Tender For Electrical Work At Bhiwadi => Limited; 1 LIGHT & FAN POINTS: P & F light/ fan/ call bell points/ sockets etc. with 2x1.5 sq.mm pvc insulated 1100 v grade copper conductor wires and 1.0 sq.mm earth wire in concealed/ surface using 1.5 mm thick PVC 20mm/25mm/32mm dia conduits, accessories such as bends, tees, saddles, draw boxes, mounting boxes, inner plates, cover plates, ceiling rose etc. (wherever required) and plugs etc. The circuit wiring starting from DB to point control box/ switch box using 2x2.5 sqmm & 1x1.0 sqmm earthing pvc insulated wiring with colour code to be provided. Identification ferrules at both ends to be provided. Notes: Each circuit shall have independent earth wire. Each point shall be earthed. Circuit wiring to be included in the point wiring rates a) one point controled by one switch 50 Nos. b) Wall fan point controlled by one 6 Amp modular switch at SB Level and 6 amp 5 pin socket at designed place 14 Nos. c) 6 Amp socket with switch at designated places 12 Nos. d) Call bell point 1 Nos. e) ONE Ceiling Fan point with 5 step electric regulator 2 Nos. f) Exaust Fan point 3 Nos. 2 POWER POINTS: Same as item no 1 but wiring for 16 A - 6 pin sockets using 4 sq.mm pvc insulated copper conductor wire with independent 2.5 sq.mm earth wire from DB to 1st Socket &1st socket to 2nd Socket with 2.5sq.mm and 1.5 sq.mm earth wire including providing and fi a) Power points with 2.5 sq.mm copper conductor wires 14 Nos. 3 A.C POINT wiring with 2x4sqmm +1x2.5 SQ mm cupper conductor from AC DB to ACPOINT in 16 swg GI conduit ac point including supply ing and fixing of metal AC box with 3 pin metal clad top and 32/25 amp SPMCB 5 Nos. 4 DISTRIBUTION BOARDS(DOUBLE DOOR) P/ F sheet metal distribution boards of approved make Double door type and making necessary connections etc. complete. a) TPN 6 Way. 2 Nos. Having Incomer - 63 Amp TPN MCB Outgoings – 6 -16 Amp SP MCB - 12 Nos, 32 Amp SP MCB - 4Nos b) S & F 40 Amp DP MCB with metal clad socket with encloser ( for ups I/P & O/P) 2 Nos. c) S & F 8 way SPN DB with 2 No. 32 AMP DP MCB Controlling to 4 Nos 10 Amp SP MCB ( For ATM ) 2 Nos. 5 LIGHT & FAN FIXTURES:P & F light fixture & accessories as per the following details and making connections, assembling, fixing, testing & installation with 3 years warranty. Following Fixtures including all accessories & extension chords as maybe necessary complete. All CFL / Flurescent fixtures (except down lighters) to be hung from the RCC ceiling by sitable chain / rods) all to fixture rates to include 3 years warranty. Including all removing, shifting, repairing, fixing, welding, cutting, instalation, testing, commissioning work of existing or proposed items for the folowing work. Including making good, proper finish of walls, floor and roof with masonary, R.C.C., plaster, pop, puty, primer, paint, etc. complete in all respects. Including color temp. for light fixtures must be 6500k. Dealer authorisation certificate with invoice detail required. Technical specification minimum 100 lumens per watt, Pf>.90, THD<20% a) Philips RC 380B LED Full glow 24 X 24 (6500K)/BAJAJ/OSRAM/HAVELLS 32 Nos. b) Philips LED Tube lights 18 W/ 22 W (6500K) /BAJAJ/OSRAM/HAVELLS/HPL 15 Nos. c) Metal body Wall fan 400 mm - Crompton High flow of capacitor start, three speed wall mounting/cabin fan of following sweep with the help of anchor bolts including making connection testing etc. as required. Each wall fan should be connected through independent switch and socket of 6Amp.(Crompton/ Almonard/ Usha/ Havells)Only Metal body Wall mounted 3 pin type fan to be used 14 Nos. d) Philips Green LEDi 15 Watt DN 194 B (6500K) /BAJAJ/OSRAM/HAVELLS/HPL 18 Nos. e) Ceiling fan 48 crompton make 4 Nos. f) Exhaust Fans - 300mm dia with frame complete - Crompton/ Bajaj/ Usha 3 Nos. 6 CABLES / WIRES P & F heavy duty armoured cable in conduit pipe internally and GI pipe externally with all bends, junctions etc. on saddles wherever exposed and crimping the relevant connection ends complete as per approved section and make - Gloster / National/ Polycab a) 3.5 core 35 sqmm aluminium 30 Rmt. b) 3.5 core 16 sqmm aluminium 45 Nos. 7 Wiring in concealed 16SWG MS conduit of required size with PVC insulated, 1100V grade multi stranded copper conductor wires of following specifications: A) 4 X 10 sqmm Cupper wire with 1x2.5 sqmm earth cupper conductor wire in pvc conduit. ( for db to electrical panel) 150 Rmt. B) 2 X 6 sqmm Cupper wire with 1x2.5 sqmm earth cupper conductor wire in pvc conduit. ( for panel to UPS db) 100 Rmt. C) 2 X 2.5 sqmm Cupper wire with 2x1.5 sqmm earth cupper conductor wire in pvc conduit. 