| 1 | Material and labour for taking out Motor Set of capacity 10 H.P to 20 HP from position and transportation of same from site to workshop and back, dismantling of cable/ pipe connection and reinstallation of motor set after necessary repairing on the existing foundation and making electrical connections including necessary nuts, bolts, washers etc., required at site of work, complete all as specified & directedNote : All spares parts required shall be measured and paid for separately |
| 2 | (a) Supply only Ball Bearing of suitable size |
| 3 | (b) Supply only Rubber washer of suitable size |
| 4 | (c ) Supply only Packing sheet of suitable size |
| 5 | (d) Supply only Bush cover of suitable size |
| 6 | (e) Supply only Mechanical Seal of suitable size |
| 7 | (f) Supply only Circlips Clamp of suitable size |
| 8 | Material and labour for taking out Motor Set of capacity 5 H.P to 7.5 HP from position and transportation of same from site to workshop and back, dismantling of cable/ pipe connection and reinstallation of motor set after necessary repairing on the existing foundation and making electrical connections including necessary nuts, bolts, washers etc., required at site of work, complete all as specified & directedNote : All spares parts required shall be measured and paid for separately |
| 9 | (a) Supply only Ball Bearing of suitable size |
| 10 | (b) Supply only Rubber washer of suitable size |
| 11 | (c ) Supply only Packing sheet of suitable size |
| 12 | (d) Supply only Bush cover of suitable size |
| 13 | (e) Supply only Mechanical Seal of suitable size |
| 14 | (f) Supply only Circlips Clamp of suitable size |
| 15 | Material and labour for taking out Motor Set of capacity 1 H.P to 3 HP from position and transportation of same from site to workshop and back, dismantling of cable/ pipe connection and reinstallation of motor set after necessary repairing on the existing foundation and making electrical connections including necessary nuts, bolts, washers etc., required at site of work, complete all as specified & directedNote : All spares parts required shall be measured and paid for separately |
| 16 | (a) Supply only Ball Bearing of suitable size |
| 17 | (b) Supply only Rubber washer of suitable size |
| 18 | (c ) Supply only Packing sheet of suitable size |
| 19 | (d) Supply only Bush cover of suitable size |
| 20 | (e) Supply only Mechanical Seal of suitable size |
| 21 | (f) Supply only Circlips Clamp of suitable size |
| 22 | Material and labour for rewinding of damaged/burnt motor of capacity 1 H.P to 20 H.P any type by using enamelled copper wire of superior quality of existing grade and same Nos. of turns including varnishing ‘F’ class insulation and drying in heat chamber / oven including all other material / fittings and testing on completion, complete all as specified & directed. |
| 23 | Material and labour for taking out Centrifugal Pump of capacity10 HP to 20 H.P and transportation of same from site to workshop and back,dismantling of cable/ pipe connection and reinstallation of pump set after repair on the existing foundation and making electrical connections complete all as specified and directedNote : All spares parts required shall be measured and paid for separately |
| 24 | (a) Pump overhauling GM bushes, shaft rematteling making key gland packing,incl all engineering work. |
| 25 | (b) Pump shaft stainless steel of same make and model duly grinded/polished |
| 26 | (c) Bearing of suitable size of pump |
| 27 | (d) Plugging leaks in casing by welding the same incl grinding for smooth surface |
| 28 | Material and labour for taking out Centrifugal Pump of capacity1 HP to 7.5 H.P and transportation of same from site to workshop and back,dismantling of cable/ pipe connection and reinstallation of pump set after repair on the existing foundation and making electrical connections complete all as specified and directedNote : All spares parts required shall be measured and paid for separately |
| 29 | (a) Pump overhauling GM bushes, shaft rematteling making key gland packing,incl all engineering work. |
| 30 | (b) Pump shaft stainless steel of same make and model duly grinded/polished |
| 31 | (c) Bearing of suitable size of pump |
