| 1 | Supply, layand testing cable LT XLPE insulated screened PVC bedded, galvnized steel strip or wire armoured , electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts (earth) grade, ofsize 240 sq mm 3.5 core complete all as specified and as directed. |
| 2 | Supply, layand testing cable LT XLPE insulated screened PVC bedded, galvnized steel strip or wire armoured , electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts (earth) grade, ofsize 185 sq mm 3.5 core complete all as specified and as directed. |
| 3 | Supply, layand testing cable LT XLPE insulated screened PVC bedded, galvnized steel strip or wire armoured , electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts (earth) grade, ofsize 120 sq mm 3.5 core complete all as specified and as directed. |
| 4 | Supply, layand testing cable LT XLPE insulated screened PVC bedded, galvnized steel strip or wire armoured , electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts (earth) grade, ofsize 70 sq mm 3.5 core complete all as specified and as directed. |
| 5 | Supply, layand testing cable LT XLPE insulated screened PVC bedded, galvnized steel strip or wire armoured , electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts (earth) grade, ofsize 50 sq mm 3.5 core complete all as specified and as directed. |
| 6 | Supply, layand testing cable LT XLPE insulated screened PVC bedded, galvnized steel strip or wire armoured , electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts (earth) grade, ofsize 35 sq mm 3.5 core complete all as specified and as directed. |
| 7 | Supply, layand testing cable LT XLPE insulated screened PVC bedded, galvnized steel strip or wire armoured , electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts (earth) grade, ofsize 10 sq mm 4 core complete all as specified and as directed. |
| 8 | Excavating in trenches in soft / loose soil not exc 1.5 m wide and not exc 1.5 m in depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc n exc 10 sqm on plan and n.exc 1.5 m in depth and getting out as I soft/ loose soil complete all as specified and as directed |
| 9 | Returning filling in, including spreading levelling, watering and well ramming in layers notexc 25 cm complete all as specified and as directed |
| 10 | Removing excavted material n exc 50 m and depositing where directed ata level notexc 1.5 m above the staring point assoil complete all as specified and as directed. |
| 11 | M&L for Sand cushioning (dry sand) to under ground cable for cable protection in layers of 23cm thick( 8 cm thick before laying of cable and 15cm thick after laying of cable) in trenches complete all as specified and as directed. Note :- Only puned layers shall be measured. |
| 12 | Supply and laying unreinforced pre cast concrete cable cover class LV type 1 flat size 250 mm x 150 mm x 40 mm for cable protection complete all as specified and as directed. |
| 13 | S & F 100 mm dia Galvanised steel tubing light grade with all necessary fittings laid in trenches, fixed to walls, poles, under road / floor etc for cable protection, complete all as specified and as directed. |
| 14 | S & F 80 mm dia Galvanised steel tubing light grade with all necessary fittings laid in trenches, fixed to walls, poles, under road / floor etc for cable protection, complete all as specified and as directed. |
| 15 | S & F 50 mm dia Galvanised steel tubing light grade with all necessary fittings laid in trenches, fixed to walls, poles, under road / floor etc for cable protection, complete all as specified and as directed. |
| 16 | Supply,installing, testingand commissioningout door type LT Panel of suitable size, pedastal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, framing with 50 x50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and paintedto both internal and External surfaces with powder coating paint in heatprocess of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and includingfollowing accessories and mounted on PCC Plat form made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (Main Panel A Hawk Area)(i) Busbar :- 600 Amps rated Copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulatorbus bar support (Square/round ) insulators of suitable size and good insulation resistance(ii)MCCB 4 Pole, 415 Volts,400 Amps adjustable type, 36 KA- 01 No (incoming)(ii)MCCB 4 Pole, 415 Volts,250 Amps adjustable type, 36 KA- 01 No (outgoing)(iii)MCCB 4 Pole, 415 Volts,200 Amps adjustable type, 36 KA- 01 No (outgoing)(iv)Suitable Capacity of CTs-01 Set(v) Indicator lamp LED type (R-Y-B) - 01 set of three (vi) 3 phase volt meter (0-500V) digital type with selector switch - 01 No (vii) Ammeter digital type (0-500A) - 01 No with selector switch - 01 No |
| 17 | Supply,installing, testingand commissioningout door type LT Panel of suitable size, pedastal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, framing with 50 x50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and paintedto both internal and External surfaces with powder coating paint in heatprocess of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and includingfollowing accessories and mounted on PCC Plat form made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (Main Panel B Hawk Area)(i) Busbar :- 800 Amps rated Copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulatorbus bar support (Square/round ) insulators of suitable size and good insulation resistance(ii)MCCB 4 Pole, 415 Volts,630 Amps adjustable type, 50 KA- 01 No (incoming)(iii)MCCB 4 Pole, 415 Volts,250 Amps adjustable type, 36 KA- 03 Nos (outgoing)(iv) Suitable Capacity of CTs-01 Set(v) Indicator lamp LED type (R-Y-B) - 01 set of three (vi) 3 phase volt meter (0-500V) digital type with selector switch - 01 No (vii) Ammeter digital type (0-800A) - 01 No with selector switch - 01 No |