180 Rmt. 8 UPS POINTS & CIRCUITS P/F UPS point in pvc conduit 1.5 mm thkns & duly wired with2x2.5 sqmm insulated copper wire along with 1x1.5 sqmm pvc insulated wire for earthing including bends, nipples, junctions, M.S switch boxes each to have 3 Nos 6 A 5 pin modular socket, 1x 6 A indicator controlled by 1x6A switch compl fine finish incl. making necessary connections & start of equipment as per details & drawings. a) 1 st point 30 Nos. 9 EARTHING: a) Earthing with copper earth plate 600 x 600mmX3 MM including accessories embodying by digging 3 mtrs below the ground level and refilling with 6 to 10 alternate layers of salt, charcoal and providing masonry enclosure with cover plate and perforated earth pipe, funnel etc. compl. and drawing of earth wire/ earth strip as per the design requirements from the earth pit to the DB panel complete as instructed.(0ne for main panel and another one for computers to be connected to UPS OUT PUT DBS. 2 Nos. b) P & L 8 SWg copper earth wire at designated places in pvc conduit in side the building. 40 Mtr. Telephone/Computer conducting and wiring 10 Supply and laying of the following sizes of PVC Conduits with all accessories concealed or on surface as required. a. 10 Pair Krone Tag Block 1 Nos. 11 Supplying and drawing the following type of cables for telephone system in existing conduit a.For telephone system with a) i. 2 Pair 0.6mm dia copper conductor (ATC) unarmoured cable. 120 Mtr. b) ii. 10 pair 0.6mm dia copper conductor (ATC) unarmoured cable. 20 Mtr. 12 Providing and installing in position the following outlets in recessed G.I boxes a) Telephone outlet box along with RJ 11 socket. 12 Nos. 13 Supplying and drawing for computer cable in existing PVC Conduit. a) 24 port Jack panel , SWAITCH , with data rack as per Dlink 1 Nos. c) I/O Box Single as per D-link 30 Nos. d) Patch Cord 1meter as per D-link 30 Nos. e) Patch Cord 2meter as per D-link 30 Nos. f) Cable cat 6 as per D-link in conduit pipe 800 Mtr. 13 MAIN PANEL FOR SMALL BRANCH :- Designing manufacturing, installing, testing and commissioning of cubical type MAIN PANEL CPRI approved made from 16 SWG CRCA sheet steel, type base M.S. channel for grouting on floor complete with MCCB, MCBs, meters, C.T., etc. complete in all respect, insulated bus bar with near shrinkable PVC sleeve in suitable bus bar chamber, wiring, name plates, danger plates, earth bus etc. & comprising of compartments with hinged doors and rubber gasket, bus bar chabmer with bolted door and rubber gasket etc. the panel being of dust & vermin proof construction and to be painted with primer and smoke gray paint (minimum two coats) to look attractive. The panel should be comprising with the following : (Degree of Protection IP-54) Nos. 1.00 INCOMER: - ALL MCCB SHOULD HAVE 25 KA SHORT CIRCUIT CURRENT CAPACITY (C- CLASS) (Legrand/ HPL/ C&S/siemens/ABB/ Schneider) (i) 150 Amp 4 - P, MCCB (3 Phase) 1 Nos. (ii) 100 Amp 4 - P, ON LOAD change over switch (iii) 250 Amp. Capacity aluminum bus bar for ATM & system room heat shrinkable proper insulation with heat shrinkable proper insulation with color coded. Analog ammeter and voltmeter with selector switches three number indicating lamp R-Y-B Phase indicators with 2 amp. back up HRC fuses & Energy Meter with KWH and PF indication (Back up Fuse protection) INCOMER: - ALL MCCB SHOULD HAVE 25 KA SHORT CIRCUIT CURRENT CAPACITY (C- CLASS) (Legrand/ HPL/ C&S/siemens/ABB/ Schneider) (i) 150 Amp 4 - P, MCCB (3 Phase) 1 Nos. (ii) 100 Amp 4 - P, ON LOAD change over switch (iii) 250 Amp. Capacity aluminum bus bar for ATM & system room heat shrinkable proper insulation with heat shrinkable proper insulation with color coded. Analog ammeter and voltmeter with selector switches three number indicating lamp R-Y-B Phase indicators with 2 amp. back up HRC fuses & Energy Meter with KWH and PF indication (Back up Fuse protection) OUT GOING : - ALL MCCB SHOULD HAVE 25 KA SHORT CIRCUIT CURRENT CAPACITY DOUBLE BUS BAR PANEL DG SUPPLY ONLY FOR LIGHT, POWER, UPS, ATM ONLY A.C. SHOULD NOT OPERATE ON DG SUPPLY All MCCB must have 25 KA S.C. current capacity All outgoing feeder should have separate door and compartment. Each outgoing feeder shall be with indicator. (i) 100 Amp 4 - P, MCCB (3 Phase) 1 Nos. (A.C.)