| 32 | (d) Plugging leaks in casing by welding the same incl grinding for smooth surface |
| 33 | S&F in replacement of Star Delta starter fully automatic, 3 phase, 415 volts, 50 Hzheavy duty with overload relay ragne 20-32 Amp having protection against single phase with provn of volt/Amp meter, indicators, selector switches, push ON/OFF switch completeincluding making necessary connections and taking down old unserviceable Starter all as specified and as directed.Make : L&T / Havells / Legrand / ABB / C&S |
| 34 | S&F in replacement of Star Delta starter fully automatic, 3 phase, 415 volts, 50 Hzheavy duty with overload relay ragne 13-22 Amp having protection against single phase with provn of volt/Amp meter, indicators, selector switches, push ON/OFF switch completeincluding making necessary connections and taking down old unserviceable Starter all as specified and as directed.Make : L&T / Havells / Legrand / ABB / C&S |
| 35 | S&F in replacement of DOL starter fully automatic, 3 phase, 415 volts, 50 Hzheavy duty with overload relay ragne 18-25 Amp having protection against single phase with provn of volt/Amp meter, indicators, selector switches, push ON/OFF switch completeincluding making necessary connections and taking down old unserviceable Starter all as specified and as directed.Make : L&T / Havells / Legrand / ABB / C&S |
| 36 | S&F in replacement of DOL starter fully automatic, 3 phase, 415 volts, 50 Hzheavy duty with overload relay ragne 23-32 Amp having protection against single phase with provn of volt/Amp meter, indicators, selector switches, push ON/OFF switch completeincluding making necessary connections and taking down old unserviceable Starter all as specified and as directed.Make : L&T / Havells / Legrand / ABB / C&S |
| 37 | Supply and fixing in replacement of CI Non Return Sluice Valves ISI Marked flanged class 1.6 PN with by-pass arrangement and necessary bolts and nuts of suitable size with and including rubber gasket for flanged joints and testing including taking out old unserceable non returnvalves complete of following sizes :-Make : KIRLOSKAR / BIR / BIV / L&T / KARTAR/ ZOLOTO |
| 38 | (a) 150 mm bore |
| 39 | (a) 100mm bore |
| 40 | (b) 80mm bore |
| 41 | Supply and fixing in replacement of CI Sluice Valves ISI Marked flanged class 1.6 PN with necessary bolts and nuts of suitable size with and including rubber gasket for flanged joints and testing including taking out old unserviceable sluice valves complete of following sizes :-Make :KIRLOSKAR / BIR / BIV / L&T / KARTAR/ ZOLOTO |
| 42 | (a) 150 mm bore |
| 43 | (a) 100mm bore |
| 44 | (b) 80mm bore |
| 45 | Supply and fixing in replacement of Gun metal globe, Ball or gate valve class-2 with iron wheel head screwed both ends for pipes of following sizes complete including taking down old unserviceable gate valves all as specified and directed :- Make :KIRLOSKAR / BIR / BIV / L&T / KARTAR /LEADER / ZOLOTO |
| 46 | (a) 80 mm bore |
| 47 | (b) 63 mm bore |
| 48 | (c) 50mm bore |
| 49 | (d) 40 mm bore |
| 50 | (e) 32 mm bore |
| 51 | (f) 25 mm bore |
| 52 | (g) 20 mm bore |
| 53 | Supply and fixing in replacement of Cast Iron Foot Valve, conforming to IS-4038, complete suitable for pipes of following sizes complete including taking down old unserviceable foot valve all as specified and directed :-Make :KIRLOSKAR / BIR / BIV / L&T / KARTAR /LEADER / ZOLOTO |
| 54 | (c) 80 mm bore |
| 55 | (a) 63 mm bore |
| 56 | (b) 50 mm bore |
| 57 | Excavating in trenches in any type of soil, not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out, complete all as specified and as directed. |
| 58 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed. |
| 59 | Removing excavated soilsnot exceeding 50 metres and depositing where directed at a level not exceeding 1.5metre above the starting point, complete all as specified and directed. |
| 60 | Supply and fixing in replacement of Galvanised iron tubing (GI), medium grade, with all fittings such as sockets, bends, elbows, tees, short pieces, connectors, back nuts, diminshing pieces, caps, plugs and unions etc., laid in trenches /fixed to walls and ceilings or laid in floors, including takind down old steel tubing complete all as specified and as directed of the following description :- Make : JINDAL PIPES / TATA / BST / PRAKASH SURYA |
