| 1 | COST OF MATERIAL |
| 2 | Supply of 11.00 meters long R.C.C. Poleas per drawing No.CEE/E-698 Rev-2 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date.Ordinary Port land cement 53 grade: IS 12269Aggregate : IS 383-1970Torsteel : IS 1786-7985MS bar : IS 432 P 1&2-1982Erectionincludes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit ofSize 0.60 x 0.60 x 1.5 mts in any type of soil and back filling the pit after erection of the pole in pit by rubble and excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately ) |
| 3 | Supply of 9.0 meters long R.C.C. Pole as per drawing No.CEE/E-565 Rev-3 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date.Ordinary Port land cement 53 grade: IS 12269Aggregate : IS 383-1970Torsteel : IS 1786-7985MS bar : IS 432 P 1&2-1982Erectionincludes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit ofSize 0.60 x 0.60 x 1.5 mts in any type of soil classified under Soft Strata of Appendix A of CPWD-8 and back filling the pit after erection of the pole in pit by rubbleand excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately) |
| 4 | Supply of 7.5 meters long R.C.C. Poleas per drawing No.CEE/E-698 Rev-2 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date.Ordinary Port land cement 53 grade: IS 12269Aggregate : IS 383-1970Torsteel : IS 1786-7985MS bar : IS 432 P 1&2-1982Erectionincludes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit ofSize 0.60 x 0.60 x 1.5 mts in any type of soil and back filling the pit after erection of the pole in pit by rubble and excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately ) |
| 5 | Supply of HDGI stay rod with plate complete for for 7.5 m long RCC pole as per technical specification. ( Rubble is dealt seperately) |
| 6 | Supply of HDGI stay rod with plate complete for 11 mts. Long RCC pole as per technical specification ( Rubble is dealt seperately) |
| 7 | Supply of Enamelled danger board |
| 8 | Supply of Anticlimbing device made out of G.I. barbed wire of size 8SWG. |
| 9 | Supply of Hot dip galvanised DP structure material consisting of the following: a] Transformer bed channel ISMC of size 100 x 50 mm, 2.74 mts long, 2 pieces alongwith transformer belting angle ISA of size 50 x 50 mm, 2740mm long, 2 pieces alongwith side supports as per Drg No. EE/IV/DP/Bed-Ch for transformer.b] GOAB switch mounting channel ISMC of size 75 x 40 mm, 2740mm mts long, 2 pieces alongwith side supports as per Drg No. EE/IV/DP/GOAB CH for each GOAB switch.The work shall include all fabrication, drilling of holes, welding, cutting etc. The hot dip galvanisation shall be done only after fabrication work is completed.c] HG fuse mounting channel ISMC of size 75 x 40 mm, 2740mm mts long, 2 pieces alongwith Lightening Arrestors mounting angles ISA of size 50 x 50 mm, 2.74 mts long alongwith side supports as per Drg No EE/IV/DP/GOAB/HG-CH forHG fuse set.d] Intake Channel ISMC for mounting Disc Insulators of size 100 x 50 mm, 1 piece as per Drg No. Drg No. EE/IV/DP/INTAKE-CH . |
| 10 | Supply of 12 KV rated voltage GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part1 to V as amended upto date and detailed specifications.Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufactures of the insulators and have minimum 320mm creepage distance and AB switches contacts shall be of copper/copper alloy. The AB switch shall be of current rating 200 A. The isolators shall be as per technical specification. |
| 11 | Supply of 11 KV H.G. Fuse (set of three HG fuses) units 200 Amp as specified in DRg No CEE/E-786 |
| 12 | Supply of 9 KV, 5 KA nominal discharge current Metal Oxide gapless distribution class lightning arrestor conforming to IEC-60049-4 and IS 3070 Part 3 1993 as amended upto datesuitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arrangements and connector suitable to connect ACSR conductor upto overall diameter 12.30 mm. |
| 13 | Supply of HDGI S.A./L.A. cross arm clamps for 11 mts. Long RCC pole as per DRG No. EE-II/20/2008 |
| 14 | Supply of HDGI S.A./L.A. cross arm clamps for 9mts. Long RCC pole as per DRG No. EE-II/20/2009 |
| 15 | Supply of HDGI L.A./S.A. cross arm clamps suitable for 7.5 RCC pole as per Drg No. CEE/E-524. |
