| 1 | Supply, installation & commissioning of Horizontal shaft end suction centrifugal type Main Fire Pump motor complete set capable to discharge clear water of 2850 LPM against a total water column head of 88 M\"High efficiency volute\" type having CI casing, Bronze impeller, and other accessaries directly coupled with horizontal foot mounted(B1) TEFC 2900 RPM (approx) ,2 pole 3 ph, 415±10% AC SQIM of suitable power, entire assembly being mounted on pump vendor\"s own manufactured MS base frame complete with all other accessories (coupling & coupling guard,cushy foot, rubber friction pad) necessary cement (1:2:4) as required, 12 mm thick cement pluster (1:4) & neat cement finish & fixing bolts etc. complete as per technical specification & direction of EIC. (for Hydrant System). |
| 2 | i) 2850 lpm at 88M Head |
| 3 | Supply,installation & commissioning of Horizontal shaft end suction centrifugal type Springkler Pump motor complete set capable to discharge clear water of 2850 LPM against a total water column head of 88 M\"High efficiency volute\" type having CI casing,Bronze impeller, and other accessaries directly coupled with horizontal foot mounted(B1) TEFC 2900 RPM (approx) ,2 pole 3 ph, 415±10% AC SQIM of suitable power, entire assembly being mounted on pump vendor\"s own manufactured MS base frame complete with all other accessories (coupling & coupling guard,cushy foot, rubber friction pad) necessary cement (1:2:4) as required, 12 mm thick cement pluster (1:4) & neat cement finish & fixing bolts etc. complete as per technical specification & direction of EIC. (for Sprinkler System) |
| 4 | i) 2850 lpm at 88M Head |
| 5 | Supply,installation & commissioning of Horizontal shaft end suction centrifugal type Jockey Pump motor complete set capable to discharge clear water of 180 LPM against a total water column head of 88 M\"High efficiency volute\" type having CI casing,Bronze impeller, and other accessaries directly coupled with horizontal foot mounted(B1) TEFC 2900 RPM (approx) ,2 pole 3 ph, 415±10% AC SQIM of suitable power, entire assembly being mounted on pump vendor\"s own manufactured MS base frame complete with all other accessories (coupling & coupling guard,cushy foot, rubber friction pad) necessary cement (1:2:4) as required, 12 mm thick cement pluster (1:4) & neat cement finish & fixing bolts etc. complete as per technical specification & direction of EIC. (for Jockey Pump) |
| 6 | i)180 lpm at 88 m Head |
| 7 | Supply, delivery at site fitting and fixing of following MS ERW pipe(Heavy) conforming to IS 3589/ IS 1239 including fabrication of all necessary accessories special viz. dismantling joints, enlarger / reducer, c.c. padestal, M.S. Channel, Angle, Flat anchor fasteners, bolts, nuts, clamps, \"U\" bolt etc. including cutting walls, ceiling, pipes, making flanged & welded joints as required, fitting, fixing complete in all respect including cost of all fittings, including sundry and jointing materials as required for laying of pipe with anti-corrosive treatment of all pipe surface & painting in any portion above ground as per technical specification and direction of EIC. |
| 8 | a) 150 mm dia. |
| 9 | b) 100 mm dia. |
| 10 | c) 80 mm dia. |
| 11 | d) 50 mm dia. |
| 12 | e) 25 mm dia. |
| 13 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 14 | a) 150 mm dia. |
| 15 | b) 100 mm dia. |
| 16 | c) 80 mm dia. |
| 17 | d) 50 mm dia. |
| 18 | Supplying, fixing of SS Ball Valve of 25 mm size for draining. |
| 19 | Structural support & MS fitting materialsfor piping with suitable size of M.S Angles, clamps, Channels & nuts & bolts / Tie-Rod etc. as per direction of EIC. |
| 20 | Scaffolding charges for erection of water Curtain nozzle at stage with Bamboo & wooden plank and cutting of slab for installation of pump motor, suction & delivery pipe etc. |
| 21 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type A) with blank Gunmetal/Stainless Steel cap and chain as required: Single headed Gunmetal. |
| 22 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required- Gun Metal. |
| 23 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required: Gun Metal. |
| 24 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the Set Set following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 25 | a) 30 Mtr. |
| 26 | Supply, delivery at site, fitting and fixing of Quartzoid bulb type sprinkler head 680 C rating and complete in all respect with all labour, tools & plants, transportation, taxes, levies etc. as per specification, drawing and direction of EIC. |