| 61 | (a) 100 mm bore |
| 62 | (b) 80 mm bore |
| 63 | (c ) 50 mm bre |
| 64 | (d) 40 mm bore |
| 65 | (e) 25 mm bore |
| 66 | (f)20 mm bore |
| 67 | M&L in replacement Gland for pump set capacity 2 HP to 20 HP complete all as specified and directed. |
| 68 | Supply only High Strength Calcium based granular disinfectant for water treatment, more stable than chlorine gas, and stronger than Bleaching Powder and Sodium Hypochlorite of following specifications :-(a) Chemical analysis & physical observations :Description : Whitish granules ofgranular size (Mesh passing through – 100 BSS) : 1.1 (± 0.1) %, Water / moisture : 5.00 (± 0.2) % Other insoluble Calcium salts: 1.1 (± 0.1) %Mercury and other Heavy Metal contaminants : BDL (The chlorination chemical must contain appropriate quantities of dispersants / corrosion inhibitors to prevent encrustation / scaling in distribution systems) |
| 69 | (b) Strength in terms of quantity of chlorination chemical required to obtain free chlorine of 1 ppm per lakh litres of water :Requirement must be 100 gm. per one lakh litre of water to achieve 05-1.0 ppm Av. Cl. at injection point (Site and raw water quality variations may apply additionally).(c) Stability : Projected shelf life of chlorination chemical must be one year with minimal loss of chlorine. Make : Purichlore / Mark Daxter / ALTOCH-Gp (Declivace Technologies Pvt Ltd) / Any E-in-C approved Make |
| 70 | Supply only Hypochlorous Acid (HOCL) for chlorination of drinking water disinfection solution having high residual effect, clear colour less and potent germicide non corrosive and non foaming stable up to100° C for drinking water as and when required in HDPE jericanes of 35 Litres capacity having the following features :(a) Potent germicide(b) Slim control(c) High residual effect to avoid contamination(d) Less hazardous(e) Work at low dosage in post disinfection(f) No after taste(g) Most reliable in operation(h) Eco friendly and biodegradableMake : Penta Water Treatment / Seacolor/ Hygene Maddox People Care / Super-Chlor Total |
| 71 | Supply of Potassium aluminum sulfate, clear in colour of class 1 quality suitable for purification of raw water all as specified and directed. |
| 72 | Supply only Bleaching powder class 1 qualiity all as specified and directed. |
| 73 | Supply only Lead pig superior quality all as specified and directed. |
| 74 | Supply only Lead wool superior quality all as specified and directed. |
| 75 | Draining out water from RCC overhead water storage tank of capacity 90,000 Ltrs, taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes all as specified and directed. |
| 76 | Draining out water from sedimentation tank of capacity 80000 Ltrs, taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes all as specified and directed. |
| 77 | Draining out water from Mild Steel water storage tank of capacity 50000 / 60000 Ltrs, taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes all as specified and directed. |
| 78 | Draining out water from underground water storage tank of capacity 45000 Ltrs, taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose,removing all scale,dirt,algae,vegetation if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes all as specified and directed. |
| 79 | Draining out water from clear water tank of capacity 40000 Ltrs, taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes all as specified and directed. |
| 80 | Draining out water from underground/ semi underground water storage tank of capacity 30000 Ltrs, taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes all as specified and directed. |
| 81 | Draining out water from PVC water storage tank of capacity 10000 Ltrs, taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation if any and flushing aftercleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes all as specified and directed. |
| 82 | Draining out water from PVC water tank of capacity 5000 Ltrs taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes all as specified and directed. |
| 83 | Draining out water from PVC water tank of capacity 1000 Ltrs taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes all as specified and directed. |