| 16 | Supply of MS Distribution Box alongwith 12nos. 200A Kit Kat fuse and MCCB of 200Amps, 415 Volts. The box shall be fabricated with MS sheet 12 gauge with overlapping rain proof slit ventilators on both sides of the distribution box with wire mesh to prevent entry of insects with pin head door hinges locking arrangement and shall have required number of bus bars made out of Aluminium strips of size 40 x 10mm for connecting MCCB, fuses and cables (for 4 feeder arrangement) & other accessories. The box shall also have \"magnetic hold\" arrangement to ensure that the box doors always remains in \"closed\" positiion when shut even without latching. |
| 17 | Supply of 100KVA, 11/0.433KV 3 PH. Aluminium Wound Distribution Transformer level-II |
| 18 | Supply of a) 11 KV brown glazed porcelain Pin Insulator with minimum failing load of 5 KN and the Minimum creepage distance of 320 mm conforming to IS 731-1971 as amended upto date & b) Forged G. I. Pin conforming to IS 2486 part 1 & 2 as amended upto date suitable for 11 KV glazed porcelain pin insulators conforming to IS: 731/71 as amended upto date. G. I pin shall conform to reference S-165 N fig. 5 of IS: 2486/ (part-II)/74 as amended upto date.Dimensions ‘X’ in said fig. shall be 150 mm (screwed 100 mm). Pin shall be supplied along with one suitable G. I. hexagonal nut and G. I. spring washer.Minimum failing load of pin shall be 10 KN. HT Porcelain insulator. |
| 19 | Supply of G.I. Earthing complete with 40mm GI Pipe, 2.5 mts long alongwith 20 kgs each salt, charcoal complete with brick masonary. |
| 20 | Supply ofACSR \" RACOON conductor of size6/1/2.59mm. The stringing rate includes transportation, jointing, jumpering with aluminium tape etc. 3.31 Kms of the conductor shall be used for stringing of 11 KV line, 0.28Kms for providing guarding and 0.25 Kms shall be used for jumpering on DP. The remaining 0.4 Kms of conductor shall be used for earthing of transformer centre which includes crimping of lugs and terminating the conductor to all the equipments of the DP with the lugs of appropriate size. The conductor shall be as per technical specification. |
| 21 | Supply of GI 4 pin LT cross arm channel typeThe 4pin cross arm shall be of 510mmlength & provided with a total of 4 holes of 22mm dia on each flange section. In addition two slotted holes of size 18 x 40 mm shall be provided on the cross arm for clamping arrangement to the pole. The 2pin side cross arm shall be of 800mm length & provided with a total of 4 holes of22mm dia on each flange section. In addition two slotted holes of size 18 x 40mm shall be provided on the left end of the cross arm for clamping arrangement to the pole.The cross arms shall be fitted vertically onto the top end of the poles, at a height conforming to the relevant I.E. rules & utilizing suitable size of HDGI clamps & HDGI washers, HDGI nut bolts. |
| 22 | Supply ofa) L.T. brown glazed porcelain pin insulators of size 100mm x 70mm conforming to type 1 fig 1 of IS:1445/1977 with amendment 2 of Feb.1981 (second revision) as amended upto date. Minimum failing load shall be 3.5kN &b) Forged G. I. Pin conforming to IS 7935/1975 as amended upto date suitable for L.T. porcelain pin insulator type 1 conforming to fig.1 of IS: 1445/77 with amendment No. 2, Feb.1981, of size 100 x 70 mm.G. I. pin shall comprise of G. I. nut and spring washer and conform to fig. No. 2 of IS: 7935/1975.Minimum failing load of pin shall be 3.5 KN. |
| 23 | Supply and Fixing ofa) L.T. brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN & b) G. I hardware suitable for L. T. shackle insulators of size 100 x 115 mm. conforming to type 2, fig. 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig. 4 of IS 7935-1975 as amended up to date, comprise of 2 G. I. strips, 2 G. I. bolts and 2 nuts with spring washers. |
| 24 | Supply of HDGI G.I. Hexagonal head bolts and hexagonal nuts conforming to IS 1363 part I to III 1992 as amended upto date of the size 3 ½\" x 5/8\" or 4\" x 5/8\",6\"x5/8\", 8\"x5/8\" |
