| 1 | fire |
| 2 | 90.17.2.9:Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. asrequired.Suitable cement concrete foundation duly plastered and with anti vibration pads.1620 lpm at 56 m Head |
| 3 | 90.17.3.3:Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)a. Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520.b. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325.c. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. As required.d. Suitable cement concrete foundation duly plastered and with anti vibration pads.180 lpm at 56 m Head |
| 4 | 90.17.1.9:Electric driven Main Fire Pump: Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration pads.1620 lpm at 56 m Head |
| 5 | 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 6 | 2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N |
| 7 | 2.1.3:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N |
| 8 | 2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N |
| 9 | 2.1.5:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.160 Amp TP&N |
| 10 | 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 11 | 90.14.3.1:Supply and providing heavy duty \"A\" section neoprene gasket in the panel boardA\" section neoprene beeding suitable for 1.60/ 2.00 mm sheet |
| 12 | 90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC) |
| 13 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 14 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 15 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 16 | OD123660/2021-2022:SITC of Auto/Manual selector switch Cat No: 61198 of L & T make ) |
| 17 | OD123661/2021-2022: Supply and providing and fixing following multi function meter to read: V, A, F, with 3 line LED display of size 96 X 96mm, 3 phase accuracy class 1 in existing panel and giving connection complete |
| 18 | OD123662/2021-2022:Providing and fixing following 9 A, 3 Pole Mini contactor, AC 3 Rating, AC coil in existing panel and giving connection complete |
| 19 | 90.14.28.8:S & F Motor starters of the following ratingsFully automatic star delta starter for 30 to 35HP motor |
| 20 | 90.14.28.2:S & F Motor starters of the following ratingsThree phase DOL starters for 0.25HP to 7.5 HP motor |
| 21 | OD123666/2021-2022:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. With 1.50 sq mm wire |
| 22 | 90.6.10.1:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm |
| 23 | 90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 24 | 90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp |
| 25 | 90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp |
| 26 | 9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 27 | 9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 28 | 9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) |
| 29 | 90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 30 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 31 | 90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG) |
| 32 | 90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG) |
| 33 | 90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG) |
| 34 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 35 | 17.5.2:CABLING & WIRINGSupplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 36 | 17.1.9.3:Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required.10 Zone |
| 37 | OD123376/2021-2022:Supply and providing Fire Escape Route size not less than 16\"x16\" as required |
| 38 | OD123377/2021-2022:Supply and providing Assembly point boards of 3mm PVC foam board size not less than 16\"x16\" as required |
| 39 | OD123378/2021-2022:SIGN BOARDS:- supply & installation of necessary Glow Sign Board made of 3 mm thick PVC foam board as per new fire station, Fire Exit passenger Lift, Electrical Duct ,Plumbing Duct, Floor level, Fire Lift in each floor |
| 40 | OD123652/2021-2022:Supplying and fixing of Priming tank of size not less than 1000 liters of storage capacity as required etc. |
| 41 | 90.17.7.1:Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :25 mm dia |
| 42 | 90.17.7.6:Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80 mm dia |
| 43 | 90.17.7.7:Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :100 mm dia |
| 44 | 90.17.7.8:Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :150 mm dia |
| 45 | 90.17.9.2:Supplying and fixing single headed internal hydrant valve with instantaneousGunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conformingto IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :Single headed Stainless steel |
| 46 | 90.17.11.4:Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required80 mm dia |
| 47 | 90.17.10.2:Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as requiredSingle headed Stainless steel |
| 48 | 90.17.11.5:Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required100 mm dia |
| 49 | 90.17.11.6:Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required150 mm dia |
| 50 | 90.17.14.4:Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :80mm dia |
| 51 | 90.17.14.5:Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :100mm dia |
| 52 | 90.17.14.7:Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :150mm dia |
| 53 | OD209000/2022-2023:Providing and fixing horizontal type cast iron double flanged Non -return valve of approved quality conforming to IS:5312 with bolts, nuts, washers, 3mm thick insertion rubber gaskets complete. as reqd. 25 mm Non Return Valve |