| 84 | Draining out water from PVC overhead water tank of capacity ranging from 250 Ltrs to 500 Ltrs placed at different locations at Ramban, Banihal & Patnitop, taking out sludge and depositing the same outside the Cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation if any and flushing after cleaning with water, cleaning walls and floors by scratching with wire brushes all as specified and directed.Note for Serial Item No 27 to 35 :1. The \"Date of Cleaning\" and \"Due on\" shall be written with synthetic enamel paint prominently on the tanks cleaned all as directed by the Engr-in-Charge. The quoted rate shall be deemed to be inclusive of this aspect.2. The T&P required for cleaning of the tanks is deemed to be included in the unit rate quoted by the contractor. |
| 85 | Taking out old unserviceable filter media from existing gravity type filter, cleaning the filter thoroughly from inside, outside and channel all around, taking out sludge and throwing the same in low lying area including replacing filter media with new filter media all as specified and directed by Engineer-in-Charge. NOTE :-- Supply only new filter media shall be measured & paidfor separately as under :- |
| 86 | Supply only filter media of size as mentioned below :- |
| 87 | a) Course aggregate of size 63mm |
| 88 | b) Course aggregate of size 40mm |
| 89 | c) Course aggregate of size 20mm |
| 90 | d) Course aggregate of size 12.5mm |
| 91 | e) Course sand suitable for filter plant |
| 92 | Repair/servicing ofchemical dosingelectric operated of make Renuka Tech Model RWT-DLX-0003, at site with the replacement of following unserviceable spares installed at water supply installation.Note : All spares parts required shall be measured and paid for separately as supply only under following items of Sch ‘A’ |
| 93 | (a) Supply only non return valve of suitable size complete all as specified. |
| 94 | (b) Supply only complete set of inlet and outlet pipe for chemical dosing pump complete all as specified. |
| 95 | (c) Supply only foot valve with strainer, 75 mm long complete all as specified |
| 96 | (d) Supply only regulator with marking from 1 to 10 to control discharge of HOCL complete all as specified. |
| 97 | Repairs / Replacement of PLC Controlled Unit with control panel for Sewage Treatment Plant with all electrical circuits, contactors driven by micro controller based programmable logic controller system, totally enclosed containing all necessary motor starters, circuit breakers, indicating lights, selector swtiches, relays, terminal blocks, controls and isolators complete and replacement of the following defective over load relay contactors in all respects all as specified and by Engineer-in-Charge :- |
| 98 | (a) Three Pole contactor AC operated of capacity 12 Amp, 5.5 HP, 5.5 KW rating 415 V - 01 NosMake : ABB, Product code No A-12-30-10(b) Three pole contactor AC operated of capacity 32 Amp, 20 HP, 15 KW rating 415 V - 01NosMake : ABB, Product code No A-30-30-01 |
| 99 | Submersible flat cable PVC insulated and PVC sheathed LT 1100 volts grade with copper conductor of size 10 Sqmm 3 Core, complete all as specified and directed.Make : Havells / Finolex / Polycab / Plaza / Asian |
| 100 | Submersible flat cable PVC insulated and PVC sheathed LT 1100 volts grade with copper conductor of size 16 Sqmm 3 Core, complete all as specified and directed.Make : Havells / Finolex / Polycab / Plaza / Asian |
| 101 | Supply only PVC Flexible pipe of size 63mm as complete as specified and as directed by the Engr-in-Charge |
| 102 | ON LOAD Change Over Switch 415 volt in sheet metal enclosure Three Pole of capacity 100 Amps complete all as specified and directed |
| 103 | ON LOAD Change Over Switch 415 volt in sheet metal enclosure Four Pole of capacity 200 Amps complete all as specified and directed |
| 104 | Dismantling and refixing the complete unit of solar water heater installed at various sites complete overhauling, cleaning, servicing all serviceable accessories including repairing/ replacing of all defective parts such as nuts, bolts, wasahers and all other minor accessories as required at site including painting to solar water heater by rubbing the old paint and applying with two coats of synthetic enamelled paint by spray painting and testing the same after repair, complete all as specified and directed of the following description.Note: Replacement of spares shall be measured and paid for seperately. |
