| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 06-01-2024 | CWE/HSR-42 OF 2023-24 PERIOD OF COMPLETION | Other | 13-01-2024 |
| Sl. No. | Item Description |
| 1 | Excavation in trenches in soft/loose soil not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cable etc. and for foundation of poles, stays etc. n exc 10 sqm on plan and n exc 1.5 in depth and getting out complete all as specified. |
| 2 | Description all as per Serial item No 1 above but Add to item 1 for each additional 1.5m or part thereof in depth beyond the first 1.5 mtr complete all as specified and directed. |
| 3 | Returning filling with earth obtained from excavation including spreading, watering & consolidation in layers not exceeding 15 cms thick, complete all as specified and directed. |
| 4 | Removing surplus soil to a distance not exceeding 50 m & depositing at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 5 | Material & labourfor Sand filling in trenches with clean dry fine sand unwashed including gently punning around cables complete all as specified and directed. |
| 6 | Material & labour for brickscovering to under ground electric cable usingsub class \"B\" bricks laid dry, flat, perpendicular to the direction of the cable complete all as specified and directed. |
| 7 | Dismantling of old broken PCC pole of any size including foundation and removing the same from site complete all as directed by Engineer-in-charge. |
| 8 | Supply errecting & fixing in true vertical position pre-stressed concretepoles 11 metre long, 152 mm x 152 mm at top and 152 mm x 260 mm at bottom, class-9 complying with requirements of IS-1678-1978 including necessary painting complete all as specified.(Note : Earth work & PCC shall be measured and paid separately) |
| 9 | Supply errecting & fixing in true vertical position pre stressed concrete pole conforming to IS-1678 of 9 mtr long,102 mm x 172 mm at top and 102 mm x 279 mm at bottom,class 10 complete as specified & directed (Note : Earth work & PCC shall be measured and paid separately) |
| 10 | Material & labour for PCC 1:3:6 type C-1 using 40 mm graded stone aggregate . in mass concrete and filling completefor foundation of Panel & Transformer yeard, pole/stay/ of poleall as specified & directed by Enge-in- Charge |
| 11 | Material & labour for PCC 1:2:4 type B-1 using 20 mm gradedstone aggregate incoping for replacement of new pole and breaking old existing copingand like includingweather slightly rounded or chamfered angles and throatyand necessary formwork completefor pole ,all as specified and directed . |
| 12 | Taking down unserviceable/old ACSR conductor any size from over head lines, poles by removing binding wire, service wire, cables and removal from site complete all as specified and directed. |
| 13 | Supply and Stretching in replacement Aluminium conductor steel reinforced (ACSR) of any size for HT/LT OH lines on poles including stringing ,binding with aluminium wire 14 SWG or aluminium tape incljumpers complete connecting of disconnected cable, service cable and street light connection complete all as specified anddirected. |
| 14 | Dismantling unserviceable galvanized earth steel wire of any size and existing hexagonal cradle guard HT/LT poles and removingbinding wire and removal of the same from sitecomplete all as specified and directed. |
| 15 | Supply and Stretching in replacement 4mm dia GI earth wire/guard cradles on existing LT poles binding with and including GI binding wire 1.63 mm complete all as specified and as directed. |
| 16 | Dismantling unserviceable stay assemblycomplete and removing from site |
| 17 | Supply and fixing in replacement stay assembly comprising of GI stay bow 14 mm dia, 40 cm long complete with accessories as shown in Electrical plate No. 1 of SSR Part – I using galvanised stay rod 20mmdia, 215 cm long with threaded ends GI nuts, bolts, washers, stay plate 30 cm x 30 cm x 6 mm thick2 Nos of thimbles, MS clamps made out of 50x6mm flat iron, loop stay insulator, stay wire 7/8 SWG complete including painting all exposed surfaces of MS work shall be given two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed by Engineer-in-charge.Note :- PCC and earth work shall be measured andpaid for separately under the respective item of schedule) |
| 18 | Dismantling insulator any type/ any size from LT/HT poles complete all as directed. |
| 19 | Supply and fixing in replacement of insulators pin type porcelain, vitreous ,white or brown or green insulator of size 50 mm height, 65 mm dia suitable for 1100 V grade including one galvanized mild steel spindle, two GI washers and one nut including removing the existing unserviceable one complete all as specified and directed. |
