| 1 | Excavation in trenches, not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, laying of cables, erection of poles, stays etc. and getting out in any type of soil, complete all as specified and directed. |
| 2 | Excavation in trenches, not exc 1.5 mtr wide and exc 1.5 mtr but not exc 3.0 mtr in depth for foundation, erection of poles, stays etc. and getting out in any type of soil, complete all as specified and directed. |
| 3 | Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exc 25cm thick, complete all as specified and directed. |
| 4 | Removing excavated soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point, complete all as specified and directed. |
| 5 | M&L for dry river sand, laid in trenches for cable protection, as 15cm thick below the cable and 8cm thick above the cable, complete all as specified and directed.Note :- Punned thickness of sand shall be measured and paid. |
| 6 | Supplying and Laying reinforced precast concrete cable cover, class HV, type-2, flat, of size 450x180x40mm, complete all as specified and directed. |
| 7 | M&L for plain cement concrete 1:4:8, type D-2 (using 40mm graded crushed stone aggregates) as in foundation, filling in and mass concrete etc., complete all as specified and directed. |
| 8 | M&L for plain cement concrete 1:2:4, type B-2 (using 40mm graded crushed stone aggregates) as in foundation, filling in and mass concrete etc., complete all specified and directed. |
| 9 | M&L for plain cement concrete 1:3:6, type C-2 (using 40mm graded crushed stone aggregates) as in foundation, filling in and mass concrete etc, complete all as specified and directed. |
| 10 | Supply erection and fabrication of cross arms, bracings, supports, clamps and back plates, fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed, complete all as specified and directed. |
| 11 | Supply, laying, commissioning & testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 volts grade, cross sectional area 70 Sqmm 3 Core, complete laid in trenches, duct, passing through pipe, fixed to poles, complete all as specified and directed. Note :- After cable passing through roads and culverts etc PCC will be done by contractor without any extra cost. |
| 12 | S&F in replacement cable jointing kit for 11 KV grade cable for outdoor termination heat shrink type joint, complete with jointing material and accessories, suitable for size 3 Core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm, complete all as specified and directed. |
| 13 | S&F straight through joints for underground cable including jointing material, accessrories and labour, complete for 3 Core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm 3 Core, complete all as specified and directed. |
| 14 | M&L for earthingcomplete with galvanised steel earth plate electrode of size 600x600x6mm thick, burried directly in ground, earth pit not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level, connected to the galvanised iron strip of size 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron and 32x6mm GI strip protected by provision of GI tube light grade 40mm bore including provision of concrete pit in PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) with 40mm thick RCC 1:2:4 cover, reinforced with XPM weight not less than 4 Kg /Sqm and 6mm dia round bar handle, excavation and earth work in any type of soil, charcoal dust and salt light grade and 20mm bore GI watering pipe light grade with funnel and wire mesh medium grade GI protection pipe 15mm bore 5 mtr long and GI strip upto main earthing of pole, complete all as shown in electrical plate No. 03 of MES Sch 2009 Part-I including dismantling old UNSV earthing and removal thereof, complete all as specified and directed. Notes :- (i) Main earthing strip from earth plate electrode to test point up to length of 7.5 meters length shall deemed to be include in quoted rates. (ii) GI protection pipe & earthing lead beyond 7.5 mtr shall be measured and paid separately under appropriate item.(ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department . |
| 15 | M&L for replacement GI tubing light grade 80mm bore with all fittings, laid in trenches or fixed to walls/ alongwith pole with suitable MS clamps, complete for protection of electric cable, complete all as specified and directed. |
| 16 | Supply, installation and erection in vertical position steel tubular swaged poles, type 410, SP-55 (11 meters long) with 300x300x6mm thick mild steel base plate continuously welded to pole, MS plate 3mm thick finial taper plug bolt, nuts and screws all as specified including factory painted with two coats of black bituminous paint internally throughout and externally for embedded portion and applying two coats of aluminium paint over a coat of red oxide primer on remaining exposed surfaces and making alternate black and white strips 30cm high with super enameled paint over a coat of red oxide primer upto 1.5 mtrs height from ground level/ coping after erecting, complete including taking down of Old UNSV pole, complete all as specified and directed. Note :-Excavation, PCC for foundation and earth work shall be measured and paid separately under respective items of this BOQ. |
| 17 | Supplying, fixing and testing gang operated air breaker switch, triple pole, mechanically operated mounted on insulators and steel frame with operating mechanism worked from ground level using heavy duty GI pipe for current rating 200 Amps, outdoor type (confirming to latest IS specifications), HT 11 KV, tripple pole with fixed contacts of phosphorous and bronze and a set of drop out HT fuse assembly, fuse carrier fitting, 12 insulator type mounted on MS channel operating rod with pad lock arrangement including dismantling old one, complete all as specified and directed. |
| 18 | S&F in replacement lightning arrestor, gapless metal oxide type complete with all fittings, suitable for a system voltage of 11 KV and of class 10 KA, complete all as specified and directed. |
| 19 | Notes :-An amount of Rs. 10,115.00 on account of Credit Schedule for Schedule \"A\" Part-II shall be deducted from total quoted amount of BOQ to arrive at the contract sum. |