| 105 | a) Capacity 300 LPD |
| 106 | b) Capacity 1000 LPD |
| 107 | Supply only the following items / spares in replacement for Solar Heaters of various capacities as mentioned in Serial No 45 here-in-before all as specified :- |
| 108 | (a) Heating element of capacity 2 KW (Electric rod) having rubber washer of size 1 ¼” or 1 ½”complete all as specified. |
| 109 | (a) Heating element of capacity 1.5 KW (Electric rod) having rubber washer of size 1 ¼” or 1 ½”complete all as specified. |
| 110 | (b) Glycol (Anti freezing solution) for filling in copper tubes complete all as specified. |
| 111 | (c) Dead flange with nut, bolts and washers complete all as specified. |
| 112 | (d)Float valve assembly 15mm dia complete all as specified. |
| 113 | (e) Thermostat suitable for solar heater complete all as specified |
| 114 | (f) Hot water steel tanknon stick 2mm thick with ceramic lining of capacity 300 Litres each including making necessary connections complete all as specified.Make : Surya Shakti / TATA BP or equivalent. |
| 115 | (g)Hot Water Steel Tanknon stick 2mm thick with ceramic lining of capacity 1000 Litres each including making necessary connections complete all as specifiedMake : Surya Shakti / TATA BP or equivalent. |
| 116 | S&F in repair G.I Socket of heavy grade for 50 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 117 | S&F in repair G.I Socket of heavy grade for 40 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 118 | S&F in repair G.I Socket of heavy grade for 25 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 119 | S&F in repair G.I Socket of heavy grade for 20 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 120 | S&F in repair G.I Socket of heavy grade for 15 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 121 | S&F in repair G.I Union of heavy grade for 50 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 122 | S&F in repair G.I Union of heavy grade for 40 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 123 | S&F in repair G.I Union of heavy grade for 25 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 124 | S&F in repair G.I Union of heavy grade for 20 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 125 | S&F in repair G.I Union of heavy grade for 15 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 126 | S&F in repair G.I elbow of heavy grade for 50 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 127 | S&F in repair G.I elbow of heavy grade for 40 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 128 | S&F in repair G.I elbow of heavy grade for 25 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 129 | S&F in repair G.I elbow of heavy grade for 20 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 130 | S&F in repair G.I elbow of heavy grade for 15 mm dia pipe including jointing material complete all as specified and directed. Make: Jindal/TATA/Prakash Tubes |
| 131 | M&L testing & Commissioning of LT panel frame CPRI approved, indoor type,factory made fabircated out of 3.15mm thick CRCA sheet, double door front/rear opening and locking arrangement, floor mounted on plateform of suitable size, aluminium bus bar chember (enclosed) with two coat of synthetic enamel paint over a coat of red oxide primer mounted on PCC blocks, fixed with grouted bold,nuts and washer and making complete connection in all respects in replacement as diected by engr-in-charge comprising of foillowing parts:-INCOMER :-(a)MCCB 125 Amp, FP, Thermal Magnetic release, 35 KA- 01 No as incomerOUTGOING :-(a)MCCB 63 Amp, TP,Thermal Magnetic release, 25 KA, 415 Volts - 02 Nos(b)MCCB 40 Amp, TP,Thermal Magnetic release, 25 KA, 415 Volts -01 Nos (c)MCB SPN 32 Amps - 01 Nos(d)Indicating lamps (Set of 03 Nos) - 01 Set. |
| 132 | (e) Aluminium bus bar chamber (4 Strips) 3 phase 415 volts 200 Amps fixed on insulatorsall as required - 01 Set(f)Digital voltmeter 0-500 volts with selector switch - 01 Set(g)Digital ammeter with CT\"s & selector switch 0-100 A cap- 02 Set(h) Panel Wiring with suitable size PVC insulated PVC sheathed 1100 volts grade with copper conductor multi-stranded cable with lugs on both ends of cable.(i) Front operated on load change over switch 100 amps.-01 No .Make : L&T/C&S/ABB/Havells(k) Star Delta starter fully automatic, 3 phase, 415 volts, 50 Hzheavy duty with overload relay ragne 20-32 Amp having protection against single phase, over load and phase reversal protection. - 02 Nos Make of starter BCH/L&T/ Seimen/C&S/Havells |