| 20 | Supply and fixing in replacement of shackle type ,procelain, vitreous, white,brown, or green insulator of size 75mm height and 90mm dia suitable for 1100V, including Galvanised MS straps,washers, insulator bolts,washers and nuts complete,all as specified and as directed. |
| 21 | Material & labour in replacement of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled Red, with letters, figures, and coventional skull and bones, in signal white colour and fixed with MS CLAMPS, bolts, and nuts of approved size, forLT 20 X 15 Cm size complete all as specified and directed. |
| 22 | Dismantling unserviceable cross arms, clamps etc and removing from site |
| 23 | Material & labourin replacement of CrossArms bracings supports, channels, clamps, anti climbing device, eye hook and back plates fabricated from structural steel sections including pole clamps stay clamps, D clamps nuts, bolts , washers,welding, bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat ofaluminiumpaint complete all as specified and directed. |
| 24 | Re-stringing/stretchingincl jointing in situ of different sizes of ACSR conductors or GI earth continuity conductors with/ withoutguarding wires on HT/ LT electric poles at different locations all as ordered manually or by mechanical means to the extent of permissible sag or tension by removing jumpers or bindings from insulators and making fresh binding with aluminium binding wire or aluminium tapes after stringing complete all as specified and directed.Note :- (a) Stretching of 4 conductor will be considered as onespan length for measurement purpose.(b) Qty of GI earth wire or ACSR conductor reqd to be replaced or extended during stringing operation shall be measured and paid separately. |
| 25 | All as per item No-24 above but 5 conductor complete all as specified and directed. |
| 26 | All as per item No-24 above but (1or 2,3) conductor complete all as specified and directed. |
| 27 | Cutting/trimming the branches of trees if any along HT/LT overhead line, 1.5 mtr on all side below/above/sides of HT/LT overhead line and removing the same upto 150 mtr away each span not exceeding 40 mtr complete all as specified and directed by Engineer-in-Charge (The above is to be ensured for the entire contract period by cutting/trimming of trees any number of times as required). |
| 28 | Taking down unserviceable/oldLT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable of any size and removal from site complete all as specified and directed. |
| 29 | Relaying of old serviceable LT/HT under groundPVC/XLPE cable any grade and any size in trenches/fixed to wall/pole/roof/laid in floor including necessary connections and thimbling complete all as specified and as directed by Engineer-in-charge. (Earth work, brick & sand cushioning shall be measured and paid for separately under appropriate item). |
| 30 | Supplying laying, jointing, testing and commissioning of LT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 volts grade complete of the following sizes all as specified and directed.(Note :- cable may be laid in trenches, under road, across the nallah, along poles/walls and in ducts etc.Execavation, earhtwork, sand cushioing, cable cover, pipe for cable protection to be measured and paid for separtely) complete all as specified and directed.120 Sqmm 3.5 core |
| 31 | Supplying laying, jointing, testing and commissioning of LT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 volts grade complete of the following sizes all as specified and directed.(Note :- cable may be laid in trenches, under road, across the nallah, along poles/walls and in ducts etc.Execavation, earhtwork, sand cushioing, cable cover, pipe for cable protection to be measured and paid for separtely) complete all as specified and directed.95 Sqmm 3.5 core |
| 32 | Supplying laying, jointing, testing and commissioning of LT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 volts grade complete of the following sizes all as specified and directed.(Note :- cable may be laid in trenches, under road, across the nallah, along poles/walls and in ducts etc.Execavation, earhtwork, sand cushioing, cable cover, pipe for cable protection to be measured and paid for separtely) complete all as specified and directed.70 Sqmm 3.5 core |
| 33 | Supplying laying, jointing, testing and commissioning of LT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 volts grade complete of the following sizes all as specified and directed.(Note :- cable may be laid in trenches, under road, across the nallah, along poles/walls and in ducts etc.Execavation, earhtwork, sand cushioing, cable cover, pipe for cable protection to be measured and paid for separtely) complete all as specified and directed.50 Sqmm 3.5 core |
