| 1 | Excavation in trenches n.exc1.5 M wideand n.exc 1.5 M depth and getting outfor laying of underground cable etc in any type of soil complete all as specified and directed Engineer-in-Charge. |
| 2 | Returning, filling in, including spreading,levelling watering and well ramming in layers n.exc 25 cm thick in any type of soil complete all as specified and directed by Engineer-in-Charge. |
| 3 | Removing of excavated soil to a distance n.exc 50 metre and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed Engineer-in-Charge. |
| 4 | Supply and Laying of bricks well burnt sub class B (old size) laid flat for cable protection width equal to the length of bricks complete all as specified and directed by Engineer-in-Charge. |
| 5 | Laying Only of bricks retrieved from items no. 10.00here-in-before laid flat for cable protection width equal to the length of bricks complete all as specified and directed by Engineer-in-Charge. |
| 6 | M&L for dry & clean sand cushioning in trenches spreading and consolidation 8 cm thick before laying the cable and 15 cm of sand after laying the cable and punned the same up 18 cm complete all as specified and directed by Engineer- in-Charge.Note:- Only punned thickness shall be measured and paid. |
| 7 | M&L for cutting of existingroad surfaces up 100 mm deep & 300 mm wide and making good disturbed portion with 100mm thick plain cement concrete 1:2:4 type B-1 (using 40mm graded crushed stone aggregate) complete all as specified and directed by Engineer-in-Charge. |
| 8 | S&F 80 mm dia bore mild steel galvanized iron tubes, \"light grade\" with all fitting and laid in trenches or fixed to pole or laid in floors for protection of cable complete all as directed. |
| 9 | S&F 50 mm dia bore mild steel galvanized iron tubes, \"light grade\" with all fitting and laid in trenches or fixed to pole or laid in floors for protection of cable complete all as directed. |
| 10 | Taking out carefully unserviceable LT under ground cable of following size from trenches / Pipes including taking out bricks, complete all as specified and as directed by Engineer-in-Charge. (Serviceable Bricks obtained shall be cleaned and stacked properly for reuse) |
| 11 | (i) 10 Sqmm, 2 Core |
| 12 | (ii) 16 Sqmm, 2 core |
| 13 | (iii) 16 Sqmm, 4 core |
| 14 | (iv) 25 Sqmm, 3.5 core |
| 15 | (v) 35 Sqmm, 3.5 core |
| 16 | (vi) 50 Sqmm, 3.5 core |
| 17 | (vii) 70 Sqmm, 3.5 core |
| 18 | (viii) 95 Sqmm, 3.5 core |
| 19 | (ix) 120 Sqmm, 3.5 core |
| 20 | (x) 150 Sqmm, 3.5 core |
| 21 | Supply & lay XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable ISI marked with aluminium conductor 1100 volt grade of following size laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified & directed.Note:-Earthwork, sand cushion, cable cover if required will be measured and paid separately under respective items of this Schedule. |
| 22 | (i) 10 Sqmm, 2 Core |
| 23 | (ii) 16 Sqmm, 2 core |
| 24 | (iii) 16 Sqmm, 4 core |
| 25 | (iv) 25 Sqmm, 3.5 core |
| 26 | (v) 35 Sqmm, 3.5 core |
| 27 | (vi) 50 Sqmm, 3.5 core |
| 28 | (vii) 70 Sqmm, 3.5 core |
| 29 | (viii) 95 Sqmm, 3.5 core |
| 30 | (ix) 120 Sqmm, 3.5 core |
| 31 | (x) 150 Sqmm, 3.5 core |
| 32 | Laying only XLPE insulated, PVC inner sheathed, armoured, LT underground cable of following size laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified & directed.Note:-(i) Cable shall be issued under Schedule B (Free for fixing)(i) Earthwork, sand cushion, cable cover if required will be measured and paid separately under respective items of this Schedule. |
| 33 | (i) 10 Sqmm to 50 Sqmm |
| 34 | (ii) 70 Sqmm to 150 Sqmm |
| 35 | Supply, installation testing & commissioning, CPRI Approved LT panel cubical type of size 0.9 x 0.6 x 0.6 Metre, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, outdoor type, factory fabricated, duly powder coated inside and out side, outer cover made out of 3.15 mm thick CRCA sheet, internal cover and partitionmade out of 2 mm thickCRCAsheet with angle iron 40 mm x 40 mm x 6 mm and 0.5 m long covered from all side with front and back openable, dust, vermin and weather proof including suitable rating Copper bus bar for 3 phase 4 wire system, wiring with suitable size coppercable and embedded in brickwork withnuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and asdirected by Engineer-in-Charge. |