| 54 | OD209001/2022-2023:Supplying , fixing, testing and commissioning of butterfly valve PN 1.6, bronze/ Gun metal seat duly ISI marked complete with Nuts, Bolts, washers, gaskets, conforming to IS 13095 of following sizes as required. 25mm dia |
| 55 | 90.17.16.2:Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless Steel (Grade 304) |
| 56 | OD123681/2021-2022:HOSE BOX :- Supplying and fixing of hose cabinet fabricated from 2mm thick MS sheet with 6mm thick glazed front glass doors and looking arrangements suitable for accommodate internal accommodate of 2 no. of 15 Mtrs long hose pipe, 1 No. branch pipe, fittings etc. The cabinet shall be painted with one coat of primer and 2 coatts of synthetic enamel paint of post office red externally and white internally and shall be suitably mounted on concrete base. |
| 57 | 90.17.17.1:Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.a. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585b. 20 mm nominal internal dia gun metal globe valve & nozzle.c. Drum and brackets for fixing the equipmets on wall.d. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.30 m |
| 58 | 90.17.18.2:Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Stainless Steel (Grade 304) |
| 59 | OD123689/2021-2022:Supply and installation, testing and commissioning of CO2 type fire extinguisher with4.5kg. Capacity complete with installation brackets with ISI mark IS:15222 |
| 60 | OD123690/2021-2022:Supply and providing 5 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required. |
| 61 | OD123687/2021-2022:AIR RELEASE VALVE:- Supply, installation, testing and commissioning of Gun metal Air Release valve 20mm dia |
| 62 | 90.17.22:Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required |
| 63 | OD123685/2021-2022:PRESSURE GAUGE:-Supplying, fixing, testing and commissioning of 0-15 Kg/sq cm100mm dia Dial type pressure gauge with isolation cock and pipe at hydrant station as per specification. |
| 64 | 90.17.20:Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. |
| 65 | 17.1.1:FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of heat detector operating at 54ºC / 57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. |
| 66 | 17.1.2:FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of smoke detector with built-in LED and mounting base complete with all connections etc. as required. |
| 67 | 17.1.3:FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of manual call boxes of MS Construction in surface/recess with stainless steel chain & hammer assembly Complete with glass and push button etc. as required. |
| 68 | 17.1.6:FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. |
| 69 | 17.1.8:FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning talk back slave station in surface/ recess suitable for operation on simplex mode complete with P.T.T. knob & speaker/ microphone enclosed in a M.S.(16 SWG)/ ABS box with break glass in front etc. complete as required. |
| 70 | OD123697/2021-2022:Copying charges of Electrical/fire Drawing per A3 sheet additional copies |
| 71 | OD123698/2021-2022:Charges for preparation of Electrical/fire Drawing per A3 sheet first copy |
| 72 | OD123699/2021-2022:Charges to be paid to Fire Department for Fire NOC |
| 73 | 2.10.3:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole |
| 74 | OD209013/2022-2023:Supply and fixing of SMPS based Battery Charger suitable for 12/24V DC, 0.5 to 10A capacity and giving connection etc as required. |
| 75 | OD209017/2022-2023:Supply & fixing 100/5 A, 7.5 VA, accuracy class 10P 10, Protection CT (Tape wound) |
| 76 | OD209042/2022-2023:Supply and fixing up to 20 A 230/ 415 V Backelite fuse unit With fuse link |
| 77 | OD70660/2023-2024:Supply and fixingLED indicator (6 V AC/DC, 12V AC/DC, 24 V AC/DC, 48V AC/DC, 63.5V AC/DC, 110 V AC/DC, 220V DC, 240 V AC), 22.5 mm cut out dia (Blue colour ) |
| 78 | OD70661/2023-2024:Supply and fixingLED indicator (6 V AC/DC, 12V AC/DC, 24 V AC/DC, 48V AC/DC, 63.5V AC/DC, 110 V AC/DC, 220V DC, 240 V AC), 22.5 mm cut out dia (Red, Green, Black, Yellow, Orange colours ) |
| 79 | 90.12.5.18:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3 core 50 sq mm |
| 80 | 90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size |
| 81 | 90.12.9.3:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench63/50 mm or nearest size |
| 82 | 90.12.9.4:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench77/63 mm or nearest size |
| 83 | OD44906/2023-2024:Supply & erection of Fire Escape rout in each floor having size 12" x 16" |
| 84 | OD45339/2023-2024:Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :4 way - 63mm dia M.S. Pipe |
| 85 | 17.3.2:PUBLIC ADDRESS SYSTEMSupplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
| 86 | OD45854/2023-2024:Supply & erecion of MICROPHONE for Intelligible, crisp and bright sound suitable for all type of PA applications. Supplied with quick detachable holder with 3-pin professional XLR connector & 6 mtrs. Twin core shielded low noise cable. |
| 87 | OD45862/2023-2024:Supplying and fixing Three Phase Voltmeter of Accuracy Class 1 |
| 88 | OD45863/2023-2024:Supplying and Three Phase Ammeter (A-R,Y,B) of accuracy Class 1. |
| 89 | OD46221/2023-2024:upplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required.25 sq - 95sq mm with 20 mm wide x 1.20 mm thick clip |
| 90 | OD46222/2023-2024:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required(.4sqmm-16 sq mm with 12 mm wide x 1 mm thick clip) |