| 25 | Providing of Low Tension metering to the DTC by Suplying of following Materials: Epoxy resin Cast L.T. CT coil of 300/5A, Class-0.5s, 50Hz,660V, Burden 15VA conforming to IS-2705 / 1992 as amended upto date (3 Nos)Electronic 3Phase,4wire ,Trivector Meter ,LT CT operated 3x240V,-/5A,50Hz, class 0.5s, Category \"A\" (DLMS COSEM Protocol) for DTC with RS 232 Optical port and complience to BIS ICS Doc: ETD 13(6211) and latest. (1 No)1.1KV multistand copper conductor 2.5sq.mm, XLPE insulated, armoured control cable conforming to relevant IS amended upto date.( 15 Mtr)Pole mounted M.S Box ( outdoor type) for Electronic Meter as Drawing No.EE/VIII/64(REV) (1 No)Al. L shape flat 40mm suitable for mounting on bushing rod and brass lug (3 Nos) |
| 26 | Supply of 35 sq.mmof single cores XLPE unarmoured Al conductor1.1KV grade power cable as per Technical Specification and as perIS:7098 (Part-I/1988) with latest ammendmentcarrying ISI mark. |
| 27 | Supply of 185sq.mmof single cores XLPE unarmoured Al conductor1.1KV grade power cable as per Technical Specification and as perIS:7098 (Part-I/1988) with latest ammendmentcarrying ISI mark. |
| 28 | Supply of Alluminium Crimping lug 185 sq.mmAluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminum of grade 1E of IS 5082-1969 suitable for aluminum cables of size 95/150/180 sq. mm. The cost of Aluminum lugs are inclusive in Supply, Erection, Testing, Commissioning of Single Core XLPE unarmored LT Power Cable/ACSR Conductor. |
| 29 | Supply of Alluminium Crimping lug 95 sq.mm Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminum of grade 1E of IS 5082-1969 suitable for ACSR Conductor to connectGOABswitch, earthing, H.G. fuses, transformer etc. |
| 30 | Supply of 11KV, 3 core, 120 sq.mm, Al conductor, XLPE, insulated, armoured cable |
| 31 | Supply of 11KV, 3 core, 95sq.mm, Al conductor, XLPE, insulated, armoured cable(from the RMU to the transformer) |
| 32 | Supply of 11KV 3 phase indoor terminating kit including sockets at RMU to be used with cables- 300sq.mm.including connection of cable armouring and screen to grounding system. |
| 33 | Supply of 11KV 3 phase indoor terminating kit including sockets at RMU to be used with cables- 120sq.mm.including connection of cable armouring and screen to grounding system. |
| 34 | Supply of 11KV 3 phase indoor terminating kit including sockets at RMU to be used with cables- 95sq.mm including connection of cable armouring and screen to grounding system. |
| 35 | Supply of 11KV 3 phase straight through jointterminating kit including sockets at 11KV end of DT to be used with cables as per - 120 sq.mm. including connection of cable armouring and screen to grounding system. |
| 36 | Supply of 11KV 3 phase outdoor terminating kit including sockets at 11KV end of DT to be used with cables as per - 95sq.mm. including connection of cable armouring and screen to grounding system. |
| 37 | Supply of 3 way RMU,11 KV, 630A, 21 KA 3 sec, SF6 outdoorRMU with 2 LBS & 1 VCB as per TS given below:Ring SW BreakersService current, Normal (A)630 A 200 ARated Voltage (KV peak) 11KV11 KVMaking capacity - Main / earth (KA) 46.5 KA46.5 KABreaking Capacity - Main / earth (KA)55/55 KA55/55 KAShort time Current - Main / earth (3 Sec) KA21.9/21.9 KA21.9/21.9 KA |
| 38 | Supply of Cable route Markers (for entire route length) |
| 39 | Warning tape |
| 40 | Supply of RCC Hume Pipe, 250mm dia with required no. of collars for road crossing. |
| 41 | Supply ofRiser GI pipe 150mm , class B |
| 42 | Supply and laying of sand for cushioning of the cables in the trench. |
| 43 | Providing and laying of \"RCC protecting covers\" ofsize 600mm length x 250mm width x 50mm thick capable of bearing load of 135 Kg. |
| 44 | Providing and laying in positioncement concrete 1:2:4 (1 cement:2 coarse sand :4 graded or basaltic stone aggregate 40 m nominal size for foundation of Ring Main Unit & poles |
| 45 | Centering Shuttering including struttings , propping etc and removal of form work for Ring Main Unit |
| 46 | Plastering of 12 mmcement plaster 1:4 (1 - cement: 4 - fine sand) for foundations of Ring Main Unit & poles |
| 47 | Supplyandlayingofburntclaywirecutbricksof75Kgs class.Wire cut bricks. |
| 48 | Cost of Erection |
