| 1 | Supply, Installation, Testing & Commissioning of 750KVA Silent type DG Setcomprising of Engine, coupled to 750KVA, 415V Alternator mounted on a common base framecomplete with 990 Ltrs fuel tank (Outside Acoustic Enclosure), Batteries & Leads, AVM Pads, Silencer, Radiator,First fill of Lube oil, Terminal Box, Auto Start Auto Stop Isolator Panel (1250 A EDO ACB) with power (CU) Cable, 300mm dia Exhaust pipe with insulation and Al Cladding complete in all respect including unloading & shifting at site with CEIG approval with meter and CTs panel & Testing for 6 Hrs at site and as instruction of Engineer in charge. |
| 2 | Supply, Installation, Testing & Commissioning of Outdoor type double Breaker AMF Control Panel suitable for750 KVA silent type DG Set as per approved SLD completeas per direction of the Engineer in charge. |
| 3 | Supply, laying, testing& commissioning of following size of XLPE insulated,PVC sheathed,round/strip armoured aluminium conductor power cable of 1100 volt grade laid directly underground with sand cushioning,brick protection clamped on surface of wall/column/existing G.I pipe/human pipe/PVC pipe inside masonry cable trench/on the cable tray/through as the case may be including cost of saddles /clamps/cable markers etc but excluding the cost of G.I pipe /HDPE pipe/PVC pipe compete with making good the damages caused as required and as per direction of Engineer-in-charge. |
| 4 | 3.5c x 300 sqmm Al.Ar. Cable in existing HDPE pipe. |
| 5 | Supply & Laying of 110mm HDPE pipe of following size KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 6 | 110mm HDPE Pipe. |
| 7 | Supply of materials & end termination of following cables including supply of single compression brass cable glands,cable sockets etc complete as required and as per direction of Engineer-in-charge. |
| 8 | 3.5 core X 300 sqmm A2XFY |
| 9 | Supply, delivery, installation, testing & commissioning of 250 micron Copper bonded Earth Rod 3 Mtr longX17.2 mm dia CPRI Certified madeup of high tensile low carbon steel with copper bonding of 99.9% electrolytic copper. Electrode should be testedin CPRI for 25KA short circuit current .Boththe ends of electrode should bethreaded and suitable for threaded Ground Rod Clamp.Ground rod clamp should be made up of brass.(Back filling compound will be provided in 25Kgs Bags) complete as required and as per direction of Engineer-in-charge. |
| 10 | Providingand fixing of 25mmX5mmdia Copper strip of wall/surfaceor in recess for connection etc. as required for earthing connection complete in all respect as required as per technical specification and instruction of Engineer in charge. |
| 11 | Construction of DG Base as per approved design with earth excavation in all kinds of soil,filling foundationwith sand,CC 1:4:8with metal in case, using Fly Ash Bricks in CM 1:6, RCC M-25, Cutting, straightening of MS or Tor steel Carriage & disposal of surplus earth, CP 12mm with CM 1:6 and two coats of paints of any approved quality to the outer side etc. complete as required and as per direction of Engineer-in-charge. |
| 12 | Construction of DG shed with supply of all materials and fixing of aluminium sheet over GI channel & angle frame etc. for protection of rain water of 750KVA DG Shed of size 2 nos; 10.0M(L)X4.50M(W)X4.50M(H) as per approved design and complete as required and as per direction of Engineer-in-charge |
| 13 | EXHAUST STACK SYSTEM |
| 14 | Supply and construction of 300MM DIA ms Black pipe4.85/5.1mm |
| 15 | Supply and fixing of 50mm thick rock wool insulation for 300mm dia pipe |
| 16 | Supply and fixing of 300mm dia Exhaust Bellow |
| 17 | Supply and fixing of Silencer cladding |
| 18 | Design and Supply of all required materials & installation ofa common Self standing GI (Hot dip galvanised) structure of 30Mtr high with all accessories for supporting the exhaust pipes of for 2X750KVA DG sets(The structure must be strong enough to withstand 200 Km/Hr wind speed as per approved drawing) complete as required and as per direction of Engineer-in-charge. |
| 19 | Supply & Installation of Lighting Protection system with Copper Air terminalcomplete with earth continuity conductor of 25x3 mm copper strip connection to earthing pit complete as required and as per direction of Engineer-in-charge |
| 20 | Supply, installation, testing and commissioning of 2nos. single dome LED aviation obstruction light including all required mounting frame and laying of sepate 3 C X 2.5 sqmm Copper Un.Ar.Cable, Time switch Control DB, Incoming cable, etccomplete and as per direction of the Engineer in charge complete. |
| 21 | N.B: The bidders are required to Quote their rates excluding of Goods & Service Tax (GST). GST as applicable will be paid extra. The existing rule of Govt. and any amendment made in future will be followed. |