| 1 | Work Part |
| 2 | Transformer {800 KVA (HV-11 KV, LV-0.433 KV), Amp (HV-42, LV-1066.70)} |
| 3 | *Internal and external inspection of two nos.transformers at EE (O&M)-I store*Checking conditions of bushing, winding, radiator, tank & leads.*HV & LV Connections*Tap Checks*General conditions of insulation*Check for dirt, metal swarf, moisture in tank and winding*Checking condition of gasket and replace with new one*Drying out transformer before oil filling*Checking leakage in transformers by pressuring through N2 and attend the leakage.*Transformer oil filling & Filtration |
| 4 | Painting and nomenclature of transformers. |
| 5 | After restoration of transformers shift to near new Railway silo switchgear location for erection and commissioning. |
| 6 | Making of 8 nos. earth pit for transformers and connect transformer |
| 7 | Making foundation for both transformers |
| 8 | Making transformer yard with proper metal fencing (Size 20ft X 35 ftx10ft) (W X L X H)and entry gate. |
| 9 | Making firewall in middle of both transformers |
| 10 | 50 mm gravel filling ( 6 inch deep) below transformer . |
| 11 | Work part for 11 KV Line |
| 12 | Dismantling 10 Nos. old railpole and re erection to new location with conductor laying and insulator installation |
| 13 | Installation of 11KV Polymer disc insulator |
| 14 | Installation 11 KV Polymer PinInsulator |
| 15 | Erection Of AB switch |
| 16 | Aluminium paint on 11 KV pole |
| 17 | Red Oxide paint on 11 KV pole |
| 18 | Laying & connection of 11 KV conductor |
| 19 | Erection Of H Beam double pole, |
| 20 | Supply part |
| 21 | Supply of AB Switch |
| 22 | Supply H Beam 37.1kg/Mtr &13 Mtr long |
| 23 | Supply 11 KV\"V\"cross arm |
| 24 | Supply11 KV Polymer PinInsulator |
| 25 | Supply11 KV DiscInsulator |
| 26 | Supply Stay set 19 mm with 7/10 swg wire |
| 27 | Supply ACSR Dog conductor double circuit 3 phase with 3% sag |
| 28 | Supply Nut-bolt |
| 29 | Supply Earthing coil |
| 30 | Supply Guarding Channel |
| 31 | Perforated cable Tray (300x50x18 MM) |
| 32 | 11 KV ,3C,End termination (UE) Kit, make 3M |