| 36 | Incoming:-(a)MCCB 4 pole,100 Amp, 35 KA, 415 volts AC with adjustable thermal and adjustable magnetic setting- 01 No.(b) Copper bus bar 150 Amp TPN - 04 No\"s(c) Digital voltmeter 0-500 volts with selector switch - 01 No(d) Digital Amp meter0-200 Amp with selector switch & CT - 01 No(e) Indicator lamp LED type (R, Y, B) complete with Bakelite fuse fitting - 01 SetOutgoing:-(a) MCCB 4 pole, 63 Amp, 16 KA, 415 volts AC- 03 No\"s, |
| 37 | Note: LT panel board shall be mounted on brickwork in CM 1:4 not less than 60 cm above ground level and 30 cm below ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate. |
| 38 | Taking down unserviceable light fitting any type from Pole / wall or any other location any capacity ,any height, any situation, repairs to the extent by removing connections from the system, checking of unserviceable spare parts and serviceable parts, replacement of unserviceable parts with new spares and testing complete, tightening the loose connection and made item functional, reassembling the fitting and re-fixing / re-hanging the same after repair in existing location or other location (as directed) and testing complete all as specified and directed by Engineer-in-Charge.Note:- (i) Spares required for repair will be measured and paid separately as supply only vide item No 15 to 18 here-in-after.(ii) Necessary T & P like ladder / Boom Vehicle, tools etc as required for taking down & fixing of Street light shall be provided by contractor without any extra cost of department. |
| 39 | Supply only LED driver of capacity 30/45 Watt suitable for 240 volts complete all as specified and directed Engineer-in-Charge. |
| 40 | Supply only LED driver of capacity 50/60 Watt suitable for 240 volts complete all as specified and directed Engineer-in-Charge. |
| 41 | Supply only LED driver of capacity 100 Watt suitable for 240 volts complete all as specified and directed Engineer-in-Charge. |
| 42 | Supply only LED driver of capacity 150 Watt suitable for 240 volts complete all as specified and directed Engineer-in-Charge. |
| 43 | S&F in repairs LED street Light fitting 60 Watt, system efficiency not less than 110 lumen / watt, IP66 protection,consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with weather proof gasket for lamp & driver compartment, fitted in cast aluminium housing with SS screws fixed on existing bracket & connecting, complete. |
| 44 | M&L for preparation of old painted steel surface of LT feeder pillar Box, 440 Volts, 3 phase of any size / location and applying two coats of synthetic enamel paint complete all as specified and directed Engineer-in-Charge. |
| 45 | M&L for Sub main wiring for connecting street light fitting from junction box with two single core, PVC insulated, (ISI marked) , unsheathed, 1100 volts grade, 2.5 Sqmm multistranded copper conductor cable drawn into and including suitable size PVC conduit 20 mm dia ISI marked medium grade with all accessories and including one single core, 2.5 Sqmm PVC insulated multistranded unsheathed 1100 volts grade copper conductor cable as earth wire including taking down old pipe & cable complete all as directed & specified.Note:2 Runs of main cable and one run earth wire with conduit will be measured as one RM for payment. |
| 46 | Supply, installation testing & commissioning bus bar chamber, factory made, weather and vermin proof having size 200 x 250 x 80 mm made out of 3.15 mm thick CRCA sheet, comprising of MCB SP 10A, C curve 10 KA breaking capacity 01 No\"s, 16 Amp 230 volt rated aluminium bus bar with mounting rail fixed on porcelein insulator, making holes on strips for connecting cables and fixing of bus bar chamber on street light pole with and including MS clamp of size 25 x 5mm including nut, bolts washers duly painted with 2 coats of enamel paint over a coat of red oxide primer including taking down old bus bar chamber, all as specified and directed. |
| 47 | Supply and fix in repair LED, post top lantern, 20 Watt, 230 volts AC, out door type, with decorative post 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp fixed over existing pole complete |