| 34 | Supplying laying, jointing, testing and commissioning of LT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 volts grade complete of the following sizes all as specified and directed.(Note :- cable may be laid in trenches, under road, across the nallah, along poles/walls and in ducts etc.Execavation, earhtwork, sand cushioing, cable cover, pipe for cable protection to be measured and paid for separtely) complete all as specified and directed.35 Sqmm 3.5 core |
| 35 | Supplying laying, jointing, testing and commissioning of LT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 volts grade complete of the following sizes all as specified and directed.(Note :- cable may be laid in trenches, under road, across the nallah, along poles/walls and in ducts etc.Execavation, earhtwork, sand cushioing, cable cover, pipe for cable protection to be measured and paid for separtely) complete all as specified and directed.25 Sqmm 3.5 core |
| 36 | Supplying laying, jointing, testing and commissioning of LT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 volts grade complete of the following sizes all as specified and directed.(Note :- cable may be laid in trenches, under road, across the nallah, along poles/walls and in ducts etc.Execavation, earhtwork, sand cushioing, cable cover, pipe for cable protection to be measured and paid for separtely) complete all as specified and directed.16 Sqmm 4 core |
| 37 | Material and labour for earthing complete with galvanized steel earth plate electrodesize 600x600x6.3 mm thick buried directly in groundvertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized iron strip 32 x 6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized including GI protection pipe light grade 40 mm dia connected to main earth lead on pole or control board and GI pipe light grade 20 mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion. |
| 38 | All as peritem 37 here-in- before but GI wire 4 mm as earthing lead |
| 39 | M & L for replacement for PVC separator in position to keep ACSR conductor on equal spacing all as specified & directed.(a) 2 Wire |
| 40 | M & L for replacement for PVC separator in position to keep ACSR conductor on equal spacing all as specified & directed.(b) 3 wire |
| 41 | M & L for replacement for PVC separator in position to keep ACSR conductor on equal spacing all as specified & directed.(c) 4 wire |
| 42 | M & L for replacement for PVC separator in position to keep ACSR conductor on equal spacing all as specified & directed.(d) 5 Wire |
| 43 | Supply and fixing installation, commissioning and testing in replacement of MCCB 400 Amps fixed on existing panel 415 volt, 4 pole, 36 KA breaking capacity with adjustable current range for overload protection and thermal releaseincluding taking down of MCCB complete with spreader terminals all as specified & directed. |
| 44 | All as peritem 43 here-in- before but 200 Amps, 4 pole 25 KA complete all as specified and directed. |
| 45 | All as peritem 43 here-in- before but 160 Amps, 4 pole 25 KA complete all as specified and directed. |
| 46 | All as peritem 43 here-in- before but 125 Amps ,4 pole,415 volts 25KA breaking capacity complete all as specified and directed.. |
| 47 | All as peritem 43 here-in- before but 100 Amps ,4 pole,415 volts 25KA breaking capacity complete all as specified and directed.. |
| 48 | All as peritem 43 here-in- before but 63 Amps ,4 pole,415 volts 16KA breaking capacity complete all as specified and directed.. |
| 49 | Material & Labour for replacement of GI strip 32 mm x 6 mm from test point upto equipment to be earthed with connecting material like nut bolts etc complete all as specified and directed. |
| 50 | Material & labour for replacement of 80 mm bore GI pipe light grade laid in trenches or fixed to wall/pole for protection of cable/earthing strip etc complete all as specified and directed. |
| 51 | Material & labour for replacement of 50 mm bore GI pipe light grade laid in trenches or fixed to wall/pole for protection of cable/earthing strip etc complete all as specified and directed. |
| 52 | Material and labour for making the hole under road and hard standing suitable for laying and inserting pipe upto 100 mm dia any length by trenchless technology, mechanical drill system or Auger system and making the surface good as existing surface.complete all as specified and as directed by Engineer-in-charge. |
| 53 | Surface Dressing/Cutting of grass,bushes,shrubs and wilds n exc.15 cm deep and removing the same from the site to clear the area of dressing complete all as specified and directed. (The above is to be ensured for the entire contract period for any number of times as required). |
| 54 | Material & Labour Painting to LTPCC poles with fluorescent Black and White synthetic enamel paint at a distance of 30 cm wide complete all as specified and directed. |
| 55 | Supply and laying or fixing or passing through pipe,1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape,overall PVC sheathed 6 sqmm 2 core nominal cross sectioncomplete all as specified and directed |
