| 1 | Cartage of following material from Store centre, Mathura to work site. |
| 2 | ST Pole/PCC Pole (11/9/8.5 mtr. Long) |
| 3 | 250 KVA T/F. |
| 4 | 11KV XLPE cable of size 3x300/240/185/120/70 Sq.mm. |
| 5 | 33 KV XLPE cable of size 3x300Sq.mm. |
| 6 | LT XLPE/PVC cable 1cx630/400/240 sq.mm. |
| 7 | ACSR Dog/Weasel/Ins. Weasel conductor |
| 8 | Other line material such as cross arm, MS top channel, bottom channel, Tee-channel, clamps, Suspension Clamp, Dead End Clamp, Cross Arm Holding Clamp, Danger Board, Pin Insulator, Disc Insulator nut & bolts etc. |
| 9 | Opening of Jumper, Connection & Earthing of Body and Neutral of 5 MVA Transformer and Dismantling of Neutral Earthing frame, cable frame. |
| 10 | Safe shifting of 5 MVA T/F. from Plinth to yard corner. |
| 11 | Re-fixing of 33 KV Cable, Jumper & Earthing (Neutral & Body Earthing connected by electric welding)., Erection of Neutral Earthing frame, Cable frame |
| 12 | Earthing of Power T/F |
| 13 | Water Level Earthing |
| 14 | Pipe in Pipe Gel Earthing |
| 15 | Digging of pit & erection of new Double STP 09 Mtr. Long for Chair Mounted Plinth Structure including grouting of pole and fixing of all clamps, cross arm, pin/disc insulator & other accessories with providing stone pad as per relevant drawings. Any fabrication if required for above support. |
| 16 | Digging of pit & erection of new Double ST/PCC Pole (11/9/8.5 mtr. long) including grouting of pole and fixing of all clamps, cross arm, pin/disc insulator & other accessories with providing stone pad as per relevant drawings. Any fabrication if required for above support. |
| 17 | Digging of pit & erection of new Single Pole 11 Mtr. Long for Tri Pole including grouting of pole and fixing of all clamps, channel, bracing,pin/disc insulator & other accessories with providing stone pad as per relevant drawings. Any fabrication if required for above support. |
| 18 | Earthing of ST/PCC pole/Body earthing of T/F. by M.S earth rod. |
| 19 | Painting of ST pole. |
| 20 | Digging of pit & erection of Stay rod with grouting cement sand and brick ballast including Nuzzling, binding Complete. |
| 21 | By Excavation land upto 6 mtr. and removing 33 KV XLPE Cable upto 50 mtr. |
| 22 | Laying of 33/11KV/LT line on Dog/weasel conductor on erected poles. |
| 23 | Laying of LT PVC/XLPE cable 1cx630/400/240 sq.mm. |
| 24 | Digging of trench by excavation of earth 0.90/1.5 Mtr. deep put brick on both side, filling of sand & brick on cable & earth ramming and dressing properly with complete job for laying 33/11 KV XLPE cable in trench |
| 25 | Laying of 33/11 KV XLPE cable in Trench/Double Pole structure & air and filling of cable jointing kit with proper dressing. |
| 26 | Installation of LT Protection System for Distribution T/F with all fittings |
| 27 | Providing & fixing of Aluminium Lug 70/150/240/400/630 |
| 28 | Straight Through for 33 KV Cable Underground |
| 29 | Jointing of cable with another cable/overhead line at the D/P structure through 33/11 KV outdoor & indoor cable jointing kit |
| 30 | Removal of old (250/160 KVA) transformer with all connected accessories from existing plinth. |
| 31 | Removal of old transformer(100/63/25/ 16 KVA) with all connected accessories from existing double pole. |
| 32 | Construction of Chair mounted plinth with fabrication & Angle clamp etc. |
| 33 | The Construction of new Plinth of Size 5’X5’X4’ aboveground level and one ft. below the ground level for 400/250 KVA transformer |
| 34 | Installation of following transformer on Plinth/Double pole with all connecting accessories jumering etc. including carriage of transformers from store centre, Mathura to work site. |
| 35 | 250 KVA Transformer on Plinth |
| 36 | Erection of Tail less unit complete |
| 37 | Construction of M.S angle fencing of size (3M x3M x2M) around the plinth of 400/250 KVA transformer and gap between the M.S angle should not be more than 65mm. |
| 38 | Complete chemical earthingof 11/0.4 KV 250/400 Distribution Transformer by digging pits 6” dia upto 3 mtr. deep including chemical filled pipe in between (pipe-in-pipe) ISI mark B Grade & connecting with G.I strip of size 50mm X 6mm with neutral/body of 11/0.4 KV distribution transformer to above pipe-in-pipe (PIP) and filling of chemical crystalline conductive mixture containing highly conductive material around the (pipe-in-pipe) up to 3 Mtr. including making of chamber at the top of the earthing. Other details are as below:-1.Earth pipe material – mild steel, Galvanised.2-Main Electrode diameter – 42.4mm.3-Auxiliary Electrode pipe, Diameter – 76mm.4-Wall Thickness of main Electrode :- 2.6mm.5-Wall thickness of auxiliary Ist whole:- 3.2mm.6- Length of earthing electrode (PIP):- 3 Meter. |
| 39 | Safe Carriage with Loading and unloading of Removed T/F and LT Cable from Work side to 132 KV S/S Store Center Mathura |
| 40 | Dismantling of 33/11KV line and cartage of material from work site to Store Centre, Mathura. |