| 48 | Material and labour in repair for earthing complete with galavanised steel earth plate electrode of size 60mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below gound level with top edge of the earth plate not less than 1.5 m below normal gound level connected to galvanised steel earth strip of size 32x6 mm by means of bolts, nuts, check nuts and washers of galavanised iron/steel and conneted to main control board as directed and including proivison of concrete pit in PCC (1:2:4) type B1 pre cost RCC earth pit cover reinforced with 8 mm dia TMT bars @ 150mmc/c of size 54cmx54cmx8cm with two handle for lifting made out of 8mm dia MS bar, provision of funnel, wire mesh, 20mm bore galavanised steel tubing (med grade) for watering. Charcoal 250 Kg and salt 200 Kg in alternate layers, 40mm bore galavanised steel tubing light grade for protection of earth lead connection including necessary excavation and earth work and testing complete all as shown on electrical plate No 3 of SSR Part-I. |
| 49 | Note : Earth strip and protection pipe upto 7.5m is included in the unit rate of this item. Contractor shall quote his rate accordingly. |
| 50 | Material and labour in repair for earthing complete with copper earth plate electrode of size 60mm x 600mm x 3mm thick buried directly in ground (earth pit not less than 2.25m deep below gound level with top edge of the earth plate not less than 1.5 m below normal gound level connected to copper earth strip of size 20x3mm by means of bolts, nuts, check nuts and washers of copper and conneted to main control board as directed and including proivison of concrete pit in PCC (1:2:4) type B1, pre cost RCC earth pit cover reinforced with 8 mm dia TMT bars @ 150mmc/c of size 54cmx54cmx8cm with two handle for lifting made out of 8mm dia MS bar, provision of funnel, wire mesh, 20mm bore galavanised steel tubing (med grade) for watering. Charcoal 250 Kg and salt 200 Kg in alternate layers, 40mm bore galavanised steel tubing light grade for protection of earth lead connection including necessary excavation and earth work and testing complete all as shown on electrical plate No 3 of SSR Part-I |
| 51 | Note : Earth strip and protection pipe upto 7.5m is included in the unit rate of this item. Contractor shall quote his rate accordingly. |
| 52 | S&F in repair timer distribution board with analog time switches complete of rating 65 Amps 3 pole 230 Volts 415 voltincluding taking down existing complete all as specified and directed by Engr in charge.Make :- Indoasian Cat part No. TL065ABO or equivalent cat No of Make C&S/ HPL / Havells |
| 53 | M&L for paintingof steel tubular poles of hight 7 to 7.50meter above GL with cross arms and bracings with two coat of aluminium paint painting, including 30 cm wide black & white alternate strips up to 1.5 metre above from ground level with synthetic enamel paint incl numbering of the pole complete all as specified and directed. |
| 54 | Supply & fix Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one coat red oxide primer, two coats aluminium paint including taking down old cross arm complete. |
| 55 | Supply stretching and fixing in position Aluminium conductor, steel reinforced (ACSR), of any size for overhead LT line with and including binding wire 14 SWG (aluminium ) for jumpers including taking down old conductor complete all as specified and directed by Engineer-in-Charge |
| 56 | Restretching / re fixing the existing LT OH / Lines ACSR conductor of any type and size including disconnecting binding wire on insulator, rebinding properly to avoid tension / fitting bending of poles, complete all as specified and directed by Engrr-in-Charge.Note:- Each line of conductor will be measured & paid separately. |
| 57 | Supply and filling transformer oil confirming to IS-335183 having dielectricstrength upto 50 KV at 4 mm gap for topping up in transformer complete |
| 58 | Dismantling old u/sinsulators of sizes, any type from pole. |
| 59 | Supply & fix pin type, porcelain, vitreous, white / brown / green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised nut, 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and directed by Engr-in-charge. |