| 56 | All as peritem 55 here-in- before but size of 10 sqmm 2 core |
| 57 | Supply, fabricating, installation, testing , commissioning and electrically connecting in replacement ofLTpanel of size 100 x 80 x 50 cm, 415 volts factory made dust and vermin proof for out door type made out of CRCA sheet 3.15 mm thick powder coated machine pressed both side opening in two halves with rubber beading including aluminium bus bar of 400 amps capacity 4 strip mounted on porcelain insulator.Bus bar chamber shall be provided with inspection covers , each ACB/MCCB /cubical switch shall have be independent opening. Panel shall be mounted on angle iron frame and legs made from angle of size 40x40x5mm frame including lifting arrangement and legs, duly spray painted internally and externally with two coats of synthetic enamel paint after a coat of red oxide primer grouted in PCC 1:3:6 type B:2 ( 40 mm graded stone aggregate ) foundation with required earth work complete including all connections for incoming / outgoing ACB/MCCBs, cable gland suitable for incoming/outgoing cable and control wiringwith suitable size of copper conductor cable comprising of following accessories including testing complete all as specified and directed by Engineer-in-charge.(i) MCCB 250 Amps, 36 KA, 4 Pole,Ics = 100% Icu with adjustable thermal and fixed magnetic release (Incoming) =01 No(ii) --do-- but MCCB 100 Amp, 25 KA,4 Pole,Ics = 100% Icu (outgoing) =03 No . (iii) Indicator lamp RYB = 01 set.(iv) Digital Ammeter 0-400 A with selector switch & CTs of suitable capacity - 01 set.(v)Digital volt meter 0-500 V with selector switch - 01 No. |
| 58 | Material and labour for replacement of indicator lamp in differenet colour code LED/Neon type (as per sample) complete (RYB) including wiring with copper conductor cable of suitable size all as specified and as directed by Engineer-in-Charge. |
| 59 | Material & labour for cleaning, rubbing by amren paper and other foreign materials external surface of feeder pillarbox/LT panelsand preparing the surface for paint, spraying by gun one coat of synthetic enamel paint of existing colour of panel on Internal and External surface, including minor repairing of panels like door hinges with welding/nuts bolts etc complete all as specified and directed . |
| 60 | Repair to LT panel board body by replacing MS sheet of existing gauge size and shape for door shutter/body of feeder piller, including replacement of broken hinges and all as specified and as directed by Engineer in Charge. |
| 61 | Supply and fix LT Cable End Joint Kit 25 to 50 Sqmm all as specify and directed |
| 62 | Supply and fix LT Cable End Joint Kit 70 to 95 Sqmm all as specify and directed |
| 63 | Supply and fix LT Cable End Joint Kit 120 to 150 Sqmm all as specify and directed |
| 64 | Dismantling of air break gang operated switches/ DO assembly vertical/horizontal mounted including insulators and operating mechanism and removing the same from site and carrying to MES store complete all as specified and directed. |
| 65 | Supplyinstallation, connecting and testing in replacement of gang operated air break switch, mounted on insulators HT 11KV ,200 Amps rating , triple pole,twelve insulator suitable for horizontalmounting fixed and spring loaded revolving tinned brass/copper copper contacts, galvanized steel base frame, 32 mm boremed grade pipe Galvanizedoperating rod(Medium Grade), operating handle, locking arrangement completeincluding taking down the existing gang operated air break switch complete all as specified and directed.(i) Cross arms of 2 pole/4 pole structure reqd for installation of GO switch,if reqd additional, shall be measured and paid seperately.(ii)Scope of wk shallinclude ACSR conductors PVC sleeves, PG clamps and thimbles reqd for jumpers/connections to OH lines of 2 poles/ 4 poles structures and outgoings feeders. |
| 66 | S & F in replacement lightening arrester metal oxide non-linear expulsion type rupturing capacity 65 KA, porcelain, conforming to IS-3070 Pt-I suitable for 11 KV, HT over head line complete including nuts, bolts, clamps, brackets etc and connecting with GI earth wire, discharge capacity 65 Kilo Amps. |
| 67 | Supply and installation replacement of drop out fuse assembly 11KV,25 Amps rating complete expulsion fuse element mounted on four/two pole structures all as specified and directed. |
| 68 | Repairs to existing two/ three/Four pole gang operated air break switchhorizontal/verticalthrow incl taking down old unsv male/female contact set and providing in replacement new male female contact set copper,spring loaded suitable for 200 Amps complete with jumpers from GOD to OH line & DO to GOD complete with thimbles incl HT tape reqd for repairing HT end termination joint icluding reuired GI pipe rod nd handle complete all as specified and directed. |