| 49 | Erection of 11.00 meters long R.C.C. Poleas per drawing No.CEE/E-698 Rev-2 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date.Ordinary Port land cement 53 grade: IS 12269Aggregate : IS 383-1970Torsteel : IS 1786-7985MS bar : IS 432 P 1&2-1982Erectionincludes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit ofSize 0.60 x 0.60 x 1.5 mts in any type of soil and back filling the pit after erection of the pole in pit by rubble and excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately ) |
| 50 | Erection of 9.0 meters long R.C.C. Pole as per drawing No.CEE/E-565 Rev-3 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date.Ordinary Port land cement 53 grade: IS 12269Aggregate : IS 383-1970Torsteel : IS 1786-7985MS bar : IS 432 P 1&2-1982Erectionincludes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit ofSize 0.60 x 0.60 x 1.5 mts in any type of soil classified under Soft Strata of Appendix A of CPWD-8 and back filling the pit after erection of the pole in pit by rubbleand excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately) |
| 51 | Erection of 7.5 meters long R.C.C. Poleas per drawing No.CEE/E-698 Rev-2 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date.Ordinary Port land cement 53 grade: IS 12269Aggregate : IS 383-1970Torsteel : IS 1786-7985MS bar : IS 432 P 1&2-1982Erectionincludes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit ofSize 0.60 x 0.60 x 1.5 mts in any type of soil and back filling the pit after erection of the pole in pit by rubble and excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately ) |
| 52 | Erection of HDGI stay rod with plate complete for for 7.5 m long RCC pole as per technical specification. ( Rubble is dealt seperately) |
| 53 | Erection of HDGI stay rod with plate complete for 11 mts. Long RCC pole as per technical specification ( Rubble is dealt seperately) |
| 54 | Erection of Enamelled danger board |
| 55 | Erection/fixing of Anticlimbing device made out of G.I. barbed wire of size 8SWG. |
| 56 | Erection, Fabrication, Transportation of Hot dip galvanised DP structure material consisting of the following:a] Transformer bed channel ISMC of size 100 x 50 mm, 2.74 mts long, 2 pieces alongwith transformer belting angle ISA of size 50 x 50 mm, 2740mm long, 2 pieces alongwith side supports as per Drg No. EE/IV/DP/Bed-Ch for transformer.b] GOAB switch mounting channel ISMC of size 75 x 40 mm, 2740mm mts long, 2 pieces alongwith side supports as per Drg No. EE/IV/DP/GOAB CH for each GOAB switch.c] HG fuse mounting channel ISMC of size 75 x 40 mm, 2740mm mts long, 2 pieces alongwith Lightening Arrestors mounting angles ISA of size 50 x 50 mm, 2.74 mts long alongwith side supports as per Drg No EE/IV/DP/GOAB/HG-CH forHG fuse set.d] Intake Channel ISMC for mounting Disc Insulators of size 100 x 50 mm, 1 piece as per Drg No. Drg No. EE/IV/DP/INTAKE-CH.The work shall include all fabrication, drilling of holes, welding, cutting etc. The hot dip galvanisation shall be done only after fabrication work is completed. |
| 57 | Transportation & Erection of 12 KV rated voltage GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part1 to V as amended upto date and detailed specifications.Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufactures of the insulators and have minimum 320mm creepage distance and AB switches contacts shall be of copper/copper alloy. The AB switch shall be of current rating 200 A. The isolators shall be as per technical specification. |
| 58 | Erection/Fixing of 11 KV H.G. Fuse (set of three HG fuses) units 200 Amp as specified in DRg No CEE/E-786 |
| 59 | Erection/Fixing of 9 KV, 5 KA nominal discharge current Metal Oxide gapless distribution class lightning arrestor conforming to IEC-60049-4 and IS 3070 Part 3 1993 as amended upto datesuitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arrangements and connector suitable to connect ACSR conductor upto overall diameter 12.30 mm. |
| 60 | Erection/Fixing of HDGI S.A./L.A. cross arm clamps for 11 mts. Long RCC pole as per DRG No. EE-II/20/2008 |
| 61 | Erection/Fixing of HDGI S.A./L.A. cross arm clamps for 9mts. Long RCC pole as per DRG No. EE-II/20/2009 |