| 60 | Supply & fix pin type, porcelain, vitreous, white / brown / green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised nut, 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and directed by Engr-in-charge. |
| 61 | Supply & fix disc type, porcelain, vitreous white / brown / green insulator including one galvanised mild steel straps washers insulator bolts, washers , nut, 145 mm height, 255 mm dia for 11000 volts grade complete all as specified and directed by Engr-in-charge. |
| 62 | Supply & fix shakle type, porcelain, vitreous, white / brown / green insulator including one galvanised mild steel straps washers insulator bolts, washers , nut, 100 mm height, 115 mm dia for 1100 volts grade complete all as specified and directed by Engr-in-charge. |
| 63 | Supply and fix in repair stay assembly for LT pole complete with accessories as shown in Electrical Plate No 1 (Dia of stay rod 16 mm) complete all as specified and directed by Engr-in-charge. |
| 64 | M&L for PCC 1:4:8 type D-2, using 40 mm graded stone aggregate as in foundation footing / mass concrete etc complete all as spd and directed. |
| 65 | S&F in repair MCCB 4 pole415 volts microprocessor release type 400 amps with breaking capacity 36 KA, complete all as specified and directed. |
| 66 | S&F in repair MCCB 4 pole415 volts microprocessor release type 250 amps with breaking capacity 36 KA, complete all as specified and directed. |
| 67 | S&F in repair MCCB 4 pole415 volts microprocessor release type 200 amps with breaking capacity 36 KA, complete all as specified and directed. |
| 68 | S&F in repair MCCB 4 pole415 volts microprocessor release type 160 amps with breaking capacity 36 KA, complete all as specified and directed. |
| 69 | S&F in repair MCCB 4 pole415 volts fixed type 100 amps with breaking capacity 16 KA, complete all as specified and directed. |
| 70 | S&F in repair MCCB 4 pole415 volts fixed type 63 amps with breaking capacity 16 KA, complete all as specified and directed. |
| 71 | M&L in replacement of Feeder pillar board kiosk type, LT (415 Volts, 50 Hz, 3 Phase, 4 wire supply) floor mounted, factory assembled, outdoor type weather and vermin proof (Protection class IP-54) made out and 3.15mm thick MS sheet CRCA sheet aluminiumbus bar of 200 Amps capacity with hingedopening, rubber lining , lockingarrangement,minimum 3 outgoings, painted externally and internally with two coats of synthetic enemel gray paint first quality ovar a coat of red oxide primer complete. |
| 72 | (a)MCCB4 Pole , 200 Amps, rupturing capacity 25 kA, 440 Volts, adjustable type - 01 Nos as incoming |
| 73 | (b)MCCB3 Pole , 63 Amps, rupturing capacity 16 kA, 440 Volts, adjustable type - 02 Nos as outgoing |
| 74 | (c)MCCB3 Pole , 25 Amps, rupturing capacity 10 kA, 440 Volts, adjustable type - 02 Nos as outgoing |
| 75 | (d)MCBSPN 10 Amps, rupturing capacity 10 KA, 240 Volts - 05 Nosas outgoing |
| 76 | (e) Indicator LED phase lamps 03 Nos (R, Y, B) - 01 Set |
| 77 | (f)Volt meter 0-500 Volts with selector switch - 01 No |
| 78 | (g)Ammeter 0 - 300A with selector switch with CTs - 01 No |
| 79 | (h)Platform for the feeder pillar board with PCC 1:2:4, 15CM thick in foundation , brick (sub class B) work in CM 1:6, redering 1:6 on exposed surfaces and 100mm thick PCC 1:3:6 type C1 using 20mm graded stone aggregate as in padding on top and grouting legs of panel.The platform shall be 450mm height above the ground level. |
| 80 | Supply and fixingin replacement of GI Bracket made of40mm dia GI pipe medium grade 1.5mtr longsuitable for street light for steel / RCC poleas per site requirement includingsuitable nut, bolt, washers and clamps complete all as specified and directed by Engineer-in-Charge |
| 81 | S&F in replacement of PVC seperator suitable for1100V four ACSR Conductor feeder complete all as specified and directed by Engineer-in-Charge |
| 82 | M&L for maintenance of gang operated air break isolators switch out door type 9 / 12 insulators double stack, triple pole, rotating type double break per pole for 11000 volts, 3 phase, 50 Hz, AC supply system having 200 / 400 Amps capacity by oiling, greasing, adjustment of lever and making the same smooth functional complete all as specified.complete all as specified and directed |