| 69 | Supply and fixing in replacement of insulators pin type porcelain, vitreous ,white or brown or green insulator of size 150 mm height, 150 mm dia suitable for 11 kV grade including one galvanized mild steel spindle, two GI washers and one nut including removing the existing unserviceable one complete all as specified and directed. |
| 70 | Supply and fixingin replacement of single Disc insulator assembly for tension with tension clamps for conductors, porcelain, vitreous 145 mm high and 255 mm dia ball and socket type, white, brown or green with tension clamps for conductors, working pressure 11 kV for disc assembly complete,all as specified and as directed. |
| 71 | Supplying laying, jointing, testing and commissioning in replacement of XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 11000 volts grade, cross sectional area 95 Sqmm 3 core suitable for 11 KV earthed systems complete all as specified and directed by Engr -in-Charge.(Note :- cable may be laid in trenches, under road, across the nallah, along poles/walls and in ducts etc . Excavation, earhtwork, sand cushioing, cable cover, pipeforcable protection to be measured and paidsepartely) . |
| 72 | Material & labour for cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination Cold shrinkable type joint complete with jointing material and accessories suitablae for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 Sqmm complete all as specified and directed. |
| 73 | Material & labour in replacement of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled Red, with letters, figures, and coventional skull and bones, in signal white colour and fixed with MS CLAMPS, bolts, and nuts of approved size, forHT 25 X 20 Cm size complete all as specified and directed. |
| 74 | Material & Labour Painting to HTPCC polewith fluorescent post office red and black synthetic enamel paint at a distance of 30 cm widecomplete all as specified and directed. |
| 75 | All as peritem 74 here-in- before but on PCC 2 pole structurespainting of bracings. |
| 76 | All as peritem 74 here-in- before but on PCC 4 pole structurespainting of bracings. |
| 77 | All as peritem 74 here-in- before but on 11 KV 2 pole structures including painting of iron angle structures and bracings. |
| 78 | Servicing of 11 KV VCB,current rating - 100 Amp/ 60 Amp, Type -UNIVAC, cleaning of all carbon particles, dust etc complete and cleaning of all parts, adjusting contacts, springs, locking arrangements, tripping coil circuits (closed/ open) using CRC spray for elect contact cleaning etc cleaning of CT and PT supporting insulators, bush trolley auxiliary contact, male female contact and check all wiring including minor item required for repair complete all as specified and directed. Note:-1.This item quoted rate not include testing and adjusting the following relay including checking and rectifying the tripping circuit complete. |
| 79 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.S&F in replacement of battery bank 2 volt 100/110 volt for vcb |
| 80 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.Isolating Contact two Pair |
| 81 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.Vaccume Interrupter |
| 82 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.Shutter for racking shuft |
| 83 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.Closing Coil 24V/110V AC/DC |
| 84 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.Shunt trip coil 24V/110V AC/DC |
| 85 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.Rached wheel |
| 86 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.Motor Cut off Switch |
| 87 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.LED indication Lamp |
| 88 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.Spring Motor with gear box |
| 89 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.Auxillery Contact Male & female |
| 90 | Supply only following spares parts of HT VCB against items No.78 all as specified and directed by Engr-in-Charge.TNC Switch |
| 91 | M & L for testing and adjusting the following relay including checking and rectifying the tripping circuit complete, Calibration of relay for 11 KV VCB incoming/ Outgoing panel. (a)Trip circuit suervision Relay, Make - AREVA – 01 No(b) Master TripRelay, 24 DC Make - AREVA- 01 No(c) Instantaneous earth fault relay,Make-L&T – 01 No(d) Intelligent Panel Meter, Make-L&T– 01 No(e) Ammeter & VoltmeterNote: - (I) The tripping system of relays are to be calibrated with 33Kv receiving station EBS Hisar and test result in this effect to be submitted to Engr-in- Charge(II) The tripping timing of the relay to be adjusted less than 33KV system at EBS Hisar (III) The testing instrument whatever required to test the relays will be arranged by the contractor at his own cost(IV) The test shall be provided fromauthorized agency. |
