Supply And Installation Of Fire Detection System , Conventional 2 Zone Fire Alarm Panel Without Battery Each Zone Capable Of Taking 20 Detectors, Power Supply 26.5Vdc,2.5,4 Monitored Siren/Relay Outputs (En54-2 Par.7.8 Certified , Repeater Expansion Port, (Connection To Optional Rs485 Expansion Module), Tcp/Ip Module For Connectivity To Smart View Software , Conventional Intrinsically Safe Optical Smoke Detectors Operating Voltage 14.8 V Dc To 28 V Dc, Operating And Storage Temperature : 40Deg.C To +70 Deg.C, Humidity (No Condensation Or Icing): 0% To 98% Rh, Housing: White Flame Retardant Polycarbonate ,Terminals: Nickel Plated Stainless Steel , Conventional Intrinsically Safe Sounder Cum Strobe, Maximum Sound Output At One Meter: 100Db(A),Supply Voltage 6-28 Vdc,Ip 65 Atexcertified, Iecx Certified , Conventional Flameproof Manual Call Point Is Break -Glass Operated With A Flap. It Is Approved For Use In Zone1,2,21 And 22Hazardous Areas, Supply Voltage 250V Ac Max ,50V Dc Max, Operating Temperature -40 Deg.C To +55 Deg.C Ip66,Atex Certified, Iecx Certified, Complies With En 54-11 , Conventional Galvanic Barrier. Voltage U0 28V Current I0 93Ma,Power P0 0.65 W, Explosion Group Iia Iib Iic,Ip20, Ambient Temperature -20 Deg C ….+60 Deg.C _-4 Of…140 Of) , Addressable Zone Monitor Module, Digital Communication:Xp95 (Discovery And Core Protocol Pulses Of 5-9Vdc., Operating Temperature -20 Deg.C To +70Deg.C,Humidity (No Condensation)0% To 95% Rh ,Ip54 , Supplying, Installation, Testing And Commissioning Of Ul Listed Addressable Control Relay Modules , 12V 7 Ah Battery , 2C X1.5 Sq.Mm Abc Multistand Pvc Insulated Twitted Pair Shielded Armoured Frls Cable (Red Color) , Flp Double Compression 1.M20 Glands