| 1 | Supply, installing, testing and commissioning, factory made and tested ,CPRI type testedLTfeeder pillar, outdoortype floor mounted ,suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated The panel shall be dust and vermin proof, IP 65 class protection and made of3.15 mm CRCA MS sheet and LT panel shall bemounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hightand fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels,powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,both side openingtype, with aprons for cable entry,with double door shutter and locking arrangement and consisting of the followingall as specified including taking out oldfeeder pillar and taking out LT cable from loop for connecting in new panel and necessary excavation etc and consisting of the following |
| 2 | (a) Aluminiumbus barfour Nos500 Amps each ,fixed on epoxy insulated with panel fixed horizontally, duly insulatedwithheat shrinkable sleeves in colour code - 04 NosIncoming:-(b) MCCB,04 Pole, 250 Amps with ultimate breaking capacity Icu- 50 KA at 415 volts , adjustable type with thermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I- 01 No(Ics=Icu=100%)Outgoing:-(c) MCCB,04 Pole, 100 Amps with ultimate breaking capacity Icu- 25 KA at 415 volts , adjustable type with thermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I- 04 No(Ics=Icu=100%)(d)Spare way for MCCB 125 Amp 4 pole - 01 Nos |
| 3 | (e) Digital type volt meter 0-500 volt with selector switch withHRC fuses/ MCBs - 1Set.(f) Digital type ammeter meter 400 Amp with selector switch withHRC fuses/ MCBs - 1Set.(g) LED phase indication lamps R,Y,BLEDtype with 3 Nos of 2A HRC Fuses – 1 set:-(h) Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminumstrips for MCCB\"s/SDFU.(j) Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 mm thick in foundation, brick work in CM 1:6 with sub class B old sized bricks, renderung 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 50cm above the nearest ground level.Note :- Panel drawings & make of MCCB will be submitted by contractor for approval from Accepting Officer before ordering the panel |
| 4 | S&F & testing commissioning of outdoor type bus bar panel pedestal type weather proof CPRI approved MS cubical panelboard outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos ofbus bar of 300 Amp capacity & MCCB 160 Amp capacity 4 pole (Ics = Icu = 100%) including one coat of red oxide and two coat of enamel paint powder coated, mounted on channels and PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. The panel shall be fixed over Angle iron frame (50 x 50 mm) of minimum height 75 cmNote :- Panel drawings & make of MCCB will be submitted by contractor for approval from Accepting Officer before ordering the panel |
| 5 | Supply, laying & testing in repalcement cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100V grade with stranded aluminium conductor of size 120 sqmm 3.5 core including taking down of old unserviceable UG cable/service wires.Make :- Havells/KEI/Polycab |
| 6 | Description all as per item No 05 above but of size 95 Sqmm 3.5 core |
| 7 | Description all as per item No 05 above but of size 70 Sqmm 3.5 core |
| 8 | Description all as per item No 05 above but of size 50 Sqmm 3.5 core |
| 9 | Description all as per item No 05 above but of size 35 Sqmm 3.5 core |
| 10 | Description all as per item No 05 above but of size 25 Sqmm 4 core |
| 11 | Description all as per item No 05 above but of size 25 Sqmm 2 core |
| 12 | Description all as per item No 05 above but of size 16 Sqmm 4 core |
| 13 | Description all as per item No 05 above but of size 16 Sqmm 2 core |
| 14 | Description all as per item No 05 above but of size 10 Sqmm 2 core |
| 15 | Supply, laying & testing in repalcement cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100V grade with stranded aluminium conductor of size 300 sqmm single core including taking down of old unserviceable UG cable/service wires.Make :- Havells/KEI/Polycab |
| 16 | Excavationin trenches in any type of soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out hard & densile soil complete all as specified and as directed. |
| 17 | Returning fitting in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed. |
| 18 | Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed. |
| 19 | M & L for laying of fine, clean sand (river sand) free from sharp materials and stone particalsin trenches for cushioning of cable 8 cm thick under cable and 15 cm thick over the cable including gently punning complete all as specified and directed. Note:- The total thickness of sand shallbe measured 18 cm after punning. |
| 20 | Supply and laying un-reinforced precast.concrete cable protection cover of class LV, type-1, flat size 250mm x 150mm x 40 mm,factory madeof specified make , complete all as specified and directed. |
| 21 | M&L for replacement of new generation energy saving and environmental friendly long life LED street light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 60 watt complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including taking down of old unserviceable street light any type/any capacity including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to LED light throgh copper connectos all as specified and directed. Make :- Havells/Bajaj/Philips |
| 22 | Supply and laying galvanised tube light gradeISI marked of size 40 mm dia incl all fittingsin trenches/fixed on pole/wall/floor or laid in positioncomplete all as specified and directed. |
| 23 | M & L for road cutting incl necessary excavation 45 cm wide and90 cm in depth as in trenches in any type of soils/rock for laying LT UG cable throughpipeafter laying /through the cable trenches will be fillingtop withM&L PCC 1:3:6 type C-1 using 20 mm grdaeds stone aggregates from top over 15 cm thick hard good of broken boulders , 63 mm gauge over 15 cm bolders 100 mm dia over filled and rammed earth to make good the disburbedsurface etc complete all as specified and directed. |
| 24 | S & F in replacement of MCCB,04 Pole, capacity 63 Amps with ultimate breaking capacity 16 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%)in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make :- L&T/Havells/Indoasian |
| 25 | Description all as per item No 24 here in above but of capacity 100 Amps with ultimate breaking capacity 25 KA and ditto- |
| 26 | Description all as per item No 24 here in above but of capacity 160 Amps with ultimate breaking capacity 25 KA and ditto- |
| 27 | Description all as per item No 24 here in above but of capacity 250 Amps with ultimate breaking capacity 25 KA and ditto- |
| 28 | Description all as per item No 24 here in above but of capacity 400 Amps with ultimate breaking capacity 25 KA and ditto- |
| 29 | M&L fo replacement of TPN Kit Kat type rewireable main switch unit of 415 Volt 50 Hz three phase of capacity 100 Amp including MS box with backelite fuse & fuse carrier fittings , operating insulated handle, top cover necessary locking arrangemnts etc as per IS/IEC 60947 1&3 including necessary wall mounting fitting as directedincluding taking down the existing all as specified and directed. Make : INDOASIAN / L&T/Havells |
| 30 | Material & labour for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5mtr below the normal ground level connected to galvanised wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron.Earth wire protected by GI pipe 15 mm bore(medium grade) and connected to main switch board or main control board as directed and as specified and shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 40 cm x 40cm x 5cm reinforced with 8mm dia TMT bars @ 15cm C/C with one handle for liftingmade out of 8mm dia bar, funnel, wire mesh, 20mm dia GI pipe medium grade for watering, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil and testing complete all as directed by Engineer-in-Charge. |