| 92 | Isolating 11 KV HT over head supply from the substation,2pole /4 pole structureand earth the complete system properly,disconnecting complete electric system of the transformer from HT and LT side including earthing strips, removing transformer and taking out from plinth , 2pole /4 pole structure and shifting to another plinth and re-connect to LT and HT side and earth connection including installing , commissioning & testing of capacity 200 kva |
| 93 | Isolating 11 KV HT over head supply from the substation,2pole /4 pole structureand earth the complete system properly,disconnecting complete electric system of the transformer from HT and LT side including earthing strips, removing transformer and taking out from substation , 2pole /4 pole structure and transporting to authorized service centre/ work shop for repair and back to the installation after repair including installing , commissioning & testing of the following capacity:NOTE:-The above quoted rates include labour charges for replacing Spares/ parts as required whichshall be measured and paid separately as supply only in relevant items .(a)Upto63 KVA |
| 94 | Isolating 11 KV HT over head supply from the substation,2pole /4 pole structureand earth the complete system properly,disconnecting complete electric system of the transformer from HT and LT side including earthing strips, removing transformer and taking out from substation , 2pole /4 pole structure and transporting to authorized service centre/ work shop for repair and back to the installation after repair including installing , commissioning & testing of the following capacity:NOTE:-The above quoted rates include labour charges for replacing Spares/ parts as required whichshall be measured and paid separately as supply only in relevant items .(b)100 KVA to 200 KVA |
| 95 | Draining out the complete transformer oil and keeping in safe custody in clean and dry containers for reuse. Opening the top cover of the transformer ,disconnecting and taking out complete core assy and dismantling it for checking the serviceability of the coil winding, checking the condition of the body, cleaning the tank and remove sludge/dirt, cleaning the coils limbs, re-fixing of core, core assy , tap changer assembly ,HT/LT Rewinding and connection , terminal studs of HT/LT sides and reassembling of transformer after repairs, refitting the transformer coil including improvement of Insulation Resistancevalue within desired level by heating or any other method to required level complete all as directed to the entire satisfaction of Engr-in-Charge:-(a)Upto63 KVANOTE:-The above quoted rates include labour charges for replacing Spares/ parts as required whichshall be measured and paid separately as supply only in relevant items . |
| 96 | Draining out the complete transformer oil and keeping in safe custody in clean and dry containers for reuse. Opening the top cover of the transformer ,disconnecting and taking out complete core assy and dismantling it for checking the serviceability of the coil winding, checking the condition of the body, cleaning the tank and remove sludge/dirt, cleaning the coils limbs, re-fixing of core, core assy , tap changer assembly ,HT/LT Rewinding and connection , terminal studs of HT/LT sides and reassembling of transformer after repairs, refitting the transformer coil including improvement of Insulation Resistancevalue within desired level by heating or any other method to required level complete all as directed to the entire satisfaction of Engr-in-Charge:-(b)100 KVA to 200 KVANOTE:-The above quoted rates include labour charges for replacing Spares/ parts as required whichshall be measured and paid separately as supply only in relevant items . |
| 97 | Material only for primary (HV side) double paper cover aluminium winded coils of existing type size and gauge and in weight complete with including11000 volt grade insulating material for transformer of 50 KVA to 160 KVA |
| 98 | All as peritem 97 here-in- before but LV size 415 voltage graded. |
| 99 | Material only for (HV side) copper winded coil of existing type size and gauge 11000 voltage complete with insulating material for transformers 50 KVA to 160 KVA . |
| 100 | All as peritem 41 here-in- before but LV side, 415 voltage rade.Note for 97-100: Actual weight of the each coil shall be measured and paid in the relevant items(ii) Labour Charges for rewinding of coiland fitting of formed coil included in the quoted rate). |
| 101 | Supplyand fixing in replacement of cork sheet gasket of 06 mm thick for transformer tank complete all as specified and directed. |
