| 1 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. a) Group C |
| 2 | Wiring for light/Power plugwith 2*4sq mm FRLS PVC insulated copper conductorsingle core cable in surface / recessed steel conduit alongwith 1 No. 4sq mm FRLS PVC insulated copper conductor single core cable for loop earthingas required. |
| 3 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.a) Group C |
| 4 | wiring forcircuit/sub main wiring along with earth wirewith the following sizes of FRLS PVC insulated copper conductor,single core cable in surface / recessed steel conduit as required. |
| 5 | 2x 10sq mm + 1x6 sq mm earth wire |
| 6 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 7 | 20 mm |
| 8 | 25 mm |
| 9 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 10 | 3 x 1.5 sq. mm |
| 11 | 3 x 4 sq. mm |
| 12 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 13 | 5/6 amps switch |
| 14 | 15/16 A switch |
| 15 | 3 pin 5/6 A socket outlet |
| 16 | 6 pin 15/16 A socket outlet |
| 17 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. |
| 18 | 180 mm X 100 mm X 60 mm deep |
| 19 | 200 mm X 150 mm X 60 mm deep |
| 20 | 200 mm X 250 mm X 60 mm deep |
| 21 | 200 mm X 125 mm X 60 mm deep |
| 22 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 23 | 12 way , Double door |
| 24 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 25 | Single pole |
| 26 | Double pole |
| 27 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc with charcoal/ coke and salt as required. |
| 28 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub main wiring/cable as required. |
| 29 | Supply & fixing of following wattage 6500 K LED battenwith rated input voltage 140-270 V AC supply, in built surge protection of 2.5 kv, CRI>80, driver efficiency >85%, THD <20% Efficacy not less than 100 lumen/watt i/c all required accessories as complete |
| 30 | 24 Watt made of aluminium body |
| 31 | 24 Watt made of aluminium body and replacing it at the place of old existing CFL tube light i/c rebate for dismantled material, testing commissioning etc complete as required. |
| 32 | Supplying and fixing PVC batten/ angle holder including connections etc. as required. |
| 33 | Supply and fixing of B22 base 10 watt minimum 3 star LED Lamp having Luminous Efficacy =95 lm/W as per BEE guidelines, 6500/3000 K, rated input voltage 240 V AC supply, in built surge protection, power factor greater than 0.9, i/c all required accessories testing commissioning etc complete as required. |
| 34 | Supply ofenergy efficient Metallic body exhaust fan of 300 mm sweep with minimum air delivery of minimum 1000 cubic meter per hour at rated RPM to operate on single phase 230 volt, 50 HZ AC Supply with 3Nos. Aerodynamically designed & Balanced Blade/impeller, copper windingwith bird guard to protect the fan in running condition, arm-set, frame and all required accessories, Installing the exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 35 | Supply of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 36 | Installation, Testing and Commissioning |
| 37 | Installation, Testing, Commissioning and replacing at the place of old existing fans i/c dismantling and rebate for dismantle material |
| 38 | Supply and fixing of 100 Wattenergy efficient LED flood light made with aluminium housing with inbuilt SPD, Lens & toughened glass, IP-66 protection, integrated electronic driver with rated input voltage 140-270 V AC supply, Lumen outputnot less than 5000 Lm, system efficacy not less than 100 Lumen/watt, Color temperature (CCT)-5700K-6500 K, CRI>80, Monting clip i/c all required accessories, making connection, testing etc complete as required. |
| 39 | Supplying of 3 x 4 sq mmsizes ofXLPE insulated PVC sheathed Aluminium conductor armoured power cable of1.1 KV grade confirming to IS:7098 (Part 1) and laying on wall surface (clamped with 1mm thick saddle)/recessed conduit including making connection with suitable size of aluminumlugs, testing etc. as required and as per technical specification enclosed. |