| 18 | Supply,installing, testingand commissioningout door type LT Panel of suitable size, pedastal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, framing with 50 x50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and paintedto both internal and External surfaces with powder coating paint in heatprocess of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and includingfollowing accessories and mounted on PCC Plat form made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (Sub Panel a,b,c,d & e Hawk Area)(i) Busbar :- 300 Amps rated Copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulatorbus bar support (Square/round ) insulators of suitable size and good insulation resistance(ii)MCCB 4 Pole, 415 Volts,250 Amps adjustable type, 36 KA- 01 No (incoming)(iii)MCCB 4 Pole, 415 Volts,40 Amps adjustable type, 16 KA- 06 Nos (outgoing)(iv) Suitable Capacity of CTs-01 Set(v) Indicator lamp LED type (R-Y-B) - 01 set of three (vi) 3 phase volt meter (0-500V) digital type with selector switch - 01 No (vii) Ammeter digital type (0-500A) - 01 No with selector switch - 01 No |
| 19 | Supply,installing, testingand commissioningout door type LT Panel of suitable size, pedastal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, framing with 50 x50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and paintedto both internal and External surfaces with powder coating paint in heatprocess of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and includingfollowing accessories and mounted on PCC Plat form made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (Main Panel A Offr Area)(i) Busbar :- 600 Amps rated Copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulatorbus bar support (Square/round ) insulators of suitable size and good insulation resistance(ii)MCCB 4 Pole, 415 Volts,500 Amps adjustable type, 36 KA- 01 No (incoming)(iii)MCCB 4 Pole, 415 Volts,160 Amps adjustable type, 36 KA- 03 Nos (outgoing)(iv) Suitable Capacity of CTs-01 Set(v) Indicator lamp LED type (R-Y-B) - 01 set of three (vi) 3 phase volt meter (0-500V) digital type with selector switch - 01 No (vii) Ammeter digital type (0-500A) - 01 No with selector switch - 01 No |
| 20 | Supply,installing, testingand commissioningout door type LT Panel of suitable size, pedastal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, framing with 50 x50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and paintedto both internal and External surfaces with powder coating paint in heatprocess of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and includingfollowing accessories and mounted on PCC Plat form made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (Sub Panel a,b & c Offr Area)(i) Busbar :- 150 Amps rated Copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulatorbus bar support (Square/round ) insulators of suitable size and good insulation resistance(ii)MCCB 4 Pole, 415 Volts,125 Amps adjustable type, 36 KA- 01 No (incoming)(iii)MCCB 4 Pole, 415 Volts, 40 Amps adjustable type, 16 KA- 04 Nos (outgoing)(iv) Suitable Capacity of CTs-01 Set(v) Indicator lamp LED type (R-Y-B) - 01 set of three (vi) 3 phase volt meter (0-500V) digital type with selector switch - 01 No (vii) Ammeter digital type (0-500A) - 01 No with selector switch - 01 No |
| 21 | M&L for Cutting theexisting road of width0.25 M x 0.6 M depth x 3.0 M lengthfor layingthe GI pipe light grade with all fittings such as bends, sockets, reducers union etc, completeof 80 mm diaas mechanicalprotection toLT cable including excavation in any type of soil, rfr , removal and PCC 1:4:8 of 15 cm below the GL for making the the road cut portion good complete all as specified and as directed.(Note :-GI pipe light grade with all fittings such as bends, sockets, reducers union etc, completeof 80 mm dia shall bemeasured and paid under the respective item ) |
| 22 | Disconnection and Removing theunserviceable Aluminium Over head conductorfrom the LT Poles carefully along with all the jumpers and Aluminium binding wire complete all as directed |
| 23 | Disconnection and removing the insulators any type from LT poles. complete all as directed |
| 24 | Disconnection and removing the cross arms from LT poles. complete all as directed |
| 25 | Dismantling the earth chamber, Excavation and removing the unserviceable earthing materials along with unserviceable earth electrodes from the existing u/s earth pits pertains to installations/ buildings and M & L for providing earthing with GI earth plate electrode 600 mm x 600 mm x 6 mm thick burried directly in ground vertically to depth of not less than 2.25 mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to GI earth strip of 32x6 mm by means of bolts, nuts, washers of GI and provision of earth lead, GI protection pipe with 15mm light grade galvanized including necessary earth work in any type of soil, PCC 1:3:6type CI (using 20mm graded stone aggregate) earth chamber and 1:2:4 type B1 RCC cover fitted with50mm thick with 6mm dia MS bars complete all as shown in SSR Pt - 1 electrical plate No 3. Note : Quoted rate deemed to include the cost or excavation and earth work PCC Chamber, funnel cover etc complete all as specified and as directed. |
| 26 | S & F LT UG cable route indicator made out of cast iron of size Head dia 4\"\" with 25 mm x 25 mm x 3 mm thick 60 cm long MS support angle and painting of exposed surfaceand markedas \"MES LT CABLE 1.1 KV\"in brown colour letters on yellow background complete including necessary earrth work cement concrete 1:2:4 for embedding MS support as required at sitecomplete all as specified and as directed. |