| 62 | Erection/Fixing of HDGI L.A./S.A. cross arm clamps suitable for 7.5 RCC pole as per Drg No. CEE/E-524. |
| 63 | Erection & Commissioning of MS Distribution Box alongwith 12nos. 200A Kit Kat fuse and MCCB of 200Amps, 415 Volts. The box shall be fabricated with MS sheet 12 gauge with overlapping rain proof slit ventilators on both sides of the distribution box with wire mesh to prevent entry of insects with pin head door hinges locking arrangement and shall have required number of bus bars made out of Aluminium strips of size 40 x 10mm for connecting MCCB, fuses and cables (for 4 feeder arrangement) & other accessories. The box shall also have \"magnetic hold\" arrangement to ensure that the box doors always remains in \"closed\" positiion when shut even without latching. |
| 64 | Erection, Testing & Commissioning (SETC) of 100KVA, 11/0.433KV 3 PH. Aluminium Wound Distribution Transformer level-II |
| 65 | Erection of a) 11 KV brown glazed porcelain Pin Insulator with minimum failing load of 5 KN and the Minimum creepage distance of 320 mm conforming to IS 731-1971 as amended upto date & b) Forged G. I. Pin conforming to IS 2486 part 1 & 2 as amended upto date suitable for 11 KV glazed porcelain pin insulators conforming to IS: 731/71 as amended upto date. G. I pin shall conform to reference S-165 N fig. 5 of IS: 2486/ (part-II)/74 as amended upto date.Dimensions ‘X’ in said fig. shall be 150 mm (screwed 100 mm). Pin shall be supplied along with one suitable G. I. hexagonal nut and G. I. spring washer.Minimum failing load of pin shall be 10 KN. HT Porcelain insulator. |
| 66 | Erection of G.I. Earthing complete with 40mm GI Pipe, 2.5 mts long alongwith 20 kgs each salt, charcoal complete with brick masonary. |
| 67 | Erection/Stringing ofACSR \" RACOON conductor of size6/1/2.59mm. The stringing rate includes transportation, jointing, jumpering with aluminium tape etc. 3.31 Kms of the conductor shall be used for stringing of 11 KV line, 0.28Kms for providing guarding and 0.25 Kms shall be used for jumpering on DP. The remaining 0.4 Kms of conductor shall be used for earthing of transformer centre which includes crimping of lugs and terminating the conductor to all the equipments of the DP with the lugs of appropriate size. The conductor shall be as per technical specification. |
| 68 | Erection of GI 4 pin LT cross arm channel typeThe 4pin cross arm shall be of 510mmlength & provided with a total of 4 holes of 22mm dia on each flange section. In addition two slotted holes of size 18 x 40 mm shall be provided on the cross arm for clamping arrangement to the pole. The 2pin side cross arm shall be of 800mm length & provided with a total of 4 holes of22mm dia on each flange section. In addition two slotted holes of size 18 x 40mm shall be provided on the left end of the cross arm for clamping arrangement to the pole.The cross arms shall be fitted vertically onto the top end of the poles, at a height conforming to the relevant I.E. rules & utilizing suitable size of HDGI clamps & HDGI washers, HDGI nut bolts. |
| 69 | Erection ofa) L.T. brown glazed porcelain pin insulators of size 100mm x 70mm conforming to type 1 fig 1 of IS:1445/1977 with amendment 2 of Feb.1981 (second revision) as amended upto date. Minimum failing load shall be 3.5kN &b) Forged G. I. Pin conforming to IS 7935/1975 as amended upto date suitable for L.T. porcelain pin insulator type 1 conforming to fig.1 of IS: 1445/77 with amendment No. 2, Feb.1981, of size 100 x 70 mm.G. I. pin shall comprise of G. I. nut and spring washer and conform to fig. No. 2 of IS: 7935/1975.Minimum failing load of pin shall be 3.5 KN. |
| 70 | Erection/Fixing ofa) L.T. brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN & b) G. I hardware suitable for L. T. shackle insulators of size 100 x 115 mm. conforming to type 2, fig. 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig. 4 of IS 7935-1975 as amended up to date, comprise of 2 G. I. strips, 2 G. I. bolts and 2 nuts with spring washers. |
| 71 | Erection/Fixing of HDGI G.I. Hexagonal head bolts and hexagonal nuts conforming to IS 1363 part I to III 1992 as amended upto date of the size 3 ½\" x 5/8\" or 4\" x 5/8\",6\"x5/8\", 8\"x5/8\" |