| 102 | Supply and fixing in replacement , HV bushing (11000 voltage graded) with heat resistance gasket suitable for following capacity of outdoor/ indoor type transformer:- (a)Up to 63 KVA |
| 103 | Supply and fixing in replacement , HV bushing (11000 voltage graded) with heat resistance gasket suitable for following capacity of outdoor/ indoor type transformer:-(b) 100 KVA to 200 KVA |
| 104 | Supply and fixing in replacement of copper terminal stud, both end threaded complete with double nuts & washers including distance piece both sides and heat resistance gasket suitable for HV size 11000 volts grade for following capacity of outdoor / indoor type transformer.(a)Up to 63 KVA |
| 105 | Supply and fixing in replacement of copper terminal stud, both end threaded complete with double nuts & washers including distance piece both sides and heat resistance gasket suitable for HV size 11000 volts grade for following capacity of outdoor / indoor type transformer.(b) 100 KVA to 200 KVA |
| 106 | Supplyand fixing in replacement of LV bushing (415 voltage grade) with heat resistance gasket suitable for following cap ofoutdoor/indoor type transformer:-(a)up to 63 KVA |
| 107 | Supplyand fixing in replacement of LV bushing (415 voltage grade) with heat resistance gasket suitable for following cap ofoutdoor/indoor type transformer:-(b) 100 KVA to 200 KVA |
| 108 | Supply and fixing in replacement of copper terminal stud, both end threaded complete with double nuts & washers including distance piece both sides and heat resistance gasket suitable for LV size 415 volts grade for following capacity of outdoor / indoor type transformer.(a)up to 63 KVA |
| 109 | Supply and fixing in replacement of copper terminal stud, both end threaded complete with double nuts & washers including distance piece both sides and heat resistance gasket suitable for LV size 415 volts grade for following capacity of outdoor / indoor type transformer.(b) 100 KVA to 200 KVA |
| 110 | Material and labour for replacement of breather assembly filled with silica gel complete for transformer of capacity up to 200 KVA. |
| 111 | Supply & pouring of fresh transformer oil in transformers for topping up the level or replacement complete all as directed by Engineer-in-Charge.(Transformer oil shall confirm to relevant IS -335 and dielectric strength of 45 KV and getting it tested before and after filling complete all as directed and specified. |
| 112 | Material & labour for cleaning sprinkled transformer oil and all other foreign materials from external surface of transformer of capacity up to 63 KVA and preparing the surface to receive paint, and applying one coat of synthetic enamel paint, including writing SM No/MES No with paint on black base complete all as directed and specified. |
| 113 | All as peritem 112 here-in- before but for 100 KVA to 200 KVA. |
| 114 | M & L for Opening / disconnecting the electrical connection of defective / burnt out LT/HT cable of any size 3 to 4 core from Transformer, LT Panel, DBs and any other connection, cutting the defective portion of cable, providing required size of thimbles/connectors at cable end and reconnecting the cable in previous location all as specified and directed by Engr-in-Charge. |
| 115 | Material & labour for dehydration and filtration of transformer oil of existing transformer of cap up to 200 KVA , 11/0.433 KV to obtain dielectric strength more than 40 KV at 2.5 mm gap including, testing complete all as specified and directed.. Note - Contractor has to bring Centrifusing machine at site for dehydration. |
| 116 | Supply and fixing in replacement silica gelCrystals complete all as specified and directed. |
| 117 | Isolating 11 KV HT over head supply from the distribution transformer mounted on platform/ 2 or 4 pole structureand earth the complete system properly,disconnecting all complete electric connection of the transformer from both HT/LT side including earthing strips, opening of transformer head and replacing cork sheet/gasket for stopping oil leakage from bushing/body including refixing all the accessories and making good to the entire satisfaction of EIC complete all as specified and directed.Note The rate of hydra crane are included in the quoted rate. |
| 118 | Shifting of trolly mounted transformer from sub stn to required location & connecting the LT and HT connection and all earthing connection and testing to restoring the supply during the period of repair of existing transformer in workshop and disconnecting and reshifting the transformer in the sub stn after the repaired transformer shifted in the existing location complete all specified and directed. Note The rate of hydra crane are included in the quoted rate. |
| 119 | Suplying and laying of gravels of size 25 mm to 40 mm for all electrical sub station, transformer and panel plateform and making even surface complete all as specified and directed. |