| 133 | Repairs of LT panel with electrical circuits, contactorscontaining all necessary motor starters - 02 Nos, circuit breakers, indicating lights, selector swtiches, relays, terminal blocks, controls and isolators complete and replacement of the following defective over load relay contactors in all respects all as specified and by Engineer-in-Charge |
| 134 | (a) 3 pole contactor for star Delta connection, AC operated suitable for 20-32 amp range, 415 VMake : L&T, Havells, ABB, C&S |
| 135 | (b) 3 pole contactor for star Delta connection, AC operated suitable for 12-18 amp range, 415 V - 03 NosMake : L&T, Havells, ABB, C&S |
| 136 | (c) Thermal overload relay suitable for 12-32 Amp contactor range, 415 Volt.Make : L&T, Havells, ABB, C&S |
| 137 | (d) Single phase preventer suitable for 5HP to 15HP motor.Make : L&T, Havells, ABB, C&S |
| 138 | Replacement of MCCB 200 Amps 4 Pole 36 KA, Fixed Thermal and fixed magnetic setting fixed in existing panel and connected to told existing cable including necessary fixing arrangement lugs, glan etc complete including takiing down old all as specified and as directed.Make : Havells/ABB/LEGRAND/Standard |
| 139 | Replacement of MCCB 160 Amps 4 Pole 36 KA, Fixed Thermal and fixed magnetic setting fixed in existing panel and connected to told existing cable including necessary fixing arrangement lugs, glan etc complete including takiing down old all as specified and as directed.Make : Havells/ABB/LEGRAND/Standard |
| 140 | Replacement of MCCB 100 Amps 4 Pole 16 KA, Fixed Thermal and fixed magnetic setting fixed in existing panel and connected to told existing cable including necessary fixing arrangement lugs, glan etc complete including takiing down old all as specified and as directed.Make : Havells/ABB/LEGRAND/Standard |
| 141 | Replacement of MCCB 63 Amps 4 Pole 16 KA, Fixed Thermal and fixed magnetic setting fixed in existing panel and connected to told existing cable including necessary fixing arrangement lugs, glan etc complete including takiing down old all as specified and as directed.Make : Havells/ABB/LEGRAND/Standard |
| 142 | S&F MCB SPN 40 Amps \"C\" series 240V 50Hz 10 KA suitable for lighting and other domestic loads complete including taking down all as specified and directed.Make : Havells/ABB/LEGRAND/C&S |
| 143 | S&F MCB TPN 63 Amps \"C\" series 415V 50Hz 10 KA suitable for lighting and other domestic loads including taking downall as specified and directed.Make : Havells/ABB/LEGRAND/C&S |
| 144 | Earthing complete with GI earth plate electrode ofsize 600mm x 600mm x 6mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 32 x 6 mm size and earthing lead protected with 50 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1:3:6 type C-1using 20mm graded crushed stone aggregate in concrete pit pre-cast RCC 40 mm thickreinforced with 6 mm diaround at 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light gradewatering pipe and frame work complete all as shown in electrical plate No. 3 of SSR Part-I2009 including testing on completion complete all as specified and as directed. |
| 145 | Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 1.5 meter (BGL) connected to galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 15mm bore “light grade” galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion. |
| 146 | Cutting CI/DI pipes 100mm bore and reducing to required length before laying for insrting new CI specials such as Tees/Reducers/Tail ieces/collers/sluice valve/Air release valve etc. complete, all as specified and directed.(Note; CI specials and earthwork will be measured and paid seperately) |
| 147 | CI/DI specials for spigot and socket/flanged pipe upto 150mm dia of bore such as bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch \"Y\" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs complete, all as specified and directed. (The fitting shall be as per IS 1538-1989) |