| 27 | a) Pendant / Upright type. |
| 28 | Supply, delivery at site, fitting and fixing of bourdon type dust & damp proof pressure gauge of 150mm dial (accuracy ± 1% having range0 -16 Kgf / cm² and complete with all valves, cocks and other fixtures as required including cost of all sundry materialsaccessories and fitting, fixing charges as required as per technical specification and direction of EIC. |
| 29 | Supply & erection of approved make 25 mm dia safety with Air release valve complete with G.M valve & G.I fittings complete. |
| 30 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required: |
| 31 | a) 80 mm dia. |
| 32 | Supplying,Fitting & Fixing of GM Gate Valve as per IS:778,screwed type,25 mm dia. |
| 33 | Supply, Delivery and installation of Co2 type fire extinguishers. |
| 34 | 4.5 Kg capacity with ISI marked CO2 type fire extinguisher squeeze grip type conforming to IS:15683:2006 made from seamless cylinder conforming to IS:7285 duly approved by Chief controller of explosive, Nagpur, fitted with ISI marked controller of explosive, Nagpur, fittet with ISI marked controlled valve conforming to IS:3224, high pressure 1 mtr. long discharge hose and horn complete with initial gas charged with carrying handle and wall mounting bracket suitable for operating between (-)30°C to (+)55°C. Fire rating -13B. |
| 35 | Supply Delivery and installation of ABC Powder type fire extinguishers (stored pressure) HSN code-84241000 conforming to IS:15683 and complete in all respect as per direction of EIC. |
| 36 | 04 Kg with ISI marked Mono Ammonium Phosphate base ABC power conforming to IS:14609 and pressurized with nitrogen gas. Suitable for operating between (-)30ºC to (+)55ºC. Fire rating -1A & 13B. |
| 37 | Foam type Fire Extingushers HSN Code:84241000. ISI marked Foam Stored Pressure type fire Extinguisher 9 ltrs capacity consisting of wielded cylinder, squeeze lever discharge valve fitted with pressure indicating gauge with internal discharge tube, discharge nozzle, suspension bracket, conforming to IS:15683 duly charged with ISI marked Aqueous film forming foam conforming to IS:4989 and pressurized with nitrogen gas. Suitable for operating between (+) 5°C to (+)55°C. Fire rating -3A & 34B. |
| 38 | Supply and fixing on wall or on stand of 9 Ltrs capacity M.S. bucket, 50% of the bucket capacity to be filled with sand. |
| 39 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 40 | i) Two loop panel |
| 41 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required and direction of EIC. |
| 42 | Supply, installation, testing and commissioningof smoke detector with builtin LED and mounting base complete with all connections etc. as required and direction of EIC. |
| 43 | Supplying, installation, testing & commissioning of heat detector operating at 54°C/57°C with rate of rise cum fixed tempreature (dual thermistor) type with mounting base complete with all connection etc. as required and direction of EIC. |
| 44 | Supplying, installation, testing & commissioning of addressable manual call point complete as required and direction of EIC. |
| 45 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required and direction of EIC. |
| 46 | Supplying, installation, testing & commissioning of fault isolator complete with base as required and direction of EIC. |
| 47 | Supply, Installation, Testing & Commissioning of photolumicent natured board and compleet in all respect as per specification, drawing and direction of EIC. |
| 48 | a) Emergency Exit (150 mm x 300 mm) |
| 49 | b) Fire Notice (450 mm x 600 mm) |
| 50 | Supply, delivery at site and drawing of 1.1 KV grade 2 × 1.5 mm2 PVCinsulated and unsheathed copper conductor flexible heat resistant and flame retardant wire (approved make) through 20 mm PVC conduit pipes and making end connections at both end as per technical specification and direction of EIC. |
| 51 | Commissioning and Trial Run of the whole fire protection and fire alarm system as per National Building Code and stipulations of local fire brigade authority and making the system ready for inspection of the fire inspector and making all arrangements for inspection on behalf of the department / end user of the housing complex and obtaining final clearance certificate from the fire department, Govt. of West Bengal as per technical specification and direction of EIC. |
| 52 | Sub-Total = 38,16,231.00 |
| 53 | Add GST @ 18% |
| 54 | Sub-Total = 45,03,152.58 |
| 55 | Add LWC @ 1% |