| 1 | Supply installation testing and comissioning of three phase, 440 Volt ,50 Hz, 11.0 KW/15 HP, Submersible pump set suitable for 150 mmBorewellwith the Headrange of 29 Mtr to 64 Mtr etc as required. |
| 2 | Supplyingand fixing of one No. PVC insulated and PVC insulated and PC sheathed flat submersible cable copper conductor of 1100 V grade, ISI marked , 3-core 4 sqmm in pipe /surface/ alongwith column pipe complete with jointing etc as required. |
| 3 | Lowring of three phase, 440 Volt ,50 Hz, 11.0 KW/15 HP, Submersible pump set suitable for 150 mmBorewellwith the Headrange of of 29 Mtr to 64 Mtr etc as required |
| 4 | S/F following size U-PVC column pipe schedule(Super heavy) complete with socket, ISI marked, heavy duty, in the suction / delivery line i/c cutting , threading etc as required. 80 MM |
| 5 | S/F 10 mm dia, PVC coated safety steel rope complete withU clamp & bolt as per directions of engineer in charge as required. |
| 6 | S/Fixing pipe holding MS clamp for holding of 80 mm dia upvc pipe complete with bolt nut washers etc complete etc as reqd. |
| 7 | S/F upvc column T & B adapter set including complete with threading etc as required. |
| 8 | S/Fixing MS well cover 12\"x3\"for existing borewell (300 mm dia) i/c painting etc as reqd. |
| 9 | Supplying and fixing of 80 mm dia Gun metal ISI marked gate valve screwed type as per IS:- 778 on the existing pipe line i/c connection testing etc. as reqd. |
| 10 | Supplying and fixing 150 mm dia pressure gauge of, 0-300 PSI or 0-14 kg per cm squire fitted with 12/15 mm dia. Pad cock valve, G.I. pipe elbow etc. complete i/c connection testing etc. as reqd. |
| 11 | Providing and Fixing 80 mm dia, with Long G.I. Socketof class \"B\" medium duty GI pipe confirming to IS: 1239 complete into P/F fittings and accessories like elbow, tee, flanges, bend, coupler, nut & bolts, gasket etc. on the surface complete including saddless etc. as reqd |
| 12 | Supplying, Installation, testing & Commissioning of water protected, dust and vermin proof, compartmentalized type double door cubical panel having 350 mm deep suitable for outdoor installation use on 415 Volts, 50 Hz AC supply with 4 strip aluminum bus bar 100 amp capacity duly PVC sleeved, made out of2 mm thick CRCA sheet with hardware duly painted with powder coated.Panel having two earth bar/stud earthing wire/strip, ventilation louver\"s, separate sectionalized detachable gland plates, din bar, LED light, suitable water tight gasket, interconnections with solid copper conductor cable 10 sq mm, complete on suitable MS frame made of 50 mm x 50 mm x 6 mm thick and along to be embedded in cement concrete foundation (1:3:6) 600 mm above ground level suitable for incorporating incoming & outgoing switch gear, etc locking arrangement, paintings, concrete as required.( panel should be as per design and drawing approved by the Engineer in charge) |
| 13 | Providing and fixing of 63 A, 30 KA, TP MCCB, Ics =100% Icuas per IEC 60947-2 with adjustable overload setting and short sircuit setting etc as required. |
| 14 | Providing and fixing three phase, 415 Volt 50 Hz, Fully automatic Star-Delta starter suitable up to 15 HP motor operation, Relay range 09-14 Amp, with inbuilt Ammeter & voltmeter with 25 Amp capacity contactor, ON/OFF indication i/c connections, interconnection and earthing etc complete with power coated sheet encloser in single door etc as required. |
| 15 | Providing of three phase, 415 Volt 50 Hz, Fully automatic Star-Delta starter suitable up to 15 HP motor operation, Relay range 09-14 Amp, with inbuilt Ammeter & voltmeter with 25 Amp capacity contactor, ON/OFF indication i/c connections, interconnection and earthing etc complete with power coated sheet encloser in single door etc as required. (Standby) |
| 16 | Supplying and laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of alluminume armoured 3.5x35 sqmm direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 17 | Providing and laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size armoured alluminume conductorin the existing masonry open duct/on air/along the existing pole as required. 3.5x35 sq. mm |
| 18 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. ( 3½ X 35 sq. mm (32mm) |
| 19 | Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. ( 3½ X 35 sq. mm) |
| 20 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 21 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |