| 1 | SCHEDULE‘A’ PART-I (SECURITY DEPOSIT FOR HT CONSUMER (BULK) OF 1X100 KVA DISTRIBUTION SUB-STATION) |
| 2 | Supply and fixing of AC three phase 4 wire fully static trivector Energy meter with KIOSK FOR 100 KVA (AMR Compatiable) CT PT metering unit fixedon the pole |
| 3 | Security deposit for HT Consumer of 1x100 KVA distribution Sub-StationContractor will be leaise with MSPDCL for load sanction on writing of Department alongwith fwg charges :- (a) 1 month energy charge for 1x100 KVA (KVAXLFXHrsxtarrif x 1) = (1x100x0.25x630hrsxRs 9.25)(b) 1 month demand charge for 1x100 KVA = Rs 100x100x1 including service connection with department Note:- Contractor is responsible for service connections and liaison with MSPDCL power house and first billing (bill amt deducted from the department elect charges). |
| 4 | SCHEDULE‘A’ PART-II (SUPPLY, ERECTION & STRINGING OF LT LINE USING AB CABLE (3X70+1X50)) |
| 5 | Supply and fixing of 9 MTR height steel tabular pole S.T.P (410 SP-31) belded with base plate and necessary angle iron for LT line arrangements two coat painting with synthetic enamel paint over a coat of primer |
| 6 | Suspension fitting for AB Cable with bare messenger wire complete with eye hook as per construction standard |
| 7 | Insulation pierching connector for AB Cable Big size (Main 16-95 sqmm service 4-35(50) Sqmm as per TS & Construction standards |
| 8 | Supply and fix LT overhead line on 9 metersteel tabularpoles with XLPE insulated AB cable 3 core x70 Sqmm +1 core x35 Sqmm |
| 9 | Supply and fix LT overhead line on 9 metersteel tabularpoles with XLPE insulated AB cable 3 core x50 Sqmm +1 core x35 Sqmm |
| 10 | Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm diaG.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required. |
| 11 | SCHEDULE‘A’ PART-III (INSTALLATION, TESTING & COMMISSIONING OF 1X100 KVA DISTR SUB-STATION ) |
| 12 | Supply installatin testing and commissioning of copper wound trnasformer step down outdoor type complete with standard fittings, HT 11 KV 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit all as per IS:2026 of capacity 100 KVA Installation of transformer on the PCC base plateform 2Mtr x 2Mtrx 60 CM above the GL and 60 Cm below the GL |
| 13 | Supplying of channel iron 100 mm X 50 mm X 6 mm (9.56 kg per metre), pole top bracket/ cross arm for Transformerconductor complete with 50 mm X 6 mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required. 2.86 Long |
| 14 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) V shape cross arm for two transforme complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required. 2.8 Mtr long |
| 15 | Supplying and erection of a set of cross bracing frame work for 11 KV over head line double pole structure having four members fabricated out of 50 mm X 50 mm X6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mmheight, complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc (as per drawing) and painting with primer and finish paint as required.. |
| 16 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 17 | Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required. |
| 18 | Supply and laying of 240 Sqmm one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 19 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge.Made of G.I. wire of dia 4 mm along with 50mmx50mmx6mm thick angle iron |
| 20 | Indor type LT panel Board made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nosaluminium strip of suitable size (one on each side) including, G.I. clamping brackets,angle iron bracket, steel fasteners, connecting to earthing system etc. as required.Incommer300 A switch fuse unti -01 No, 300 A Change over switch -01 No, RYB Indicator with sliding fuse unit -01 Set, Voltmeter-01, Ameter -01Outgoing100A MCCBTPN -01 No, 63 A MCCB TPN -01 No , 30 A SPN -04 Nos& 16 A SPN-04 Nos |
| 21 | SCHEDULE‘A’ PART-IV (SUPPLY ERECTION & STRINGING OF 11KV LINE (0.5 KM) WITH ACSR (RABBIT) CONDUCTOR WITH 9M LONG STEEL TABULAR POLE) |
| 22 | Supply of 11 MTR height steel tabular pole S.T.P (410 SP-31) belded with base plate and necessary arrangements two coat painting with synthetic enamel paint over a coat of primer: |
| 23 | Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required. |
| 24 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) pole topbracket/ cross arm for single 11 KV over head line conductor complete with 50 mm X 6mm flat iron clamp, bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required. |
| 25 | Erection of pole top/ straight two wire/ V shape two wire, angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11 KV as required. |
| 26 | Supplying and erection for 11 KVACSR Rabbit conductor etc. as required |
| 27 | Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required |
| 28 | Supplying and erection of 11 KV disc insulator for 11 KV over head lines withgalvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required. |
| 29 | Supplying and erection of three piece nonlinear resistortype lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required. |
| 30 | Supply and hanging of overhead line of 11KV on 11 meter steel poles with continuous GI earth wire, , fixing in cross arms with necessary accessories and ACSR Conductor size 3 of 6/1x3.50mm(Rabbit) 400x3 = 1200 +300 mtr extra for HT connection etc 1.5Km@214kg/km= 321.00Kg |
| 31 | Erection of steel tubular or rail pole strut in cement concrete 1:3:6 (1 cement : 3coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling and secured with holding clamps, bolts, nuts, etc. as required. |
| 32 | Providing and making steel pole collar with cement concrete (1 cement : 3 coarse sand : 6 stone aggregate 20mm) of specified size and shape including form work, plastering if required, curing etc as required. (volume of pole/ pipe not to be deducted)( 24x0.40x0.40x0.30 |
| 33 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 34 | 11 KVA Gang Operating device ( Air breaker switch) with insulators, bracing arms and necessary nuts bolts |