| 72 | Erection of Low Tension metering to the DTC by Suplying of following Materials:Epoxy resin Cast L.T. CT coil of 300/5A, Class-0.5s, 50Hz,660V, Burden 15VA conforming to IS-2705 / 1992 as amended upto date (3 Nos)Electronic 3Phase,4wire ,Trivector Meter ,LT CT operated 3x240V,-/5A,50Hz, class 0.5s, Category \"A\" (DLMS COSEM Protocol) for DTC with RS 232 Optical port and complience to BIS ICS Doc: ETD 13(6211) and latest. (1 No)1.1KV multistand copper conductor 2.5sq.mm, XLPE insulated, armoured control cable conforming to relevant IS amended upto date.( 15 Mtr)Pole mounted M.S Box ( outdoor type) for Electronic Meter as Drawing No.EE/VIII/64(REV) (1 No)Al. L shape flat 40mm suitable for mounting on bushing rod and brass lug (3 Nos) |
| 73 | Erection of 35 sq.mmof single cores XLPE unarmoured Al conductor1.1KV grade power cable as per Technical Specification and as perIS:7098 (Part-I/1988) with latest ammendmentcarrying ISI mark. |
| 74 | Erection of 185sq.mmof single cores XLPE unarmoured Al conductor1.1KV grade power cable as per Technical Specification and as perIS:7098 (Part-I/1988) with latest ammendmentcarrying ISI mark. |
| 75 | Erection of Alluminium Crimping lug 185 sq.mmAluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminum of grade 1E of IS 5082-1969 suitable for aluminum cables of size 95/150/180 sq. mm. The cost of Aluminum lugs are inclusive in Supply, Erection, Testing, Commissioning of Single Core XLPE unarmored LT Power Cable/ACSR Conductor. |
| 76 | Erection of Alluminium Crimping lug 95 sq.mm Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminum of grade 1E of IS 5082-1969 suitable for ACSR Conductor to connectGOABswitch, earthing, H.G. fuses, transformer etc. |
| 77 | Erection of 11KV, 3 core, 120 sq.mm, Al conductor, XLPE, insulated, armoured cable |
| 78 | Erection of 11KV, 3 core, 95sq.mm, Al conductor, XLPE, insulated, armoured cable(from the RMU to the transformer) |
| 79 | Erection of 11KV 3 phase indoor terminating kit including sockets at RMU to be used with cables- 300sq.mm.including connection of cable armouring and screen to grounding system. |
| 80 | Erection of 11KV 3 phase indoor terminating kit including sockets at RMU to be used with cables- 120sq.mm.including connection of cable armouring and screen to grounding system. |
| 81 | Erection of 11KV 3 phase indoor terminating kit including sockets at RMU to be used with cables- 95sq.mm including connection of cable armouring and screen to grounding system. |
| 82 | Erection of 11KV 3 phase straight through jointterminating kit including sockets at 11KV end of DT to be used with cables as per - 120 sq.mm. including connection of cable armouring and screen to grounding system. |
| 83 | Erection of 11KV 3 phase outdoor terminating kit including sockets at 11KV end of DT to be used with cables as per - 95sq.mm. including connection of cable armouring and screen to grounding system. |
| 84 | Erection of 3 way RMU,11 KV, 630A, 21 KA 3 sec, SF6 outdoorRMU with 2 LBS & 1 VCB as per TS given below:Ring SW BreakersService current, Normal (A)630 A 200 ARated Voltage (KV peak) 11KV11 KVMaking capacity - Main / earth (KA) 46.5 KA46.5 KABreaking Capacity - Main / earth (KA)55/55 KA55/55 KAShort time Current - Main / earth (3 Sec) KA21.9/21.9 KA21.9/21.9 KA |
| 85 | Erection/Installation of Cable route Markers (for entire route length) |
| 86 | Erection of RCC Hume Pipe, 250mm dia with required no. of collars for road crossing. inclusive of erection |
| 87 | Erection ofRiser GI pipe 150mm , class B |
| 88 | Excavation of pit of sizes (0.60 x 1.10 x 60 )mts in any type of soil for laying of 11KV cable of sizes3 core 120sq.mm . |
| 89 | Excavation of pit of sizes (0.60 x 1.10 x 60 )mts in all type of ordinary rock including all type of laterite rocks of3 core, 120sq.mm . Hard Rock |
| 90 | Filling of available excavated earth (excluding rock/stones) in trench, plinth, sides, foundations etc. in layer not exceeding 0.3mts. Depth consolidating each deposited layer by ramming and watering lead up to 25mts. |
| 91 | Laying of \"RCC protecting covers\" ofsize 600mm length x 250mm width x 50mm thick capable of bearing load of 135 Kg. |