| 83 | Dismantlingchain link fencing fixed with steel fillets & nut bolt etc, of any type complete all as specified |
| 84 | Supply only chain link fencing 4 mm dia galvanized steel wire aperture of size as directed, made up into mattresses or cages lapped wired conforming to IS 2721 all as specified & directed.Note:-Fixing only fencing will be measured and paid separately. |
| 85 | Fixing only chain link fencing of description fixed to steel post with mild steel flat & nut bolt etc.Note: (i) Supply only fencing, will be measured and paid separately.(ii) Supply and fix mild steel nut bolt, line wire and flat will be measured and paid separately. |
| 86 | Supplying and fixing in replacementmale contact/moving contact for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge. |
| 87 | Supplying and fixing in replacement female contact /fix contact jawfor gang operated air break device 11 KVcomplete all as directed at site by Engr-in-charge. |
| 88 | M&L in replacement of Air break gang operated switch with 12 Nos insulators outdoor type, triple pole, mechanically operated, suitable for vertical installation, single break, provided with locking arrangement, consisting of MS Channel, HT post type insulator copper alloy, high pressure, assembly drop out fuses, operating rod 25mm dia GI pipe, medium grade for operating from 1.2 m above GL complete including drop out fuses conforming to IS rated voltage 11 KV and for current rating 200 Amp all as specified. Make:BHEL, PACTIL OBLUM, ABB |
| 89 | Material and labour for sprading of stone aggregate of nominal size not more than 25mm under 4/6 pole HT structure /surounding area of outdoor RMUmanually without damaging any equipments, cable or parts , spreading & levelling of finished gravel uniformaly in layers n. ecc. 15 cm thick watered and rammed to true surface including surface excavation and removal complete all as specified and directed. |
| 90 | M & L in replacement of Anti climbing devices spikes type fabricated out of MS bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed by Engr-in-Charge. |
| 91 | M & L in replacement of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as specified and directed by Engr-in-Charge. |
| 92 | Supply and fixing in replacement of LT feeder pillar boxoutdoor type factory made weather and vermin proof made out from 3.15 mm sheet supported with legs 45 cm long made of angle iron 50x50x5 mm of size 1.2 mtrx1 mtrx1 mtr with 3 Nos 0.8mtr Aluminium bus bar of size 40x10mm or 400 Amps for 1100 Volt post Insulator 08 Nos duly drilled hole forLT Cable connection including front and rear side openable with locking arrangment suitable for 1100 V LT and provision for incoming and out going LT cable connection including painting with two coats of smoke gray synthetic enamels paint over a coat of red oxide primer complete |
| 93 | Note:- Feeder piller box shall be mounted on brick plate form built in (1:4) not less then 60 cm above ground level with suitable PCC foundation rendering 15 mm in CM (1:6), applying two coats and cement base paints and supported on 04 nos angle iron with concrete base. |
| 94 | Supply and fixing in replacement of LT feeder pillar boxoutdoor type factory made weather and vermin proof made out from 3.15 mm sheet supported with legs 45 cm long made of angle iron 50x50x5 mm of size 1.2 mtrx1 mtrx1 mtr with 3 Nos 0.8mtr Aluminium bus bar of size 40x8 mm or 200 Amps for 1100 Volt post Insulator 08 Nos duly drilled hole forLT Cable connection including front and rear side openable with locking arrangment suitable for 1100 V LT and provision for incoming and out going LT cable connection including painting with two coats of smoke gray synthetic enamels paint over a coat of red oxide primer complete |
| 95 | Note:- Feeder piller box shall be mounted on brick plate form built in (1:4) not less then 60 cm above ground level with suitable PCC foundation rendering 15 mm in CM (1:6), applying two coats and cement base paints and supported on 04 nos angle iron with concrete base. |