cooler of any size and capacity complete all as specified and directed. |
| 161 | Supply and fix in replacement front grill, double diversion with grill box for control switches, for desert cooler of any make any type made of PGI sheet of 22 gauge complete all as specified and directed. |
| 162 | Supply and fix in replacement two sides and one back sutter having grooves arrangement made by GI sheet of existing shape and size for desert cooler complete all as specified and directed. |
| 163 | Supply and fix in replacement of water tank of desert cooler of size not less than 102cm x102cm x 26cm (Approx) made from 20 gauge PGI sheet as per site requirement including necessary holes & drain plug complete all as specified and directed. |
| 164 | Supply and fix in replacement of water tank of desert cooler of size not less than 102cm x 85cm x 20cm (Approx) made from 20 gauge PGI sheet as per site requirement including necessary holes & drain plug complete all as specified and directed. |
| 165 | Dismantling the old U/S desert cooler and supply & fixing in replacement new cabinet fabricated with 24 gauge GI sheet consisting of three side panels, front, top and tank, GI wire net including vertical member, of size not less than 85cm x 60cm x 52 Cm in size with double diversion grills and grill box suitable for not less then 15” sweep fan and making holes with fixing arrangement including providing 4 way PVC distributor, PVC pipe 1.5 to 2 Mtr for water, wood wool pads, electrical wiring for fan & pump, controlled separately with 5 amp Piano type switch etc water tank and top cover painted with two coats of black anti corrosion paint complete all as specified and directed. |
| 166 | Taking out and opening carefully the exhaust fan / kit fan motor of desert coolers of any make / model, cutting and removing old short circuited stator winding complete and rewinding with super enamelled copper winding wire of existing gauge including replacement of unserviceable GM bush, ball bearing, MS Saft, long nuts bolts etc and reasembling complete all as specified and directed.Note:- Repair work will be carried out within 07 day after intimation to contactor on telephonic followed by in writting. Any delay beyound 07 day shall be compensated through panel recovery @ 350 per day/ per desert cooler till the date of rectification or repaired fan and deposited in MES store yard complete all as specified and directed. |
| 167 | Supply & fixing wood wool padmimimum 15mm thick for sides and back shutters of coolers made out of chicken wire mesh filled with fine quality wood wool and stitched with GI wire net frame for desert cooler of any make & size complete all as specified and directed. |
| 168 | Material and labour for replacement of switch assembly complete for Air cooler/ desert cooler of any size and capacity complete all as specified and directed. |
| 169 | Supply and fixing in repair cord flexible three core copper conductor multi-stranded2 mtr long with 5 Amps plug top and connected to the equipment complete all as specified and directed. |
| 170 | Supply and fixing in repair angle iron frame for mounting fan motor of desert cooler with nut, bolt and all accessories complete all as specified and directed. |
| 171 | Taking down unserviceable/ damage wall mounted cooling coil unit of split type AC complete by means of disconnecting electrical connection and suction and discharge pipe line and S&F new cooling coil unit of suitable capacity of existing dismantled model or equivalent approved by Engineer-in-Charge including remote control, proper fixing on wall, connect to electrical system and connect to suction and discharge pipe line, drain water pipe line as directed and testing and commissioning complete for satisfactory performance of unit after gas charging Suitable for 1.5/2 TR capacity, split AC, 230VAC complete all as specified and directed. |
| 172 | Material and labour for replacement of3 core, 4 sqmm, copper conductor PVC insulated flexible cable from main supply point to out door unit point complete all as specified and directed. |
| 173 | All as per item No.169.00 above but 3 core, 2.5 Sqmm complete all as specified and directed. |
| 174 | All as per item No.169.00 above but 3 core, 1.5 Sqmm complete all as specified and directed. |
| 175 | Supply and fix single pole contactor of suitable model and size for 1.5/2 TR split type AC complete all as specified and directed. |
| 176 | Supply and fix long shaft (Double) indoor unit motor (blower) of suitable HP, as per site requirement, for cooling coil of capacity 1.5/2 TR split AC complete all as specified and directed. |
| 177 | Supply and fix in replacement single shaft, blower motor of 1/6,1/8,1/5 HP capacity for split type AC of capacity 1.5/2 TR/Air Curtain of any size complete all as specified and directed. Make:- AUE, Fracmaster, Popular |
| 178 | Supply and fix in replacement swing motor for split type AC of any capacity complete all as specified and directed. |
| 179 | Supply only suitable remote control handset of split type AC of any capacity in replacement of old unserviceable remote control handset of any type complete all as specified and directed. |
| 180 | Supply and fix in replacement angle valve of size 5/8\", 1/2\" or nearest size suitable for split type AC of any capacity complete all as specified and directed. |
| 181 | Supply and fix in replacement brass flare nut of size 5/8\", 1/2\" or nearest size suitable for split type AC of any capacity complete all as specified and directed. |
| 182 | Supply and fix in replacement of blower of indoor unit of split type air conditionor suitable for 1.5/ 2 TR capacity as per sample complete all as specified and directed. |
| 183 | Material and labour for taking out the Air Curtain of any size from the wall above the door, cleaning the blower complete & refixing in position complete all as specified and directed. |
| 184 | Material and labour for cutting the existing window including additions/ alterations to make opening suitable for fixing the window type air conditioner including welding/ wood work as per site requirement to match with adjoining/ existing surfaces and shifting the window type air conditioner to the new altered location/ existing including the necessary connections and testing complete all as specified and directed. |
| 185 | Labour only for removing & reinstallation of split type AC 1.5/2TR cap, indoor & outdoor unit including all allied work such as bending, shaping, brazing to copper tubing & insulation to tubing, connection of water drain piping & fixing it properly, etc including testing & commissioning complete all as specified and directed. |
| 186 | NOTE : SCHEDULE OF CREDIT (Amount on page No 53 shall be deducted offline from the total quoted amount to arrive at the net contract sum to be considered for acceptance. |